MINI MCR-SL-CVS-24-5-10-NC
Constant voltage source
Data sheet
105264_en_01
1
© PHOENIX CONTACT 2013-04-03
Description
Configurable constant voltage source for generating highprecision constant voltages.
The voltage supply is also the input voltage. It is between
9.6 V DC and 30 V DC. The DIP switches accessible from
the side of the housing allow configuration of the 10 V DC,
7.5 V DC, 5 V DC and 2.5 V DC output voltages.
Features
–
–
–
Configurable constant voltage source
Approval for Ex-zone 2 (nA)
Screw or spring-cage connection can be provided
Output and supply (input) are are electrically isolated from
one another.
NOTE: Correct usage in potentially explosive areas
The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided
here during installation and observe the information in the "Safety regulations and installation notes".
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
This data sheet is valid for all products listed on the following page:
MINI MCR-SL-CVS-24-5-10-NC
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 4
5
Safety regulations and installation notes.................................................................................. 6
5.1
Installation notes ................................................................................................................. 6
5.2
Installation in the Ex area (zone 2)............................................................................................ 6
6
Installation ............................................................................................................................... 7
6.1
Structure ........................................................................................................................... 7
6.2
Block diagram ..................................................................................................................... 7
6.3
Power supply ...................................................................................................................... 7
6.4
Assembly........................................................................................................................... 8
6.5
Connecting the wires ............................................................................................................ 8
7
Configuration ........................................................................................................................... 9
7.1
Configuration table ............................................................................................................... 9
8
Adjustment .............................................................................................................................. 9
105264_en_01
PHOENIX CONTACT
2
MINI MCR-SL-CVS-24-5-10-NC
3
Ordering data
Description
Type
Order No.
Pcs. / Pkt.
Constant voltage source, input voltage 9.6 - 30 V DC, output voltage 10 V,
7.5 V, 5 V, 2.5 V DC, electrically isolated, can be configured via DIP
switches, screw connection technology, standard configuration
MINI MCR-SL-CVS-24-5-10-NC
2902822
1
Constant voltage source, input voltage 9.6 - 30 V DC, output voltage 10 V,
7.5 V, 5 V, 2.5 V DC, electrically isolated, can be configured via DIP
switches, spring cage connection technology, standard configuration
MINI MCR-SL-CVS-24-5-10-SP-NC
2902823
1
Constant voltage source, input voltage 9.6 - 30 V DC, output voltage 10 V,
7.5 V, 5 V, 2.5 V DC, electrically isolated, can be configured via DIP
switches, spring cage connection technology, standard configuration
MINI MCR-SL-CVS-24-5-10-SP-NC
2902823
1
Accessories
Type
Order No.
Pcs. / Pkt.
DIN rail connector (TBUS), 5-pos., for bridging the supply voltage, can be
snapped onto NS 35/... DIN rails according to EN 60715
ME 6,2 TBUS-2 1,5/5-ST-3,81 GN
2869728
10
MCR power terminal block for supplying several MINI Analog modules via
the T-connector, with screw connection, maximum current consumption of
up to 2 A
MINI MCR-SL-PTB
2864134
1
MCR power terminal block for supplying several MINI Analog modules via MINI MCR-SL-PTB-SP
the T-connector, with spring-cage connection, maximum current consumption of up to 2 A
2864147
1
DIN rail power supply unit, primary-switched mode, slim design, output: 24
V DC / 1.5 A
MINI-SYS-PS-100-240AC/24DC/1.5
2866983
1
DIN rail power supply unit, primary-switched mode, slim design, output: 24
V DC / 1.5 A, ATEX approval
MINI-PS-100-240AC/24DC/1.5/EX
2866653
1
Eight MINI analog signal converters with screw connection method can be
connected to a control system using a system adapter and system cabling
with a minimum of wiring and very low error risk.
MINI MCR-SL-V8-FLK 16-A
2811268
1
Fold up transparent cover for MINI MCR modules with additional labeling
option using insert strips and flat Zack marker strip 6.2 mm
MINI MCR DKL
2308111
10
Label for extended marking of MINI MCR modules in connection with the
MINI MCR-DKL
MINI MCR-DKL-LABEL
2810272
10
105264_en_01
PHOENIX CONTACT
3
MINI MCR-SL-CVS-24-5-10-NC
4
Technical data
Input
Voltage input signal
9.6 V DC ... 30 V DC
Output
Max. voltage output signal
10 V DC
7.5 V DC
5 V DC
2.5 V DC
Configurable/programmable
Yes, preconfigured
Short-circuit current
approx. 32 mA
Ripple
< 20 mVPP
Supply
Nominal supply voltage
24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order
No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a
35 mm DIN rail according to EN 60715))
Max. current consumption
< 25 mA (10 V output with 30 mA load at 24 V DC IN)
< 65 mA (10 V output with 30 mA load at 9.6 V DC IN)
< 50 mA (10 V voltage output with 30 mA load at 12 V DC IN)
< 20 mA (10 V voltage output with 30 mA load at 30 V DC IN)
Power consumption
< 600 mW (at 24 V IN)
< 624 mW (at 9.6 V IN)
< 564 mW (At 12 V IN)
< 540 mW (At 30 V IN)
General data
Maximum transmission error
≤ 0.1 % (of final value)
≤ 0.5 % (Without adjustment)
Temperature coefficient, typical
< 0.002 %/K
Maximum temperature coefficient
< 0.01 %/K
Electrical isolation
Basic insulation according to EN 61010
Surge voltage category
II
Mounting position
Any
Degree of protection
IP20
Pollution degree
2
Rated insulation voltage
50 V AC/DC
Dimensions W / H / D
6.2 mm / 93.1 mm / 102.5 mm
Type of housing
PBT green
Connection data
Screw connection
Spring-cage conn.
Conductor cross section, solid
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
Conductor cross section, stranded
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
Stripping length
12 mm
8 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
105264_en_01
PHOENIX CONTACT
4
MINI MCR-SL-CVS-24-5-10-NC
Conformance with EMC Directive 2004/108/EC
Noise immunity according to EN 61000-6-2
When being exposed to interference, there may be minimal deviations.
Noise emission according to EN 61000-6-4
Conformance / approvals
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada
508 listed
UL, USA / Canada
Class I, Div. 2, Groups A, B, C, D T5 applied for
105264_en_01
PHOENIX CONTACT
5
MINI MCR-SL-CVS-24-5-10-NC
5
Safety regulations and installation notes
5.1
Installation notes
–
–
–
–
–
The category 3 device is suitable for installation in the
zone 2 potentially explosive area. It fulfills the requirements of EN 60079-0:2009 and EN 60079-15:2010.
Installation, operation, and maintenance may only be
carried out by qualified electricians. Follow the installation instructions described. When installing and operating the device, the applicable regulations and safety
directives (including national safety directives), as well
as general technical regulations, must be observed.
The technical data is provided in this package slip and
on the certificates (conformity assessment, additional
approvals where applicable).
It is not permissible to open or modify the device. Do not
repair the device yourself but replace it with an equivalent device. Repairs may only be carried out by the manufacturer. The manufacturer is not liable for damage
resulting from violation.
The IP20 degree of protection (IEC 60529/EN 60529) of
the device is intended for use in a clean and dry environment. Do not subject the device to any load that exceeds the described limits.
The device is not designed for use in atmospheres with
a danger of dust explosions.
105264_en_01
5.2
–
–
–
–
–
–
Installation in the Ex area (zone 2)
Observe the specified conditions for use in potentially
explosive areas.
The device must be installed in a housing (control or distributor box) which meets the requirements of EN
60079-15 and provides at least IP54 (EN 60529) degree
of protection.
During installation and when connecting the supply and
signal circuits, observe the requirements of EN 6007914. Devices may only be connected to circuits in zone 2
if they are suitable for operation in Ex zone 2 and for the
prevailing conditions at the place of use.
In potentially explosive areas, terminals may only be
snapped onto or off the DIN rail connector and wires
may only be connected or disconnected when the power is switched off.
The device must be stopped and immediately removed
from the Ex area if it is damaged, has been subjected to
an impermissible load, has been stored incorrectly, or if
it malfunctions.
You can download the latest documents for these devices from www.phoenixcontact.net/products.
PHOENIX CONTACT
6
MINI MCR-SL-CVS-24-5-10-NC
6
6.2
Installation
Block diagram
OUT
NOTE: electrostatic discharge!
The device contains components that can be
damaged or destroyed by electrostatic discharge. When handling the device, observe
the necessary safety precautions against
electrostatic discharge (ESD) according to
EN 61340-5-1 and EN 61340-5-1.
6.1
+ 1
– 2
+ 3
– 4
Structure
3
2
OUT U
GND 1
+24V
OUT
OUT U
GND 1
O
DC , 7,5
0V DC
...3 5V
9°F
9,6 VDC, C ...+14
2,5 0VD -4°
IN: : 9,6...3 °C /
T
OU = IN: °...+65
+
–20
TU 1
OU
Tamb
OU
+
TU
GN
+24V
GND 2
GN
+24
V
+24 ND 2
G
7
o.
ial N
Structure
Output: constant voltage
Potentiometer for adjustment
Cover
Groove for ZBF 6 zack marker strip
Input/supply voltage
Connection for DIN rail connector
Universal snap-on foot for EN DIN rails
DIP switch S1
105264_en_01
8
G Gc X
II 3 A II C T4
Ex n
D2
6
1.
2.
3.
4.
5.
6.
7.
8.
6.3
+
8
Ser
Figure 1
5
D2 4
1
GN
Block diagram
Power supply
-
V 3
V
7
www.phoenixcontact.com
D1 2
Figure 2
D1
- 6
5
GN
+24
5
8 –
Zone 2
Warning – Do n ot seperate
when energized
1
, 10
C
VD
FF
S1
7 +
GND 2
4
y
an
rm -NC
Ge 10
rg, 4-52
2
lo VS- 82 t
B
2
5
tan rce
L-C 0
82
32 R-S .: 29 Cons Sou
C o
ge
lta
I M rd.–N
C
Vo
VD
MIN O ON
6 –
+24V
GND 2
1
e
mb
5 +
NOTE: Never connect the supply voltage directly to the DIN rail connector. It is not permitted to draw power from the DIN rail connector
or from individual modules.
Supply via the MINI Analog Module
Where the total current consumption of the aligned modules
does not exceed 400 mA, the power can be supplied directly
at the connection terminal blocks of the module.
A 400 mA fuse should be connected upstream.
Supply via a power terminal block
The MINI MCR-SL-PTB power terminal block (Order No.
2864134) or the MINI MCR-SL-PTB-SP power terminal
block (Order No. 2864147), which are the same shape, are
used to feed the supply voltage to the DIN rail connector.
A 2 A fuse should be connected upstream.
Supply via a system power supply unit
The system power supply unit with 1.5 A output current connects the DIN rail connector to the supply voltage and can
thus be used to supply several modules from the mains.
– MINI-SYS-PS-100-240AC/24DC/1.5 (Order No.
2866983)
– Potentially explosive areas:
MINI-PS-100-240AC/24DC/1.5/EX (Order No.
2866653)
PHOENIX CONTACT
7
MINI MCR-SL-CVS-24-5-10-NC
6.4
Assembly
Screw connection:
B
A
B
A
D
www.interface.phoenixcontact.com
C
E
Figure 4
•
•
Figure 3
–
6.5
Insert the wire into the corresponding connection terminal block.
Use a screwdriver to tighten the screw in the opening
above the connection terminal block.
Spring-cage connection:
Mount the module on a 35 mm DIN rail according to EN
60715.
When using the DIN rail connector, first place it into the
DIN rail (see A – C). It is used to bridge the power supply. It is also absolutely vital that you snap the module
and the DIN rail connector into position in the correct direction: the snap-on foot should be at the bottom and
the connector on the left.
A
B
Connecting the wires
The MINI MCR-SL-CVS-24-5-10... is available in two connection versions:
– Screw terminal blocks (MINI MCR-SL-CVS-24-5-10NC)
– Spring-cage terminal blocks (MINI MCR-SL-CVS-24-510-SP-NC)
Seri
Figure 5
•
•
105264_en_01
Screw connection
www.interface.phoenixcontact.com
–
Mounting and removing
X
XXX
XXX
o. X
al N
Seri
o. X
al N
XXX
XXX
X
Spring-cage connection
Insert a screwdriver into the opening above the connection terminal block.
Insert the wire into the corresponding connection terminal block.
PHOENIX CONTACT
8
MINI MCR-SL-CVS-24-5-10-NC
7
Configuration
You set the constant output voltage with DIP switch S1 (see
table).
Standard Configuration
If it is an "NC version", the device has the standard configuration:
10 V constant output voltage (all DIP switches in the "off" position).
7.1
Configuration table
• = ON
OUT
8
10 V
7.5 V
5V
2.5 V
DIP S1
1
2
•
•
•
•
Adjustment
A potentiometer is located underneath the cover; this is
used for fine adjustment of the analog signals once the configuration of the DIP switches has been modified.
The transmission error without adjustment is