Energy measurement device to measure electrical parameters in low voltage installations up to 700 V, acquisition
of individual harmonic oscillations - can be extended with communication and special functional modules
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4046356657136
Weight per Piece (excluding packing)
800.000 g
Custom tariff number
90303100
Country of origin
Tunisia
Technical data
Dimensions
Width
96 mm
Height
96 mm
Depth
82 mm
Installation depth with extension module
80 mm
Installation depth without extension module
60 mm
Ambient conditions
Ambient temperature (operation)
-10 °C ... 55 °C (14 °F to 131 °F)
Ambient temperature (storage/transport)
-20 °C ... 85 °C (-4 °F ... 185 °F)
Max. permissible relative humidity (operation)
≤ 95 %
Max. salt spray content
≤ 2.5 %
Degree of protection
IP52 (Front)
09/12/2019 Page 1 / 7
https://www.phoenixcontact.com/us/products/2902352
Measuring instrument - EEM-MA600-24DC - 2902352
Technical data
Ambient conditions
IP30 (Back side)
Input data
Measuring principle
True r.m.s. value measurement
Acquisition of harmonics
up to 63rd harmonic
Measured value
AC sine (50/60 Hz)
Input name
Voltage measuring input V1, V2, V3
Input voltage range
18 V AC ... 700 V AC (Phase/Phase)
11 V AC ... 404 V AC (Phase/neutral conductor)
Input voltage
500 kV AC (Primary, via external voltage transducers)
Secondary: 60, 100, 110, 115, 120, 173, 190 V AC
Precision
0.2 %
Input name
Current measuring input I1, I2, I3
Input current range
via external transformers
Input current
9999 A (primary)
1 A and 5 A, secondary
Current measuring range
0 A ... 9999 A
Overload capacity
6 A (Permanent)
Response threshold from measuring range nominal value
10 mA
Precision
0.2 %
Current overload
10 x IN for 1 s
Messbereich_Leistung
0 MW ... 8000 MW
0 Mvar ... 8000 Mvar
0 MVA ... 8000 MVA
Precision
0.5 %
Active energy (IEC 62053-22)
Class 0.5 S
Reactive power (IEC 62053-23)
Class 2
Voltage input signal
Via extension module
Output data
Output description
via extension module
Interfaces
Designation
Via extension module
General
Display
LCD display, backlighting
Measuring rate
approximately
Supply voltage
24 V DC
09/12/2019 Page 2 / 7
https://www.phoenixcontact.com/us/products/2902352
Measuring instrument - EEM-MA600-24DC - 2902352
Technical data
General
Supply voltage range
12 V DC ... 48 V DC -6 % ... +20 %
Nominal power consumption
10 VA
Power consumption
20 VA (with max. number of extension modules)
Mains type
3-phase (3 or 4-wire), 2-phase (2-wire), and single-phase (1-wire)
Color
black
Conformance
CE-compliant
Test voltage
3.5 kV AC (50 Hz, 1 min.)
UL data
Nominal supply voltage range
12 V DC ... 48 V DC -6 % ... +20 %
Power consumption
10 VA
Operating mode
Indoor use
Surge voltages
Transient overvoltage according to installation classes
Overvoltage category
I, II, III
Overvoltage category of the supply
Min. II
Altitude
≤ 2000 m
Ambient temperature (operation)
0 °C ... 40 °C
Max. permissible relative humidity (operation)
80 % (up to 31°C)
50 % (at 40 °C)
Standards and Regulations
Conformance
CE-compliant
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Classifications
eCl@ss
eCl@ss 4.0
27210900
eCl@ss 4.1
27210900
eCl@ss 5.0
27210900
eCl@ss 5.1
27210900
eCl@ss 6.0
27142300
eCl@ss 7.0
27142330
eCl@ss 8.0
27142330
eCl@ss 9.0
27142330
09/12/2019 Page 3 / 7
https://www.phoenixcontact.com/us/products/2902352
Measuring instrument - EEM-MA600-24DC - 2902352
Classifications
ETIM
ETIM 4.0
EC002301
ETIM 5.0
EC002301
ETIM 6.0
EC002301
ETIM 7.0
EC002301
UNSPSC
UNSPSC 6.01
30211916
UNSPSC 7.0901
39121535
UNSPSC 11
39121535
UNSPSC 12.01
39121535
UNSPSC 13.2
39121535
Approvals
Approvals
Approvals
UL Listed / cUL Listed / EAC / cULus Listed
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 357804
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 357804
EAC
RU *DE.A*30.B.01628
09/12/2019 Page 4 / 7
https://www.phoenixcontact.com/us/products/2902352
Measuring instrument - EEM-MA600-24DC - 2902352
Approvals
cULus Listed
Accessories
Accessories
Assembly adapter
DIN rail adapter - EEM-MKT-DRA - 2902078
DIN rail adapter for EEM-MA600 and EEM-MA400 energy meters
Communication module
Communication module - EEM-RS485-MA600 - 2901367
RS-485 JBUS/MODBUS communication module for EEM-MA600
Communication module - EEM-PB-MA600 - 2901368
PROFIBUS (1.5 Mbps) communication module for EEM-MA600
Communication module - EEM-PB 12-MA600 - 2901418
PROFIBUS (12 Mbps) communication module for EEM-MA600
09/12/2019 Page 5 / 7
https://www.phoenixcontact.com/us/products/2902352
Measuring instrument - EEM-MA600-24DC - 2902352
Accessories
Communication module - EEM-ETH-MA600 - 2901373
Ethernet communication module for the EEM-MA600 with integrated web server
Communication module - EEM-ETH-RS485-MA600 - 2901374
Gateway RS-485/Ethernet communication module for the EEM-MA600 with integrated web server
Function module
Special function module - EEM-MEMO-MA600 - 2901370
Storage module for intermediate storage of values for EEM-MA600
Special function module - EEM-2DIO-MA600 - 2901371
Special functional module with two digital inputs and outputs for EEM-MA600
Special function module - EEM-2AO-MA600 - 2901475
Special functional module with two analog outputs (0–20/4-20mA) for EEM-MA600
09/12/2019 Page 6 / 7
https://www.phoenixcontact.com/us/products/2902352
Phoenix Contact 2019 © - all rights reserved
http://www.phoenixcontact.com
09/12/2019 Page 7 / 7
很抱歉,暂时无法提供与“2902352”相匹配的价格&库存,您可以联系我们找货