MINI MCR-RTD-UI-NC
Temperature transducers for resistance thermometers and remote resistance-type sensors
Data sheet
105446_en_00
1
© PHOENIX CONTACT 2013-01-14
Description
Configurable 3-way isolated temperature transducer. The de- Features
vice is suitable for the connection of resistance thermometers
– Configurable 3-way temperature transducer
and remote resistance-type sensors in 2, 3 and 4-wire con– Configurable via DIP switches for Pt 100 and Pt 1000
nection technology.
(IEC 751)
The measured values are converted into a linear current or
– Extended functionality configurable with free software
voltage signal.
– Approval for Ex-zone 2 (nA)
The device can either be configured via DIP switches or, with
extended functionality, via the S port using the software (FDT/ – Screw or spring-cage connection can be provided
DTM).
The device supports fault monitoring.
WARNING: Correct usage in potentially explosive areas
The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided
here during installation and observe the information in the "Safety regulations and installation notes".
Make sure you always use the latest documentation.
It can be downloaded from the product at www.phoenixcontact.net/products.
This data sheet is valid for all products listed on the following page:
MINI MCR-RTD-UI-NC
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 4
5
Safety regulations and installation notes.................................................................................. 6
5.1
Installation notes ................................................................................................................. 6
5.2
Installation in the Ex area (zone 2)............................................................................................ 6
6
Installation ............................................................................................................................... 7
6.1
Connection notes ................................................................................................................ 7
6.2
Structure ........................................................................................................................... 7
6.3
Block diagram ..................................................................................................................... 7
6.4
Power supply ...................................................................................................................... 8
6.5
Assembly........................................................................................................................... 8
6.6
Connecting the wires ............................................................................................................ 9
7
Fault monitoring FM............................................................................................................... 10
8
Configuration ......................................................................................................................... 11
8.1
Configuration via DIP switches .............................................................................................. 11
8.2
Connectable sensors .......................................................................................................... 11
8.3
Configuration via software (FDT/DTM) .................................................................................... 14
9
Diagnostic indicator ............................................................................................................... 14
105446_en_00
PHOENIX CONTACT
2
MINI MCR-RTD-UI-NC
3
Ordering data
Description
Order No.
Pcs. / Pkt.
Configurable temperature transducer for the connection of 2, 3, and 4-con- MINI MCR-RTD-UI-NC
ductor resistance thermometers and resistance-type sensors. Can be configured via DIP switches or, with extended functionality, using the software.
Screw connection, standard configuration.
2902849
1
Configurable temperature transducer for the connection of 2, 3, and 4-con- MINI MCR-RTD-UI-SP-NC
ductor resistance thermometers and resistance-type sensors. Can be configured via DIP switches or, with extended functionality, using the software.
Spring-cage connection, standard configuration.
2902850
1
Accessories
Type
Order No.
Pcs. / Pkt.
Programming adapter with USB interface, for programming with software.
IFS-USB-PROG-ADAPTER
2811271
1
The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply
the supply voltage to the T-connector. The FM power terminal block offers
the additional function of monitoring in combination with the fault monitoring module. Screw connection.
MINI MCR-SL-PTB-FM
2902958
1
The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply
the supply voltage to the T-connector. The FM power terminal block offers
the additional function of monitoring in combination with the fault monitoring module. Spring-cage connection.
MINI MCR-SL-PTB-FM-SP
2902959
1
The fault monitoring module is used to evaluate and report group errors
from the fault monitoring system and to monitor the supply voltages. The
error is reported via an N/O contact. Screw connection, standard configuration.
MINI MCR-SL-FM-RC-NC
2902961
1
The fault monitoring module is used to evaluate and report group errors
from the fault monitoring system and to monitor the supply voltages. The
error is reported via an N/O contact. Spring-cage connection, standard
configuration.
MINI MCR-SL-FM-RC-SP-NC
2902962
1
DIN rail connector (TBUS), 5-pos., for bridging the supply voltage, can be
snapped onto NS 35/... DIN rails according to EN 60715
ME 6,2 TBUS-2 1,5/5-ST-3,81 GN
2869728
10
DIN rail power supply unit, primary-switched mode, slim design, output:
24 V DC / 1.5 A
MINI-SYS-PS-100-240AC/24DC/1.5
2866983
1
Eight MINI analog signal converters with screw connection method can be
connected to a control system using a system adapter and system cabling
with a minimum of wiring and very low error risk.
MINI MCR-SL-V8-FLK 16-A
2811268
1
MINI analog multiplexer, generates one analog output from 8 analog input
signals, for MINI analog module with screw connection.
MINI MCR-SL-MUX-V8-FLK 16
2811815
1
Fold up transparent cover for MINI MCR modules with additional labeling
option using insert strips and flat Zack marker strip 6.2 mm
MINI MCR DKL
2308111
10
Label for extended marking of MINI MCR modules in connection with the
MINI MCR-DKL
MINI MCR-DKL-LABEL
2810272
10
105446_en_00
Type
PHOENIX CONTACT
3
MINI MCR-RTD-UI-NC
4
Technical data
Input
Configurable/programmable
Yes
Sensor type
Pt, Ni, Cu sensors
Sensor input current
Approx. 200 µA
Max. permissible overall conductor resistance
≤ 25 Ω (Per cable)
Linear resistance measuring range
0 Ω ... 4000 Ω (Minimum measuring span: 10% of the selected measuring range)
Temperature measuring range
-200 °C ... 850 °C (Range depending on the sensor type)
Measuring range span
min. 50 K
Connection method
2, 3, 4-wire
Output
Voltage output signal
0 V ... 10 V
10 V ... 0 V
0 V ... 5 V
1 V ... 5 V
Max. voltage output signal
Approx. 12.3 V
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. current output signal
24.6 mA
Configurable/programmable
Yes
Load/output load voltage output
10 kΩ
Ripple
< 20 mVPP
Load/output load current output
500 Ω (at 20 mA)
Supply
Supply voltage range
9.6 V DC ... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order
No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a
35 mm DIN rail according to EN 60715))
Typical current consumption
< 27 mA (at 24 V DC)
Power consumption
≤ 700 mW (at IOUT = 20 mA, 9.6 V DC, load 500 Ω)
Diagnostic and status indicators
Status display
LED red
General data
Transmission error resistance thermometer
0.1% * 350 K / set measuring range; 0.1% > 350 K (Pt/Ni)
0.3% * 200 K / set measuring range; 0.3% > 200 K (Cu)
Transmission error resistance-type sensor
2Ω
Maximum temperature coefficient
0.01 %/K
Step response (0–99%)
Typ. 200 ms (2-wire)
Typ. 500 ms (3-wire)
Typ. 500 ms (4-wire)
Electrical isolation
Basic insulation according to EN 61010
Surge voltage category
II
Mounting position
Any
Degree of protection
IP20
Pollution degree
2
Rated insulation voltage
50 V AC/DC
105446_en_00
PHOENIX CONTACT
4
MINI MCR-RTD-UI-NC
General data [...]
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Dimensions W / H / D
6.2 mm / 93.1 mm / 102.5 mm
Type of housing
PBT green
Connection data
Screw connection
Conductor cross section, solid
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
Conductor cross section, stranded
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
Stripping length
12 mm
8 mm
Spring-cage conn.
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (no condensation)
Conformance with EMC Directive 2004/108/EC
Noise immunity according to EN 61000-6-2
When being exposed to interference, there may be minimal deviations.
Noise emission according to EN 61000-6-4
Conformance / approvals
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada
UL 508 Recognized applied for
UL, USA / Canada
Class I, Div. 2, Groups A, B, C, D T5 applied for
Shipbuilding
GL applied for
105446_en_00
PHOENIX CONTACT
5
MINI MCR-RTD-UI-NC
5
Safety regulations and installation notes
5.1
Installation notes
–
–
–
–
–
The category 3 device is suitable for installation in the
zone 2 potentially explosive area. It fulfills the requirements of EN 60079-0:2009 and EN 60079-15:2010.
Installation, operation, and maintenance may only be carried out by qualified electricians. Follow the installation instructions described. When installing and operating the
device, the applicable regulations and safety directives
(including national safety directives), as well as general
technical regulations, must be observed. The technical
data is provided in this package slip and on the certificates (conformity assessment, additional approvals
where applicable).
It is not permissible to open or modify the device. Do not
repair the device yourself but replace it with an equivalent
device. Repairs may only be carried out by the manufacturer. The manufacturer is not liable for damage resulting
from violation.
The IP20 degree of protection (IEC 60529/EN 60529) of
the device is intended for use in a clean and dry environment. Do not subject the device to any load that exceeds
the described limits.
The device is not designed for use in atmospheres with a
danger of dust explosions.
105446_en_00
5.2
–
–
–
–
–
–
Installation in the Ex area (zone 2)
Observe the specified conditions for use in potentially explosive areas.
The device must be installed in a housing (control or distributor box) which meets the requirements of EN 6007915 and provides at least IP54 (EN 60529) degree of protection.
During installation and when connecting the supply and
signal circuits, observe the requirements of EN 6007914. Devices may only be connected to circuits in zone 2 if
they are suitable for operation in Ex zone 2 and for the
prevailing conditions at the place of use.
In potentially explosive areas, terminals may only be
snapped onto or off the DIN rail connector and wires may
only be connected or disconnected when the power is
switched off.
The device must be stopped and immediately removed
from the Ex area if it is damaged, has been subjected to
an impermissible load, has been stored incorrectly, or if it
malfunctions.
You can download the latest documents for these devices from www.phoenixcontact.net/products.
PHOENIX CONTACT
6
MINI MCR-RTD-UI-NC
6.3
6
Installation
6.1
Connection notes
Block diagram
OUT
IN
Sensor / Field
PLC / DCS
S-Port
NOTE: Electrostatic discharge!
The device contains components that can be
damaged or destroyed by electrostatic discharge. When handling the device, observe the
necessary safety precautions against electrostatic discharge (ESD) according to EN 613405-1 and EN 61340-5-2.
1
2
ϑ
ϑ
6
ϑ
+24V
3
3
4
GND 2
GND 2
7 +
8 –
6
S-P
Tamb
,I
TU
OU
5 active
+
D1
5
GN
6
sive
pas
6
V
+24
7
+
D2
GN
ort
2
2
www.phoenixcontact.com
S
/ DC
PLC
- 8
+24
F
4
Figure 2
Block diagram
ϑ
ϑ
G Gc X
II 3 A II C T4
Ex n
-4
GND 2
0
V
1
3
FM
S2
8
ON
OF
3
Warning – Do n ot seperate
when energized
Zone 2
R 0
V
3 I MC .: 29
er 760 , 10...0
o
3 A
ion
MINrd.–N
dit DIN 4 4)0m
O
on
l C 651, , 20...(
a
ign ST 6...10V
ld
S
O
F
/ ie
D
G ,0
sor
RT 751, )...5V
Sen
C 0(1
°F
149
D IE A,
...+
RT ..20m C
°
4
(4). D / –
IN: : 0 ...30V 5°C
T ,6
6
1
OU 9 0°...+
ϑ
1
–2
11
1
S1
9
1
o.
ial N
Ser
+24V
2
3
4
2
28
8
Figure 1
6 –
FM
y
an
erm
, G NC
erg UImb TD– 84 9
lo
5 B –R 2
7
5
passive
GND 1
2
Structure
5
5 +
active
4
6.2
OUT U,I
1
10
Structure
1.
Input: resistance thermometer and remote resistancetype sensor
2. Cover
3. Diagnostics LED
4. S-PORT
5. Groove for ZBF 6 zack marker strip
6. Output: Standard signals
7. Supply voltage
8. Connection for DIN rail connector
9. Universal snap-on foot for EN DIN rails
10. DIP switch S1
11. DIP switch S2
105446_en_00
PHOENIX CONTACT
7
MINI MCR-RTD-UI-NC
6.4
Power supply
6.5
Assembly
B
A
NOTE: Never connect the supply voltage directly to the DIN rail connector. It is not permitted to draw power from the DIN rail connector
or from individual modules.
Supply via the MINI Analog Module
C
Where the total current consumption of the aligned modules
does not exceed 400 mA, the power can be supplied directly
at the connection terminal blocks of the module.
A
D
E
www.interface.phoenixcontact.com
B
X
XXX
XXX
o. X
al N
Seri
Figure 4
–
Figure 3
Spring-cage connection
A 400 mA fuse should be connected upstream.
Supply via a Power Terminal Block
The MINI MCR-SL-PTB-FM power terminal block (Order No.
2902958) or the MINI MCR-SL-PTB-FM-SP power terminal
block (Order No. 2902959), which are the same shape, are
used to feed the supply voltage to the DIN rail connector.
–
Mounting and removing
Mount the module on a 35 mm DIN rail according to EN
60715.
When using the DIN rail connector, first place it into the
DIN rail (see A – C). It is used to bridge the power supply.
It is also absolutely vital that you snap the module and the
DIN rail connector into position in the correct direction:
the snap-on foot should be at the bottom and the connector on the left.
We recommend connecting a 2.5 A slow-blow fuse (e.g.,
SIBA 179 120.2,5 20x5).
Supply via a system power supply unit
The system power supply unit with 1.5 A output current connects the DIN rail connector to the supply voltage and can
therefore be used to supply several modules from the mains.
– MINI-SYS-PS-100-240AC/24DC/1.5 (Order No.
2866983)
– Potentially explosive areas:
MINI-PS-100-240AC/24DC/1.5/EX (Order No. 2866653)
105446_en_00
PHOENIX CONTACT
8
MINI MCR-RTD-UI-NC
6.6
Connecting the wires
The module is available in two connection versions:
– Screw terminal blocks (for MINI MCR-RTD-UI-NC)
– "Spring-cage terminal blocks (for MINI MCR-RTD-UI-SPNC)
Screw connection:
B
www.interface.phoenixcontact.com
A
Figure 5
•
•
X
XXX
XXX
o. X
al N
Seri
Screw connection
Insert the wire into the corresponding connection terminal
block.
Use a screwdriver to tighten the screw in the opening
above the connection terminal block.
Spring-cage connection:
A
www.interface.phoenixcontact.com
B
Figure 6
•
•
X
XXX
XXX
o. X
al N
Seri
Spring-cage connection
Insert a screwdriver into the opening above the connection terminal block.
Insert the wire into the corresponding connection terminal
block.
105446_en_00
PHOENIX CONTACT
9
MINI MCR-RTD-UI-NC
7
Fault monitoring FM
Detected errors on the signal input or in the device are reported via the DIN rail connector to the MINI MCR-SL-FMRC-NC (Order No. 2902961) or MINI MCR-SL-FM-RC-SPNC (Order No. 2902962), which are the same shape. The
module reports the error centrally via an N/C contact.
In one group, a fault monitoring module is only required once.
Individual evaluation of the up to 80 Phoenix Contact isolation
amplifiers can be omitted.
The fault monitoring module can also be used to monitor the
supply voltage.
•
For the behavior of the fault monitoring contact for the different DIP switch configurations, please refer to the table.
Error response
A
B
C
D
NE43
Upscale
Downscale
0 mA
Upscale/downscale
Module error
Invalid DIP switch configuration
105446_en_00
Fault monitoring: N/C contact
Measuring range Measuring range
overrange
underrange
activated
deactivated
activated
activated
deactivated
deactivated
deactivated
deactivated
activated
activated
Cable break
Short-circuit
activated
activated
activated
deactivated
activated
deactivated
activated
activated
deactivated
activated
Activated (error is always reported)
Activated (error is always reported)
PHOENIX CONTACT
10
MINI MCR-RTD-UI-NC
8
Configuration
The modules have the standard configuration:
– Sensor Pt 100 IEC 751
– 3-wire
– -50...150°C
– Output 4...20 mA
– Error evaluation according to NE43 (downscale)
– Fault monitoring contact reacts to all errors
The module can also be configured with the
supply voltage not connected.
8.2
8.1
Configuration via DIP switches
At delivery, all DIP switches are in the "OFF" position.
Configure the DIP switches according to the planned application using the configuration tables.
DIP switch S1 is used to specify the configuration method,
connection method, output signal range, and measuring
range start value.
DIP switch S2 is used to specify the measuring range final
value, sensor type (Pt 100/Pt 1000, IEC 751), an the error
contact behavior.
Connectable sensors
Sensor Standard
type
Pt 100
IEC 751 = GOST 6651-2009 ( = 0.00385)
Pt 200
IEC 751 = GOST 6651-2009 ( = 0.00385)
Pt 500
IEC 751 = GOST 6651-2009 ( = 0.00385)
Pt 1000 IEC 751 = GOST 6651-2009 ( = 0.00385)
Pt 100
GOST 6651-2009 ( = 0.00391)
Pt 1000 GOST 6651-2009 ( = 0.00391)
Pt 100
JIS C1604-1997
Pt 1000 JIS C1604-1997
Ni 100
DIN 43760
Ni 1000 DIN 43760
Cu 50
GOST 6651-2009 ( = 1.428)
Cu 100
GOST 6651-2009 ( = 1.428)
Cu 53
GOST 6651-2009 ( = 1.426)
Customer-specific characteristic curves
105446_en_00
Measuring range
-200°C ... +850°C
-200°C ... +850°C
-200°C ... +850°C
-200°C ... +850°C
-200°C ... +850°C
-200°C ... +850°C
-200°C ... +850°C
-200°C ... +850°C
-60°C ... +250°C
-60°C ... +250°C
-180°C ... +200°C
-180°C ... +200°C
-50°C ... +180°C
Smallest measuring
range span
50 K
50 K
50 K
50 K
50 K
50 K
50 K
50 K
50 K
50 K
50 K
50 K
50 K
PHOENIX CONTACT
11
MINI MCR-RTD-UI-NC
Configuration tables
• = ON DIP S1
1 2 3 4 5 6 7 8
Connection technology
Configuration via software
2-wire
3-wire
4-wire
0...20 mA
20...0 mA
4...20 mA
20...4 mA
0...10 V
10...0 V
0...5 V
1...5 V
0°C
32°F
-10°C
14°F
-20°C
-4°F
-30°C
-22°F
-40°C
-40°F
-50°C
-58°F
-100°C
-148°F
-150°C
-238°F
Analog output signal
Start temperature
•
•
• •
•
•
• •
•
•
• •
• • •
•
•
•
• •
•
•
• •
Measuring range final value
DIP S2
1 2 3 4 5 6
0°C
5°C
10°C
15°C
20°C
25°C
30°C
35°C
40°C
45°C
50°C
55°C
60°C
65°C
70°C
75°C
80°C
85°C
90°C
95°C
100°C
105°C
110°C
115°C
120°C
125°C
130°C
135°C
140°C
145°C
150°C
155°C
105446_en_00
32°F
41°F
50°F
59°F
68°F
77°F
86°F
95°F
104°F
113°F
122°F
131°F
140°F
149°F
158°F
167°F
176°F
185°F
194°F
203°F
212°F
221°F
230°F
239°F
248°F
257°F
266°F
275°F
284°F
293°F
302°F
311°F
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
1 2 3
160°C
165°C
170°C
175°C
180°C
185°C
190°C
195°C
200°C
210°C
220°C
230°C
240°C
250°C
260°C
270°C
280°C
290°C
300°C
325°C
350°C
375°C
400°C
425°C
450°C
475°C
500°C
550°C
600°C
650°C
700°C
850°C
320°F
329°F
338°F
347°F
356°F
365°F
374°F
383°F
392°F
410°F
428°F
446°F
464°F
482°F
500°F
518°F
536°F
554°F
572°F
617°F
662°F
707°F
752°F
797°F
842°F
887°F
932°F
1022°F
1112°F
1202°F
1292°F
1562°F
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
• = ON
DIP S2
4 5 6 7 8 9 0
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
• •
• •
• •
• •
• •
• •
• •
• •
• • •
• • •
• • •
• • •
• • •
• • •
• • •
• • •
PHOENIX CONTACT
12
MINI MCR-RTD-UI-NC
Fault evaluation
0...20 mA 20...0
4...20
20...4
0...10 V 10...0 V 0...5 V
mA
mA
mA
A Cable break
21 mA
21 mA 21 mA 21 mA 10.5 V
10.5 V 5.25 V
Overrange
20.5 mA 20.5 mA 20.5 mA 20.5 mA 10.25 V 10.25 V 5.125 V
Underrange
0 mA
0 mA
4 mA
4 mA
0V
0V
0V
Short circuit
0 mA
0 mA
4 mA
4 mA
0V
0V
0V
B Cable break
21 mA
21 mA 21 mA 21 mA 10.5 V
10.5 V 5.25 V
Overrange
20.5 mA 20.5 mA 20.5 mA 20.5 mA 10.25 V 10.25 V 5.125 V
Underrange
0 mA
0 mA
3.5 mA 3.5 mA 0 V
0V
0V
Short circuit
0 mA
0 mA
3 mA
3 mA
0V
0V
0V
C Cable break
21 mA
21 mA 21 mA 21 mA 10.5 V
10.5 V 5.25 V
Overrange
20 mA
20 mA 20 mA 20 mA 10 V
10 V
5V
Underrange
0 mA
0 mA
4 mA
4 mA
0V
0V
0V
Short circuit
21 mA
21 mA 21 mA 21 mA 10.5 V
10.5 V 5.25 V
D Cable break
0 mA
0 mA
4 mA
4 mA
0V
0V
0V
Overrange
20 mA
20 mA 20 mA 20 mA 10 V
10 V
5V
Underrange
0 mA
0 mA
4 mA
4 mA
0V
0V
0V
Short circuit
0 mA
0 mA
4 mA
4 mA
0V
0V
0V
NE43
(Only OUT = 4...20 mA or 20...4 mA)
Upscale
Cable break, overrange, underrange, short circuit
Downscale
Cable break, overrange, underrange, short circuit
0 mA
Cable break, overrange, underrange, short circuit
Up/downscale
Cable break, short circuit
= 3.5 mA
Overrange, underrange
= 21.5 mA
Sensor type
Pt 100 (IEC 751)
Pt 1000 (IEC 751)
105446_en_00
• = ON
DIP S2
7 8 9 0
Analog OUT
1...5 V
5.25 V
5.125 V
1V
1V
5.25 V
5.125 V
0.875 V
0.75 V
5.25 V
5V
1V
5.25 V
1V
5V
1V
1V
•
•
• •
= 21.5 mA
•
= 3.5 mA •
•
= 0 mA
• •
• • •
•
PHOENIX CONTACT
13
MINI MCR-RTD-UI-NC
8.3
Configuration via software (FDT/DTM)
Use the IFS-USB-PROG-ADAPTER
(Order No.: 2811271) for connecting the
device to the PC.
Figure 7
9
Diagnostic indicator
The red LED indicates the following error states:
– LED flashes at 2.8 Hz: sensor error or invalid DIP switch
configuration
– LED flashes at 1.4 Hz: simulation mode
– LED is permanently on: internal device error
Connection for programming adapter
Software configuration provides advantages such as 13 different sensor types, customer-specific characteristic curves,
free adjustment of signal output, temperature ranges, and
error indication.
The software consists of the FDT framework application and
a driver (DTM) for every device. The software is available free
of charge on the Internet at www.phoenixcontact.com.
•
Enter the order number of your measuring transducer in
the search field. The installation packages can be found
under Downloads.
•
If you are already using an FDT framework application,
only download the DTMs.
•
In any other case, download the IFS-CONF software
package. It contains both the framework application and
the pre-installed DTMs.
ANALOG-CONF standard software
•
If you do not require an FDT/DTM-based software solution, you can use the ANALOG-CONF standard software.
This software also allows for performing all the settings
on the device. The software is available free of charge on
the Internet at www.phoenixcontact.com.
The USB driver for the programming adapter is
part of the IFS-CONF, ANALOG-CONF, and of
the DTM installation package.
105446_en_00
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
www.phoenixcontact.com
14