https://www.phoenixcontact.com/gb/products/2902829
Signal conditioner - MINI MCR-SL-UI-I-LP-NC - 2902829
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
2-way loop-powered isolating amplifier (supplied on the output side), can be configured via DIP switches, with
screw connection technology and standard configuration.
Product Description
The 6.2 mm wide MINI MCR-SL-UI-I-LP... configurable 2-way isolating amplifier is used to electrically isolate, condition, and filter analog signals.
The output loops that supply the loop-powered isolating amplifier enable the isolating amplifier to operate on an active analog input module. The
modules are supplied via the current loop of the controller.
On the input side, standard analog signals and non-standard analog signals can be connected, starting from 2 mA or 50 mV up to 40 mA or 30 V.
These are converted to a 4...20 mA signal.
The DIP switches accessible on the housing side enable the configuration of input signal ranges.
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4046356682350
Weight per Piece (excluding packing)
82.000 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
6.2 mm
Height
93.1 mm
Depth
102.5 mm
Ambient conditions
04/16/2018 Page 1 / 9
https://www.phoenixcontact.com/gb/products/2902829
Signal conditioner - MINI MCR-SL-UI-I-LP-NC - 2902829
Technical data
Ambient conditions
Ambient temperature (operation)
-25 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Input data
Number of inputs
1
Voltage input signal
0 mV ... 1000 mV
0 mV ... 750 mV
0 mV ... 500 mV
0 mV ... 300 mV
0 mV ... 250 mV
0 mV ... 200 mV
0 mV ... 150 mV
0 mV ... 125 mV
0 mV ... 120 mV
0 mV ... 100 mV
0 mV ... 75 mV
0 mV ... 60 mV
0 mV ... 50 mV
0 V ... 10 V
0 V ... 7.5 V
0 V ... 5 V
0 V ... 3 V
0 V ... 2.5 V
0 V ... 2 V
0 V ... 1.5 V
0 V ... 1.25 V
0 V ... 1.2 V
0 V ... 30 V
0 V ... 25 V
0 V ... 20 V
0 V ... 12.5 V
0 V ... 12 V
0 V ... 15 V
-1000 mV ... 1000 mV
-750 mV ... 750 mV
-500 mV ... 500 mV
-300 mV ... 300 mV
-250 mV ... 250 mV
-200 mV ... 200 mV
-125 mV ... 125 mV
-120 mV ... 120 mV
04/16/2018 Page 2 / 9
https://www.phoenixcontact.com/gb/products/2902829
Signal conditioner - MINI MCR-SL-UI-I-LP-NC - 2902829
Technical data
Input data
-150 mV ... 150 mV
-100 mV ... 100 mV
-75 mV ... 75 mV
-60 mV ... 60 mV
-50 mV ... 50 mV
-10 V ... 10 V
-7.5 V ... 7.5 V
-5 V ... 5 V
-3 V ... 3 V
-2.5 V ... 2.5 V
-2 V ... 2 V
-1.25 V ... 1.25 V
-1.2 V ... 1.2 V
-1.5 V ... 1.5 V
-30 V ... 30 V
-25 V ... 25 V
-20 V ... 20 V
-12.5 V ... 12.5 V
-12 V ... 12 V
-15 V ... 15 V
200 mV ... 1000 mV
150 mV ... 750 mV
100 mV ... 500 mV
60 mV ... 300 mV
50 mV ... 250 mV
40 mV ... 200 mV
25 mV ... 125 mV
24 mV ... 120 mV
30 mV ... 150 mV
20 mV ... 100 mV
15 mV ... 75 mV
12 mV ... 60 mV
10 mV ... 50 mV
2 V ... 10 V (additional areas can be configured, see table)
1.5 V ... 7.5 V
1 V ... 5 V
0.6 V ... 3 V
0.5 V ... 2.5 V
0.4 V ... 2 V
0.25 V ... 1.25 V
04/16/2018 Page 3 / 9
https://www.phoenixcontact.com/gb/products/2902829
Signal conditioner - MINI MCR-SL-UI-I-LP-NC - 2902829
Technical data
Input data
0.24 V ... 1.2 V
0.3 V ... 1.5 V
6 V ... 30 V
5 V ... 25 V
4 V ... 20 V
2.5 V ... 12.5 V
2.4 V ... 12 V
3 V ... 15 V
Current input signal
0 mA ... 40 mA
0 mA ... 30 mA
0 mA ... 20 mA
0 mA ... 12 mA
0 mA ... 10 mA
0 mA ... 8 mA
0 mA ... 7.5 mA
0 mA ... 5 mA
0 mA ... 6 mA
0 mA ... 4 mA
0 mA ... 3 mA
0 mA ... 2.5 mA
0 mA ... 2 mA
-40 mA ... 40 mA
-30 mA ... 30 mA
-20 mA ... 20 mA
-12 mA ... 12 mA
-10 mA ... 10 mA
-8 mA ... 8 mA
-7.5 mA ... 7.5 mA
-5 mA ... 5 mA
-6 mA ... 6 mA
-4 mA ... 4 mA
-3 mA ... 3 mA
-2.5 mA ... 2.5 mA
-2 mA ... 2 mA
8 mA ... 40 mA
6 mA ... 30 mA
4 mA ... 20 mA
2.4 mA ... 12 mA
2 mA ... 10 mA
1.6 mA ... 8 mA
04/16/2018 Page 4 / 9
https://www.phoenixcontact.com/gb/products/2902829
Signal conditioner - MINI MCR-SL-UI-I-LP-NC - 2902829
Technical data
Input data
1.5 mA ... 7.5 mA
1 mA ... 5 mA
1.2 mA ... 6 mA
0.8 mA ... 4 mA
0.6 mA ... 3 mA
0.5 mA ... 2.5 mA
0.4 mA ... 2 mA
max. input voltage
< 40 V
Max. input current
< 50 mA (Dielectric strength up to 30 V)
Input resistance of voltage input
approx. 100 kΩ (At ≤ 1 V, otherwise approximately 1 MΩ)
Input resistance current input
≤ 50 Ω
Output data
Number of outputs
1
Configurable/programmable
Yes, preconfigured
Current output signal
4 mA ... 20 mA
Max. output current
35 mA (output limit)
Load/output load current output
< 1000 Ω ((UB - 8 V) / 22 mA)
Ripple
< 20 mVPP (at 500 Ω)
Power supply
Supply voltage range
no separate supply voltage necessary
Power consumption
28 mW (without signal)
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG min.
26
Conductor cross section AWG max.
12
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Stripping length
12 mm
Screw thread
M3
General
No. of channels
1
Maximum transmission error
< 0.1 % (of final value)
< 0.2 % (Without adjustment)
Maximum temperature coefficient
0.01 %/K
Temperature coefficient, typical
0.005 %/K
Limit frequency (3 dB)
approx. 30 Hz
Alignment zero
±2%
04/16/2018 Page 5 / 9
https://www.phoenixcontact.com/gb/products/2902829
Signal conditioner - MINI MCR-SL-UI-I-LP-NC - 2902829
Technical data
General
Alignment span
±2%
Step response (10-90%)
approx. 16 ms
Electrical isolation
Basic insulation according to EN 61010
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
50 V AC/DC
Test voltage input/output
1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color
green
Housing material
PBT
Mounting position
any
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T5
Class I, Zone 2, Group IIC
Certificate of classification
DNV GL 14085-15HH
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
EMC data
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
0.5 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
2%
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
0.5 %
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Standards/regulations
EN 61000-4-2
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
EN 61000-4-4
04/16/2018 Page 6 / 9
https://www.phoenixcontact.com/gb/products/2902829
Signal conditioner - MINI MCR-SL-UI-I-LP-NC - 2902829
Technical data
Standards and Regulations
Comments
Criterion B
Standards/regulations
EN 61000-4-5
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Electrical isolation
Basic insulation according to EN 61010
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T5
Class I, Zone 2, Group IIC
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Block diagram
OUT
1
I
US
+ 1
IN I
PWR IN
PLC / DCS
5 +
5
PWR
active
passive
4-wire
GND
2
OUT
3
U
US
OUT
IN
Sensor / Field
– 2
+ 3
GND
OUT I
6 –
IN U
6
7
4-wire
GND
4 – 4
GND
8
Zone 2
Classifications
eCl@ss
eCl@ss 4.0
27210120
eCl@ss 4.1
27210120
eCl@ss 5.0
27210120
eCl@ss 5.1
27210120
eCl@ss 6.0
27210120
04/16/2018 Page 7 / 9
https://www.phoenixcontact.com/gb/products/2902829
Signal conditioner - MINI MCR-SL-UI-I-LP-NC - 2902829
Classifications
eCl@ss
eCl@ss 7.0
27210120
eCl@ss 8.0
27210120
eCl@ss 9.0
27210120
ETIM
ETIM 4.0
EC002653
ETIM 5.0
EC002653
ETIM 6.0
EC002653
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
Approvals
Approvals
Approvals
UL Listed / cUL Listed / EAC / GL / cULus Listed
Ex Approvals
UL Listed / cUL Listed / ATEX / cULus Listed
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
EAC
EAC-Zulassung
04/16/2018 Page 8 / 9
https://www.phoenixcontact.com/gb/products/2902829
Signal conditioner - MINI MCR-SL-UI-I-LP-NC - 2902829
Approvals
GL
http://exchange.dnv.com/tari/
14085-15 HH
cULus Listed
Accessories
Accessories
Marking material
Transparent cover - MINI MCR DKL - 2308111
Fold up transparent cover for MINI MCR modules with additional labeling option using insert strips and flat Zack
marker strip 6.2 mm
Marking label - MINI MCR-DKL-LABEL - 2810272
Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL
System adapter
System adapter - MINI MCR-SL-V8-FLK 16-A - 2811268
Eight MINI analog signal converters with screw connection method can be connected to a control system using a
system adapter and system cabling with a minimum of wiring and very low error risk.
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
04/16/2018 Page 9 / 9
很抱歉,暂时无法提供与“2902829”相匹配的价格&库存,您可以联系我们找货
免费人工找货