Primary-switched TRIO POWER power supply with push-in connection for DIN rail mounting, input: 1-phase,
output: 12 V DC/10 A
Product Description
TRIO POWER power supplies with standard functionality
The TRIO POWER power supply range with push-in connection has been perfected for use in machine building. All functions and the space-saving
design of the single and three-phase modules are optimally tailored to the stringent requirements. Under challenging ambient conditions, the power
supply units, which feature an extremely robust electrical and mechanical design, ensure the reliable supply of all loads.
Your advantages
Save time and costs, thanks to the Push-in connection and narrow design
Increase system availability, thanks to dynamic boost with 150% of the nominal current for five seconds
Maximum flexibility due to the wide temperature range from -25°C to +70°C and device startup at -40°C
Electrically robust, thanks to high electric strength
Mechanically robust, thanks to high vibration and shock resistance
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4055626255460
Weight per Piece (excluding packing)
580.000 g
Custom tariff number
85044030
Country of origin
China
Technical data
Dimensions
Width
35 mm
09/09/2019 Page 1 / 8
https://www.phoenixcontact.com/us/products/2903158
Power supply unit - TRIO-PS-2G/1AC/12DC/10 - 2903158
Technical data
Dimensions
Height
130 mm
Depth
115 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2
Installation height
≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Input data
Nominal input voltage range
100 V AC ... 240 V AC
110 V DC ... 250 V DC
Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
99 V DC ... 275 V DC
Dielectric strength maximum
≤ 300 V AC 15 s
AC frequency range
50 Hz ... 60 Hz ±10 %
Discharge current to PE
< 0.25 mA
Current consumption
2.2 A (100 V AC)
1.9 A (120 V AC)
1.1 A (230 V AC)
1.1 A (240 V AC)
Nominal power consumption
254.7 VA
Inrush current
≤ 30 A (typical)
Mains buffering time
typ. 20 ms (120 V AC)
typ. 20 ms (230 V AC)
Input fuse
6.3 A Fast blow (internal (device protection))
Recommended breaker for input protection
6 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi)
0.53
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
12 V DC ±1 %
Setting range of the output voltage (USet)
12 V DC ... 18 V DC (> 12 V DC, constant capacity restricted)
Nominal output current (IN)
10 A
Dynamic Boost (IDyn.Boost)
15 A (5 s)
09/09/2019 Page 2 / 8
https://www.phoenixcontact.com/us/products/2903158
Power supply unit - TRIO-PS-2G/1AC/12DC/10 - 2903158
Technical data
Output data
Derating
> 60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
yes
Feedback voltage resistance
< 25 V
Protection against overvoltage at the output (OVP)
≤ 22 V DC
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple
< 50 mVPP (with nominal values)
Output power
120 W
Typical response time
89 % (for 230 V AC and nominal values)
Insulation voltage input/output
3 kV AC (type test)
1.5 kV AC (routine test)
Protection class
II (in closed control cabinet)
Degree of protection
IP20
MTBF (IEC 61709, SN 29500)
> (25 °C)
> 1700000 h (40 °C)
60 °C
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
Connection data, input
Connection method
Push-in connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
10 mm
Connection data, output
Connection method
Push-in connection
09/09/2019 Page 3 / 8
https://www.phoenixcontact.com/us/products/2903158
Power supply unit - TRIO-PS-2G/1AC/12DC/10 - 2903158
Technical data
Connection data, output
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
8 mm
Connection data for signaling
Connection method
Push-in connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
16
Stripping length
8 mm
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Noise emission
EN 55011 (EN 55022)
Noise immunity
EN 61000-6-2:2005
Standards/regulations
EN 61000-4-2
Contact discharge
4 kV (Test Level 2)
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1.4 GHz ... 2 GHz
Test field strength
3 V/m (Test Level 2)
Standards/regulations
EN 61000-4-4
Comments
Criterion B
Standards/regulations
EN 61000-6-3
EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-4-11
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard - Safety of transformers
EN 61558-2-16 (air clearances and creepage distances only)
09/09/2019 Page 4 / 8
https://www.phoenixcontact.com/us/products/2903158
Power supply unit - TRIO-PS-2G/1AC/12DC/10 - 2903158
Technical data
Standards and Regulations
Standard - Electrical safety
IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard – Limitation of mains harmonic currents
EN 61000-3-2
UL approvals
UL Listed UL 508
UL/C-UL Recognized UL 60950-1
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 4g, 90 min.
Rail applications
EN 50121-4
Environmental Product Compliance
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Block diagram
09/09/2019 Page 5 / 8
https://www.phoenixcontact.com/us/products/2903158
Power supply unit - TRIO-PS-2G/1AC/12DC/10 - 2903158
Classifications
eCl@ss
eCl@ss 4.0
27040702
eCl@ss 4.1
27040702
eCl@ss 5.0
27049002
eCl@ss 5.1
27049002
eCl@ss 6.0
27049000
eCl@ss 7.0
27049002
eCl@ss 8.0
27049002
eCl@ss 9.0
27040701
ETIM
ETIM 4.0
EC002540
ETIM 5.0
EC002540
ETIM 6.0
EC002540
ETIM 7.0
EC002540
UNSPSC
UNSPSC 13.2
39121004
Approvals
Approvals
Approvals
UL Listed / UL Recognized / cUL Recognized / cUL Listed / EAC / cULus Recognized / cULus Listed
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 123528
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 211944
09/09/2019 Page 6 / 8
https://www.phoenixcontact.com/us/products/2903158
Power supply unit - TRIO-PS-2G/1AC/12DC/10 - 2903158
Approvals
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 211944
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 123528
EAC
RU CDE.A*30.B.01082
cULus Recognized
cULus Listed
Accessories
Accessories
Device protection
Type 3 surge protection device - PLT-SEC-T3-230-FM-PT - 2907928
Type 2/3 surge protection, consisting of protective plug and base element with Push-in connection. For single-phase
power supply network with integrated status indicator and remote signaling. Nominal voltage 230 V AC/DC.
Type 3 surge protection device - PLT-SEC-T3-24-FM-PT - 2907925
Type 3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote
signaling for single-phase power supply networks. Nominal voltage 24 V AC/DC.
09/09/2019 Page 7 / 8
https://www.phoenixcontact.com/us/products/2903158
Phoenix Contact 2019 © - all rights reserved
http://www.phoenixcontact.com
09/09/2019 Page 8 / 8
很抱歉,暂时无法提供与“2903158”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+1510.236671+194.95890
- 5+1456.315285+187.99810
- 10+1402.3938810+181.03730