https://www.phoenixcontact.com/us/products/2904903
Temperature measuring transducer - MACX PL-T-UIREL-UP-SP - 2904903
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Freely programmable temperature transducer with analog output and 3 limit value relays, standard configuration,
resistance thermometer with 2, 3 or 4-conductor technology, thermocouples, electrical isolation, wide-range
power supply, spring-cage connection, PLd
The figure shows a version with a
screw connection
Product Features
Key commercial data
Packing unit
1 pc
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
35 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
typ. 5 % ... 95 % (non-condensing)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
05/18/2015 Page 1 / 5
https://www.phoenixcontact.com/us/products/2904903
Temperature measuring transducer - MACX PL-T-UIREL-UP-SP - 2904903
Technical data
Input data
Sensor types (RTD) that can be used
Pt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC)
B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range
-200 °C ... 850 °C
Input signal range
0 Ω ... 50 kΩ
Potentiometer resistance range
0 Ω ... 50 kΩ
Input signal range
-1000 mV ... 1000 mV
Output data
Current output signal
4 mA ... 20 mA
Max. current output signal
22 mA
Load/output load current output
≤ 600 Ω (at 20 mA)
Behavior in the event of a sensor error
according to NE 43 or freely configurable
Output name
Relay output
Output description
1 SIL/PL
Contact type
2 PDT
Contact material
AgSnO2, hard gold-plated
Maximum switching voltage
250 V AC (250 V DC)
Maximum inrush current
2 A (250 V AC)
2 A (28 V DC)
0.2 A (120 V DC)
Power supply
Supply voltage range
24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Power consumption
< 2.4 W
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
16
Connection method
Push-in connection
General
Maximum transmission error
0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA)
Maximum temperature coefficient
0.01 %/K
Inflammability class according to UL 94
V0
Pollution degree
2
05/18/2015 Page 2 / 5
https://www.phoenixcontact.com/us/products/2904903
Temperature measuring transducer - MACX PL-T-UIREL-UP-SP - 2904903
Technical data
General
Surge voltage category
II
Housing material
PA 66-FR
Color
yellow
Designation
Input/output/power supply
Electrical isolation
300 Vrms (Rated insulation voltage (surge voltage category II; pollution
degree 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Designation
Input/output
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Designation
Input/power supply
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Designation
Input/switching output
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Conformance
CE-compliant
ATEX
II 3 G Ex nA nC ic IIC T4 Gc X
IECEx
Ex nA nC ic IIC T4 Gc X
UL, USA / Canada
UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Classifications
eCl@ss
eCl@ss 5.1
27210107
eCl@ss 6.0
27210120
ETIM
ETIM 4.0
EC002653
ETIM 5.0
EC002653
Approvals
Approvals
Approvals
UL Listed / cUL Listed / GL / Functional Safety / cULus Listed
05/18/2015 Page 3 / 5
https://www.phoenixcontact.com/us/products/2904903
Temperature measuring transducer - MACX PL-T-UIREL-UP-SP - 2904903
Approvals
Ex Approvals
ATEX / IECEx / UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
UL Listed
cUL Listed
GL
Functional Safety
cULus Listed
Drawings
Block diagram
IN
Sensor / Field
OUT
PLC / DCS
passive
RTD
TC
-
ϑ
ϑ
+
4.3
4.3
4.2
4.2
4.1
4.1
3.3
3.3
OUT 3.2
3.2
GND
I
+
3.1
Poti
3.6 34
ϑ
4.3
3.5 31
4.2
3.4 32
4.1
5.3
DI
5.3
5.2
5.2
5.1
5.1
2.6
24
2.5
21
NC 1.3
Power
24V ...230V AC/DC
1.2
2.4 22
1.1
Zone 2
Div. 2
1.6
14
1.5
11
DI
1.4 12
05/18/2015 Page 4 / 5
https://www.phoenixcontact.com/us/products/2904903
Phoenix Contact 2015 © - all rights reserved
http://www.phoenixcontact.com
05/18/2015 Page 5 / 5