https://www.phoenixcontact.com/us/products/2903299
Relay Module - RIF-3-RSC-LV-120AC/3X21 - 2903299
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Pre-assembled relay module with screw connection, consisting of: relay base, power contact relay, plug-in
display/interference suppression module, and retaining bracket. Contact type: 3 changeover contacts. Input
voltage: 120 V AC
The figure shows the 24 V DC
version
Key Commercial Data
Packing unit
1
GTIN
GTIN
4046356732055
Custom tariff number
85364900
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
40 mm
Height
96 mm
Depth
90 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 50 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Coil side
Nominal input voltage UN
120 V AC
04/10/2017 Page 1 / 5
https://www.phoenixcontact.com/us/products/2903299
Relay Module - RIF-3-RSC-LV-120AC/3X21 - 2903299
Technical data
Coil side
Input voltage range in reference to UN
see diagram
Mains frequency
50 Hz
60 Hz
Typical input current at UN
23 mA
Typical response time
5 ms ... 15 ms
Typical release time range
5 ms ... 20 ms
Coil voltage
120 V AC
Protective circuit
Varistor
Operating voltage display
Yellow LED
Contact side
Contact type
3 PDTs
Type of switch contact
Single contact
Contact material
AgNi
Maximum switching voltage
250 V AC/DC
Minimum switching voltage
10 V (At 24 mA)
Min. switching current
10 mA (at 24 V)
Maximum inrush current
30 A (20 ms, N/O contact)
Limiting continuous current
6 A (see diagram)
Interrupting rating (ohmic load) max.
144 W (at 24 V DC)
124 W (at 48 V DC)
108 W (at 60 V DC)
52 W (at 110 V DC)
48 W (at 220 V DC)
1500 VA (for 250 V AC)
Switching capacity in acc. with DIN VDE 0660/IEC 60947
2 A (at 24 V, DC13)
0.22 A (at 120 V, DC13)
0.11 A (at 250 V, DC13)
3 A (at 24 V, AC15)
3 A (at 120 V, AC15)
1.5 A (at 240 V, AC15)
Connection data input side
Connection name
Coil side
Connection method
Screw connection
Stripping length
8 mm
Conductor cross section solid
0.14 mm² ... 6 mm²
Conductor cross section flexible
0.14 mm² ... 4 mm²
04/10/2017 Page 2 / 5
https://www.phoenixcontact.com/us/products/2903299
Relay Module - RIF-3-RSC-LV-120AC/3X21 - 2903299
Technical data
Connection data input side
Conductor cross section AWG
26 ... 10
Connection data output side
Connection name
Contact side
Connection method
Screw connection
Stripping length
8 mm
Conductor cross section solid
0.14 mm² ... 6 mm²
Conductor cross section flexible
0.14 mm² ... 4 mm²
Conductor cross section AWG
26 ... 10
General
Test voltage relay winding/relay contact
2.5 kVrms (50 Hz, 1 min.)
Test voltage relay contact/relay contact
2 kVrms (50 Hz, 1 min.)
Operating mode
100% operating factor
Degree of protection
IP20 (Relay socket)
RT I (Relay)
Mechanical service life
Approx. 2x 10 cycles
Mounting position
any
Assembly instructions
In rows with zero spacing
7
Standards and Regulations
Standards/regulations
DIN EN 50178
Rated insulation voltage
250 V AC
Rated surge voltage
4 kV
Insulation
Basic insulation
Degree of pollution
2
Overvoltage category
III
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
04/10/2017 Page 3 / 5
https://www.phoenixcontact.com/us/products/2903299
Relay Module - RIF-3-RSC-LV-120AC/3X21 - 2903299
Circuit diagram
Diagram
32 22 12
Coil voltage U/UN
34 24 14
31 21 11
A2
A1
AC coils
1,8
1,7
1,6
1,5
1,4
1,3
1,2
1,1
1,0
0,9
0,8
0,7
0,6
20
30
80
40
50
60
70
Ambient temperature [°C]
DC coil (observe contact derating)
AC coil (observe contact derating)
Operating voltage range
Diagram
Diagram
11
10
10
6
4
9
2
1
0,5
0,3
0,2
0,1
10
20
30
50 70 100
200
Switching voltage [V]
300
AC, ohmic load
DC, ohmic load
Interrupting rating
Limiting continuous current per contact [A]
Switching current [A]
20
8
7
6
5
4
3
2
1
20
30
40
Contact derating
Diagram
7
1
10
10
6
0,9
5
10
4
0 0,2 0,4 0,6 0,8 1,0 1,2 1,4 1,6 1,8 2,0 2,2 2,4 2,6
Switching capacity [kVA]
Reduction factor
Cycles
80
DC coil
AC coil
Diagram
10
50
60
70
Ambient temperature [°C]
0,8
0,7
0,6
0,5
0,4
0,3
1
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
COS j
! 250 V AC, ohmic load
Electrical service life
Service life reduction factor
04/10/2017 Page 4 / 5
https://www.phoenixcontact.com/us/products/2903299
Relay Module - RIF-3-RSC-LV-120AC/3X21 - 2903299
Articles in set
Relay socket - RIF-3-BSC/3X21 - 2900936
RIF-3... relay base, for octal relay with 3 changeover contacts, screw connection, plug-in option for input/interference
suppression modules, for mounting on NS 35/7,5
Single relay - REL-OR3/L-120AC/3X21 - 2903695
Pluggable octal relay with power contacts, 3 PDT, test button, mechanical switching position indication, coil voltage 120 V
AC
Plug-in module - RIF-V-120-230 UC - 2900948
Plug-in module, for mounting on RIF-1, RIF-2, RIF-3, and RIF-4, with varistor, input voltage: 120 - 230 V AC/DC ±20%
Retaining bracket - RIF-RH-3 - 2900955
Relay retaining bracket, with holder for marking material, suitable for RIF-3 relay base, for octal relay
Phoenix Contact 2017 © - all rights reserved
http://www.phoenixcontact.com
04/10/2017 Page 5 / 5