MINI MCR-2-UI-I-OLP(-PT)(-C)
Output loop-powered 2-way isolator
Data sheet
106298_en_02
1
© PHOENIX CONTACT 2016-02-29
Description
The 2-way output loop-powered isolator with plug-in
connection technology, which can be configured using DIP
switches, is used for the electrical isolation, conversion, and
filtering of unipolar and bipolar standard and normalized
signals.
The device allows operation on an active analog input
module.
The device is powered via the current loop of the controller.
Features
–
–
–
–
–
Output loop-powered 2-way isolator with plug-in
connection technology
Approval for Ex-zone 2 (nA)
74 input ranges can be set via DIP switches
Screw or push-in connection available
Reinforced insulation according to IEC 61010-1
On the input side, standard analog signals and nonstandard analog signals can be connected, ranging from
2 mA or 50 mV up to 40 mA or 30 V. These are converted to
a 4 mA ... 20 mA signal.
There is no need for adjustment following a measuring
range changeover.
WARNING: Correct usage in potentially explosive areas
The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided
here during installation and observe the information in the "Safety regulations and installation notes".
This device offers the option of NFC communication.
You can use the MINI Analog Pro Smartphone app to call-up DIP switch setting help and comprehensive
module information via the NFC interface of your Smartphone.
The MINI Analog Pro Smartphone app is available to you free.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
This document is valid for the products listed in the “Ordering data”.
MINI MCR-2-UI-I-OLP(-PT)(-C)
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 5
5
Safety regulations and installation notes.................................................................................. 8
5.1
Installation notes ................................................................................................................. 8
5.2
Installation in Zone 2............................................................................................................. 8
5.3
UL Notes ........................................................................................................................... 8
6
Installation ............................................................................................................................... 9
6.1
Connection notes ................................................................................................................ 9
6.2
Structure ........................................................................................................................... 9
6.3
Block diagram ..................................................................................................................... 9
6.4
Power supply ...................................................................................................................... 9
6.5
Assembly........................................................................................................................... 9
6.6
FASTCON Pro plugs .......................................................................................................... 10
6.7
Current measurement ......................................................................................................... 10
6.8
Marking ........................................................................................................................... 10
7
Configuration ......................................................................................................................... 11
8
Status indicator...................................................................................................................... 12
106298_en_02
PHOENIX CONTACT 2 / 12
MINI MCR-2-UI-I-OLP(-PT)(-C)
3
Ordering data
Description
Type
Order No.
Pcs./Pkt.
Output loop-powered 2-way isolator with plug-in connection technology for
the electrical isolation of unipolar and bipolar analog signals. Input
configurable via DIP switch. Screw connection technology, standard
configuration.
MINI MCR-2-UI-I-OLP
2902061
1
Output loop-powered 2-way isolator with plug-in connection technology for
the electrical isolation of unipolar and bipolar analog signals. Input
configurable via DIP switch. Push-in connection technology, standard
configuration.
MINI MCR-2-UI-I-OLP-PT
2902063
1
Output loop-powered 2-way isolator with plug-in connection technology for
the electrical isolation of unipolar and bipolar analog signals. Input
configurable via DIP switch. Screw connection technology, order
configuration.
MINI MCR-2-UI-I-OLP-C
2902060
1
Output loop-powered 2-way isolator with plug-in connection technology for
the electrical isolation of unipolar and bipolar analog signals. Input
configurable via DIP switch. Push-in connection technology, order
configuration.
MINI MCR-2-UI-I-OLP-PT-C
2902062
1
Accessories
Type
Order No.
Pcs./Pkt.
Marker for end clamp, Sheet, white, unlabeled, can be labeled with:
THERMOMARK CARD, BLUEMARK CLED, BLUEMARK LED,
TOPMARK LASER, Mounting type: snapped into marker carrier, Lettering
field: 30 x 5 mm
UCT-EM (30X5)
0801505
10
Marker for end clamp, can be ordered: by sheet, white, labeled according
to customer specifications, Mounting type: snapped into marker carrier,
Lettering field: 30 x 5 mm
UCT-EM (30X5) CUS
0801589
1
Marker for end clamp, Sheet, yellow, unlabeled, can be labeled with:
THERMOMARK CARD, BLUEMARK CLED, BLUEMARK LED,
TOPMARK LASER, Mounting type: snapped into marker carrier, Lettering
field: 30 x 5 mm
UCT-EM (30X5) YE
0830340
10
Marker for end clamp, can be ordered: by sheet, yellow, labeled according
to customer specifications, Mounting type: snapped into marker carrier,
Lettering field: 30 x 5 mm
UCT-EM (30X5) YE CUS
0830348
1
Plastic label, Sheet, white, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5)
0819301
10
Plastic label, Sheet, white, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5)L
0820138
5
Plastic label, Sheet, yellow, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5) YE
0822615
10
Plastic label, can be ordered: by sheet, white, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5) CUS
0824550
1
Plastic label, can be ordered: by sheet, yellow, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5) YE CUS
0824551
1
Plastic label, can be ordered: by sheet, white, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5)L CUS
0824552
1
Plastic label, Sheet, yellow, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5)L YE
0825325
5
Plastic label, can be ordered: by sheet, yellow, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5)L YE CUS
0826680
1
106298_en_02
PHOENIX CONTACT 3 / 12
MINI MCR-2-UI-I-OLP(-PT)(-C)
Accessories
Type
Order No.
Pcs./Pkt.
Plastic label, Sheet, silver, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5) SR
0828095
10
Plastic label, can be ordered: by sheet, silver, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5) SR CUS
0828099
1
Plastic label, Sheet, silver, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5)L SR
0828103
5
Marker strip, Roll, white, unlabeled, can be labeled with: THERMOMARK
ROLL, THERMOMARK X, THERMOMARK S1.1, THERMOMARK ROLL
X1, Mounting type: Adhesive, Lettering field: continuous x 5 mm
SK 5,0 WH:REEL
0805221
1
106298_en_02
PHOENIX CONTACT 4 / 12
MINI MCR-2-UI-I-OLP(-PT)(-C)
4
Technical data
Input
Configurable/programmable
Yes
Voltage input signal
0 mV ... 1000 mV
0 mV ... 750 mV
0 mV ... 500 mV
0 mV ... 300 mV
0 mV ... 250 mV
0 mV ... 200 mV
0 mV ... 125 mV
0 mV ... 120 mV
0 mV ... 150 mV
0 mV ... 100 mV
0 mV ... 75 mV
0 mV ... 60 mV
0 mV ... 50 mV
0 V ... 10 V
0 V ... 7.5 V
0 V ... 5 V
0 V ... 3 V
0 V ... 2.5 V
0 V ... 2 V
0 V ... 1.5 V
0 V ... 1.25 V
0 V ... 1.2 V
0 V ... 30 V
0 V ... 25 V
0 V ... 20 V
0 V ... 12.5 V
0 V ... 12 V
0 V ... 15 V
-1000 mV ... 1000 mV
-750 mV ... 750 mV
-500 mV ... 500 mV
-300 mV ... 300 mV
-250 mV ... 250 mV
-200 mV ... 200 mV
-125 mV ... 125 mV
-120 mV ... 120 mV
-150 mV ... 150 mV
-100 mV ... 100 mV
-75 mV ... 75 mV
-60 mV ... 60 mV
-50 mV ... 50 mV
-10 V ... 10 V
-7.5 V ... 7.5 V
-5 V ... 5 V
-3 V ... 3 V
-2.5 V ... 2.5 V
-2 V ... 2 V
-1.25 V ... 1.25 V
-1.2 V ... 1.2 V
-1.5 V ... 1.5 V
-30 V ... 30 V
-25 V ... 25 V
-20 V ... 20 V
-12.5 V ... 12.5 V
-12 V ... 12 V
1 V ... 5 V
1 V ... 5 V
Max. voltage input signal
< 30 V
106298_en_02
PHOENIX CONTACT 5 / 12
MINI MCR-2-UI-I-OLP(-PT)(-C)
Input
Current input signal
0 mA ... 0.04 A
0 mA ... 0.03 A
0 mA ... 0.02 A
0 mA ... 0.012 A
0 mA ... 0.01 A
0 mA ... 0.008 A
0 mA ... 0.0075 A
0 mA ... 0.005 A
0 mA ... 0.006 A
0 mA ... 0.004 A
0 mA ... 0.003 A
0 mA ... 0.0025 A
0 mA ... 0.002 A
4 mA ... 0.02 A
2 mA ... 0.01 A
1 mA ... 0.005 A
Max. current input signal
< 40 mA (Dielectric strength up to 30 V)
Input resistance of voltage input
approx. 100 kΩ (At ≤ 1 V, otherwise approximately 1 MΩ)
Input resistance current input
≤ 50 Ω
Output
Current output signal
4 mA ... 0.02 A
Max. current output signal
29 mA
Ripple
< 20 mVPP (at 600 Ω)
Load/output load current output
(UB - 8 V) / 22 mA
Supply
Supply voltage range
8 V DC ... 30 V DC (no separate supply voltage necessary)
Typical current consumption
≤ 20 mA
Power consumption
≤ 600 mW
Diagnostic and status indicators
Operating voltage display
Green LED
General data
Limit frequency (3 dB)
approx. 30 Hz
Maximum transmission error
< 0.1 % (of final value)
Temperature coefficient, typical
0.005 %/K
Maximum temperature coefficient
0.01 %/K
Step response (10-90%)
15 ms
Electrical isolation
Reinforced insulation in accordance with IEC 61010-1
Overvoltage category
II
Mounting position
any
Degree of protection
IP20
Degree of pollution
2
Rated insulation voltage
300 V (effective)
Test voltage, input/output/supply
3 kV (50 Hz, 1 min.)
Dimensions W/H/D
6.2 mm / 110.5 mm / 120.5 mm
Type of housing
PBT gray
106298_en_02
PHOENIX CONTACT 6 / 12
MINI MCR-2-UI-I-OLP(-PT)(-C)
Connection data
Screw connection
Push-in connection
Solid conductor cross section with ferrule
0.2 mm² ... 1.5 mm²
0.14 mm² ... 2.5 mm²
Solid conductor cross section without ferrule
0.2 mm² ... 2.5 mm²
0.14 mm² ... 2.5 mm²
Conductor cross section, flexible
0.2 mm² ... 1.5 mm²
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12
24 ... 12
Stripping length
10 mm
10 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Conformance with EMC Directive 2004/108/EC (valid until 19.04.2016) / 2014/30/EU (valid from 20.04.2016)
Noise immunity according to EN 61000-6-2
When being exposed to interference, there may be minimal deviations.
Noise emission according to EN 61000-6-4
Conformance / approvals
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada
UL 508 Listed
UL, USA / Canada
Class I, Div. 2, Groups A, B, C, D T5
UL, USA / Canada
Class I, Zone 2, Group IIC T5
Shipbuilding DNV GL 14085-15HH
D, EMC1
106298_en_02
PHOENIX CONTACT 7 / 12
MINI MCR-2-UI-I-OLP(-PT)(-C)
5
Safety regulations and installation notes
5.1
Installation notes
•
•
•
•
•
•
•
•
•
•
•
The category 3 device is suitable for installation in
potentially explosive area zone 2. It fulfills the
requirements of EN 60079-0:2012 and EN 6007915:2010.
Installation, operation, and maintenance may only be
carried out by qualified electricians. Follow the
installation instructions as described. When installing
and operating the device, the applicable regulations
and safety directives (including national safety
directives), as well as generally approved technical
regulations, must be observed. The safety data is
provided in this package slip and on the certificates
(conformity assessment, additional approvals where
applicable).
While the devices are in operation, contact-dangerous
voltages may be present on the control elements. For
this reason parameterization, conductor connection,
and opening of the module lid are allowed only when
devices are in a de-energized state unless the
connected circuits are exclusively SELV or PELV
circuits.
The device must not be opened or modified. Do not
repair the device yourself, replace it with an equivalent
device. Repairs may only be carried out by the
manufacturer. The manufacturer is not liable for
damage resulting from violation.
The IP20 protection (IEC 60529/EN 60529) of the
device is intended for use in a clean and dry
environment. The device must not be subject to
mechanical strain and/or thermal loads, which exceed
the limits described.
The device is not designed for use in atmospheres with
a danger of dust explosions.
The device complies with the EMC regulations for
industrial areas (EMC class A). When using the device
in residential areas, it may cause radio interference.
If the device is not used as described in the
documentation, the intended protection can be
negatively affected.
To protect the device against mechanical or electrical
damage, install it in a suitable housing with appropriate
degree of protection as per IEC 60529.
Provide a switch/circuit breaker close to the device,
which is labeled as the disconnecting device for this
device.
Provide for a overcurrent protection device (I ≤ 4 A) in
the installation.
106298_en_02
•
•
•
•
5.2
•
•
•
•
5.3
There is a double isolation of 300 Veff between
neighboring modules of the same type oriented the
same way. The device has a base isolation of 150 Veff
to other neighboring modules on the side with the DIP
switch.
The voltages present at the input, output and supply are
extra-low voltages (ELV). Depending on the
application, dangerous voltage (> 30 V) against ground
could occur. For this event, safe electrical isolation from
the other connections has been implemented.
The device must be stopped if it is damaged, has been
subjected to an impermissible load, stored incorrectly,
or if it malfunctions.
Only use copper connecting cables providing the
permitted temperature range (60°C/75°C).
Installation in Zone 2
Observe the specified conditions for use in potentially
explosive areas! Install the device in a suitable
approved housing (with a minimum of IP54 protection)
that meets the requirements of EN 60079-15. Observe
the requirements of EN 60079-14.
Only devices which are designed for operation in Ex
zone 2 and are suitable for the conditions at the
installation location may be connected to the circuits in
the Ex zone.
In potentially explosive areas, terminals may only be
snapped onto or off the DIN rail connector and wires
may only be connected or disconnected when the
power is switched off.
The device must be stopped and immediately removed
from the Ex area if it is damaged, was subject to an
impermissible load, stored incorrectly or if it
malfunctions.
UL Notes
INDUSTRIAL CONTROL EQUIPMENT FOR
HAZARDOUS LOCATIONS 45FP
1 Suitable for use in class 1, division 2, groups A, B, C and
D hazardous locations, or nonhazardous locations only.
2 WARNING - EXPLOSION HAZARD: Do not disconnect
equipment unless power has been removed or the area
is known to be non-hazardous.
3 WARNING - EXPLOSION HAZARD: Substitution of any
components may impair suitability for Class I, Division
2.
4 This device is open-type and is required to be installed
in an enclosure suitable for the environment and can
only be accessed with the use of a tool or key.
PHOENIX CONTACT 8 / 12
MINI MCR-2-UI-I-OLP(-PT)(-C)
6.3
6
Installation
6.1
Connection notes
Block diagram
The device contains components that can be
damaged or destroyed by electrostatic
discharge. When handling the device,
observe the necessary safety precautions
against electrostatic discharge (ESD)
according to EN 61340-5-1 and IEC 61340-51.
OUT I+
US
2
– 2
3
+ 3
OUT U+
4-wire
OUT U-
6.2
TI–
+ 1
1
4-wire
OUT I-
US
OUT
IN
Sensor / Field
4
– 4
IN I+
PLC / DCS
TI+
5 +
PWR In
passive
OUT I
IN I–
5
6 –
6
PWR
active
7
IN U+
8
IN U–
Structure
2
1
PWR
1
2
3
4
10
Zone 2
3
8
7
6
5
4
y
an
rm
Ge LP
rg, I-I-O
be
1 ioner
lom 2-U 06
it
5 B CR- 02 ond
2
8
9
c
M 2
32
al
9
Figure 2
6.4
.:
n
DC
NI No sig
0V
MIOrd.- ered
+/-3
p to
ow
Cu A
pp
loo 0mV D 40m
t
to
tpu
°F
+/-5A up
Ou
158
U: 0m 0mADC 0°...+
IN I:
4...2 0V / -4
IN T: p: 8...3.+70°C
..
o
°
U
0
o
O L -4
Block diagram
Power supply
The device is powered via the current loop of the controller.
5
T I+
OU
1
Tamb
6.5
Assembly
US
ire
4-w
T I-
TI-
2 OU
+
1
IN
T I+
I+
+
+
ss
U+
sepa
IN
4
rate w
0
XX
6
ww
w.p
hoe
nixc
For User
om
X
d
QR
de
Co
ergize
ct.c
S1
Gc
G
II 3 IIC T4
A
Ex n
8
onta
hen en
IN
U-
7
8
T I-
4 OU
3
I
ire
4-w
F
o not
6 OUT
OF
1
ng-D
-
R IN
PW ive
pa
5
R
PWtice
6
ac
ON 3
I-
Warni
IN
5
US
OU
2
TI+
7
Figure 3
Mounting and removing
!
–
Figure 1
1
2
3
4
5
6
7
8
9
10
Structure
Green “PWR” LED, power supply
Cover with labeling option
Current input
DIP switch S1
Voltage input
NFC coil
Universal snap-on foot for EN DIN rails
Spindle screw
Current output
Current measuring socket
106298_en_02
Mount the module on a 35 mm DIN rail according to EN
60715.
An ME 6,2 TBUS-2 DIN rail connector (Order No.: 2869728)
is used to supply active devices. A DIN rail connector is not
necessary for operation of this loop-powered device.
This device can be snapped onto a DIN rail connector – an
electrically conductive connection is not established. This
means that you do not need to disconnect an existing DIN
rail connector element connection.
PHOENIX CONTACT 9 / 12
MINI MCR-2-UI-I-OLP(-PT)(-C)
6.6
FASTCON Pro plugs
6.7
Current measurement
The device has pluggable connection terminals with an
integrated test disconnect terminal block, with either push-in
or screw-in connection technology.
The device allows current measurement without
disconnection of the conductors by means of integrated test
disconnect terminals.
You can plug or screw the FASTCON Pro plugs onto the device directly
without tools. You can use the integrated spindle screw to easily remove
the plugs from the module or set the isolating position, even when the
plugs are connected. For this purpose, use a screwdriver of sufficient
width, e.g. SZF 1-0.6x3.5 (order number: 1204517).
Test sockets which support current measurement are
marked TI+ or TI-.
For the current measurement, use 2 mm probe tips of the
type Fluke TL75-1 or probe tips with a comparable tip shape.
The spindle screw will turn by itself when the FASTCON Pro
plugs are connected. There is no need for you to fix the
spindle screw in place as well.
4-way coding prevents incorrect insertion into the module.
Screw connection:
AWG 26-16
2
0,2-1,5 mm
MINI MCR-2-…
B
A
Figure 4
•
•
10 mm
Figure 6
0,5-0,6 Nm
5-7 lb ln
Screw connection
Test disconnect terminal block
Furthermore, individual circuits can be specifically
disconnected, e.g. for commissioning.
You can set the isolating position by turning the integrated
spindle screw through 180°. The isolating position is
indicated by the marking on the plugs.
Insert the wire into the corresponding connection terminal block.
Use a screwdriver to tighten the screw in the opening
above the connection terminal block.
Push-in connection:
AWG 26-12
0,2-2,5 mm2
MINI MCR-2-…-PT
A
10 mm
Figure 7
6.8
A
Figure 5
•
B
Push-in connection
Disconnect position
Marking
Standard UCT-EM... or UC-EMLP tags are available for
marking the devices and can be printed as per customer
requirements. In addition, the covers provide enough space
for the use of freely chosen sticky labels such as SK 5.0
WH:REEL without concealing the LED diagnostic
indicators.
Insert the wire into the corresponding connection terminal block.
106298_en_02
PHOENIX CONTACT 10 / 12
MINI MCR-2-UI-I-OLP(-PT)(-C)
7
Configuration
Standard configuration for devicesnot configured to order:
Input 2...10 V, output 4...20 mA (all DIP switches in the "off"
position; transmission error < 0.1%).
Using DIP switch S1, specify the combination of input and
output standard signal ranges.
IN
unipolar
0 ... 2 mA
0 ... 2.5 mA
0 ... 3 mA
0 ... 4 mA
0 ... 5 mA
0 ... 6 mA
0 ... 7.5 mA
0 ... 8 mA
0 ... 10 mA
0 ... 12 mA
0 ... 20 mA
0 ... 30 mA
0 ... 40 mA
• = ON
DIP S1
Live zero
1 2 3 4 5 6 7
• •
• •
•
•
•
•
•
•
• •
1 ... 5 mA
• • •
•
•
•
2 ... 10 mA
• •
•
4 ... 20 mA
•
bipolar
Terminal
8 9 0
•
•
•
•
•
•
0 ... 50 mV
0 ... 60 mV
0 ... 75 mV
0 ... 100 mV
0 ... 120 mV
0 ... 125 mV
0 ... 150 mV
0 ... 200 mV
0 ... 250 mV
0 ... 300 mV
0 ... 500 mV
0 ... 750 mV
0 ... 1000 mV
0 ... 1.2 V
0 ... 1.25 V
0 ... 1.5 V
0 ... 2 V
0 ... 2.5 V
0 ... 3 V
0 ... 5 V
0 ... 7.5 V
0 ... 10 V
0 ... 12 V
0 ... 12.5 V
0 ... 15 V
0 ... 20 V
0 ... 25 V
0 ... 30 V
±50 mV
±60 mV
±75 mV
±100 mV
±120 mV
±125 mV
±150 mV
±200 mV
±250 mV
±300 mV
±500 mV
±750 mV
±1000 mV
±1.2 V
±1.25 V
±1.5 V
±2 V
±2.5 V
±3 V
±5 V
±7.5 V
±10 V
±12 V
±12.5 V
±15 V
±20 V
±25 V
±30 V
Signal
conversion
IN bipolar
IN unipolar
IN Live zero
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
1 ... 5 V
•
•
•
2 ... 10 V
•
•
•
•
•
•
/
/
/
•
•
•
•
•
•
•
•
•
•
•
•
OUT Live zero (4 ... 20 mA)
OUT Live zero (4 ... 20 mA)
OUT Live zero (4 ... 20 mA)
•
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
•
•
Additional signal combinations that are not
listed in the table are available on request.
106298_en_02
PHOENIX CONTACT 11 / 12
MINI MCR-2-UI-I-OLP(-PT)(-C)
8
Status indicator
Green LED
106298_en_02
PWR
Lit
Supply voltage
Supply voltage present
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com