https://www.phoenixcontact.com/us/products/2904673
Power and error message module - TC-MACX-MCR-PTB - 2904673
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Power and fault signaling module, only for use on the Termination Carrier
Why buy this product
Simple or redundant supply, decoupled from diode, protected against polarization
Installation in zone 2 permitted (protection type “n” according to EN 60079-15)
Error message in the event of energy supply failure or fuse fault, can be selected and deselected via DIP switch
Bus cable error message for MACX MCR-...(2)NAM... devices connected via DIN rail connectors, can be selected and deselected via DIP switch
Relay output (PDT) and flashing LED for error messages
Supply current up to 2 A (max. 2 x 2,5 AT backup fuse required)
May only be used on the Termination Carrier
Undervoltage detection at the input, can be selected and deselected via DIP switch (set to 19.2 V supply voltage)
Key Commercial Data
Packing unit
1 STK
Custom tariff number
90303310
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
17.5 mm
Height
99 mm
Depth
114.5 mm
09/07/2016 Page 1 / 4
https://www.phoenixcontact.com/us/products/2904673
Power and error message module - TC-MACX-MCR-PTB - 2904673
Technical data
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 60 °C (only on Termination Carrier)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 61000-6-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Evaluation criterion
A
Flammability rating according to UL 94
V0
Conformance
CE-compliant
ATEX
II 3 G Ex nA nC IIC T4 Gc X
IECEx
Ex nA nC IIC T4 Gc X
UL, USA/Canada
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T5
Class I, Zone 2, Group IIC
Drawings
Dimensional drawing
17,5 7
114,5
99
Classifications
eCl@ss
eCl@ss 4.0
27210121
eCl@ss 4.1
27210121
eCl@ss 5.0
27210121
09/07/2016 Page 2 / 4
https://www.phoenixcontact.com/us/products/2904673
Power and error message module - TC-MACX-MCR-PTB - 2904673
Classifications
eCl@ss
eCl@ss 5.1
27210121
eCl@ss 6.0
27210121
eCl@ss 7.0
27210121
eCl@ss 8.0
27242601
eCl@ss 9.0
27242601
ETIM
ETIM 2.0
EC001431
ETIM 3.0
EC001596
ETIM 4.0
EC001596
ETIM 5.0
EC001596
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
Approvals
Approvals
Approvals
UL Listed / cUL Listed / cULus Listed
Ex Approvals
ATEX
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 330267
09/07/2016 Page 3 / 4
https://www.phoenixcontact.com/us/products/2904673
Power and error message module - TC-MACX-MCR-PTB - 2904673
Approvals
cUL Listed
cULus Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 330267
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com