https://www.phoenixcontact.com/us/products/2903912
Hybrid motor starter - ELR H5-I-PT- 24DC/500AC-9 - 2903912
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Hybrid motor starter for reversing 3~ AC motors up to 550 V AC, with 24 V DC input, 9 A output current,
adjustable overload shutdown, and push-in connection.
The figure shows the ELR H5-IESPT- 24DC/500AC-9 version
Product Features
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
280.0 GRM
Custom tariff number
85371099
Country of origin
Germany
Technical data
Input data
Input name
Device supply
Rated control supply voltage US
24 V DC (According to IEC 60947-1)
Voltage range with reference to US
0.8 ... 1.25
Rated control supply current IS
≤ 40 mA
Protective circuit
Protection against polarity reversal
Surge protection
Operating voltage display
Green LED
Status display
Yellow LED
Indication
Red LED
Input name
Control input right/left
Typical input current at UN
≤ 5 mA
Rated control supply current IS
≤ 40 mA (According to IEC 60947-1)
05/18/2015 Page 1 / 6
https://www.phoenixcontact.com/us/products/2903912
Hybrid motor starter - ELR H5-I-PT- 24DC/500AC-9 - 2903912
Technical data
Input data
Rated actuating voltage UC
24 V DC
Voltage range with reference to UC
0.8 ... 1.25
Rated actuating current IC
≤ 5 mA
Protective circuit
Protection against polarity reversal
Typical response time
< 35 ms
Typical turn-off time
< 40 ms
Output data load output
Rated operating voltage Ue
500 V AC
Operating voltage range
42 V AC ... 550 V AC
Load current
max. 9 A (see derating curve)
Min. load current
1.5 A
Rated operating current at AC-51
9A
Rated operating current at AC-53a
6.5 A
Leakage current
0 mA
Residual voltage
< 0.5 V (at Ie)
Protective circuit
Surge protection
Output data reply output
Note
Confirmation 01: floating change-over contact, signal contact
Contact type
1 PDT
Contact material
AgSnO2, hard gold-plated
Maximum switching voltage
30 V AC
36 V DC
Minimum switching voltage
100 mV AC/DC (at 10 mA)
Min. switching current
1 mA (at 24 V)
Maximum inrush current
50 mA
Limiting continuous current
50 mA
Interrupting rating (ohmic load) max.
1.2 W (at 24 V DC)
Note
the following values are applicable if a gold layer is destroyed
Maximum switching voltage
250 V AC/DC
Minimum switching voltage
5 V (at 100 mA)
Min. switching current
10 mA (at 12 V)
Limiting continuous current
6A
Interrupting rating (ohmic load) max.
140 W (at 24 V DC)
20 W (at 48 V DC)
18 W (at 60 V DC)
23 W (at 110 V DC)
05/18/2015 Page 2 / 6
https://www.phoenixcontact.com/us/products/2903912
Hybrid motor starter - ELR H5-I-PT- 24DC/500AC-9 - 2903912
Technical data
Output data reply output
40 W (at 220 V DC)
1500 VA (for 250 V AC)
Switching capacity according to IEC 60947-5-1
2 A (at 24 V, DC13)
0.2 A (at 110 V, DC13)
0.1 A (at 220 V, DC13)
3 A (at 24 V, AC15)
3 A (at 120 V, AC15)
3 A (at 230 V, AC15)
Measuring technology and signaling contact
Measuring via
Current transformer for line current on L1 and L3
Connection data
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
General
Test voltage input/output
4 kVrms
Mounting position
Vertical (horizontal DIN rail)
Assembly instructions
can be aligned with spacing: see derating
Operating mode
100% operating factor
Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
DIN EN 50178
Insulation
Safe isolation (EN 50178) for mains voltage ≤ 500 V AC
Safe isolation (IEC 60947-1) for mains voltage ≤ 300 V AC
Basic insulation (IEC 60947-1) for mains voltage of 300 ... 500 V AC
Pollution degree
2
Surge voltage category
III
Designation
Standards/regulations
Standards/regulations
IEC 60947-1
EN 60947-4-2
Dimensions
05/18/2015 Page 3 / 6
https://www.phoenixcontact.com/us/products/2903912
Hybrid motor starter - ELR H5-I-PT- 24DC/500AC-9 - 2903912
Technical data
Dimensions
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Degree of protection
IP20
UL data
Short-circuit current rating (SCCR)
100 kA (500 V AC (30 A CC/30 A J (high fault) fuse))
5 kA (500 V AC (20 A RK5 (standard fault) fuse))
Classifications
eCl@ss
eCl@ss 4.0
27371102
eCl@ss 4.1
27371102
eCl@ss 5.0
27371601
eCl@ss 5.1
27371601
eCl@ss 6.0
27371601
eCl@ss 7.0
27371601
eCl@ss 8.0
27370905
ETIM
ETIM 3.0
EC000066
ETIM 4.0
EC000066
ETIM 5.0
EC001037
UNSPSC
UNSPSC 6.01
30211915
UNSPSC 7.0901
39121514
UNSPSC 11
39121514
UNSPSC 12.01
39121514
UNSPSC 13.2
39121514
Approvals
Approvals
05/18/2015 Page 4 / 6
https://www.phoenixcontact.com/us/products/2903912
Hybrid motor starter - ELR H5-I-PT- 24DC/500AC-9 - 2903912
Approvals
Approvals
UL Listed / cUL Listed / IECEE CB Scheme / UL Listed / cUL Listed / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
IECEE CB Scheme
UL Listed
cUL Listed
cULus Listed
Drawings
05/18/2015 Page 5 / 6
https://www.phoenixcontact.com/us/products/2903912
Hybrid motor starter - ELR H5-I-PT- 24DC/500AC-9 - 2903912
Load current [A]
Diagram
Block diagram
MAN
RES
AUTO
9
8
7
6
5
4
3
2
1
0,18
RES
1/L1 3/L2 5/L3
Logic
µP
Us
T
0
50
60
70
Ambient temperature [°C]
= aligned with > 20 mm spacing
= aligned without spacing
10
20
30
40
R
L
& Error
97 96 95
2/T1 4/T2 6/T3
Derating diagram
Phoenix Contact 2015 © - all rights reserved
http://www.phoenixcontact.com
05/18/2015 Page 6 / 6