MACX MCR-EX-IDS-2I-2I(-SP)
Output signal conditioner, Ex i, 2-channel
Data sheet
109174_en_02
1
© PHOENIX CONTACT 2021-05-20
Description
The 2-channel output signal conditioner is used for
controlling the intrinsically safe (Ex i) I/P converters,
regulating valves, and indicators installed in the Ex area.
Features
For operating the intrinsically safe SMART actuators, the
analog measuring value can be overlayed with digital
communication signals (HART) on the Ex or non-Ex side
and transmitted bidirectionally in an electrically isolated
manner.
–
–
–
–
–
–
–
–
Sockets are integrated into the COMBICON connectors for
connecting HART (HHT) communicators.
–
The device enables open-circuit and short-circuit
monitoring.
–
An open or short-circuited field circuit causes a high input
impedance on the controller side, thus enabling open-circuit
and short-circuit monitoring via the control system.
–
–
The device isolates and transmits 0.2/4 mA ... 20 mA
signals to the Ex area in an with intrinsic safety.
Readiness for operation is indicated via a green LED.
The device is approved for safety-related applications up to
SIL 2 (1oo1) / SIL 3 (1oo2).
–
–
2-channel
Input 0.2/4 mA ... 20 mA
Output 0.2/4 mA ... 20 mA, intrinsically safe [Ex ia]
Output load up to 700 Ω
Bidirectional HART signal transmission
Short circuit monitoring
Line break monitoring
Up to SIL 2 (1oo1) / SIL 3 (1oo2) in accordance with
IEC/EN 61508
Safe electrical isolation between input, output, and
supply
Energy supply and error indication possible via DIN rail
connector
Installation in Ex zone 2 permitted
Plug-in connection terminal blocks, either screw or
spring-cage connection technology (Push-in
technology)
Housing width of 12.5 mm
High transmission accuracy
WARNING: Explosion hazard
The device is an item of associated equipment with an EPL [Ga], [Da] (ATEX category 1) with "intrinsic safety" type
of protection and can be installed in zone 2 potentially explosive areas as an EPL Gc (ATEX category 3) device.
Intrinsically safe circuits can be led up to zone 0/zone 20. It satisfies the requirements of the following standards.
Comprehensive details are to be found in the EU Declaration of Conformity, which is enclosed and also available
on our website in the latest version:
IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 60079-11
When installing and operating the device, the applicable safety directives (including national safety directives),
accident prevention regulations, as well as general technical regulations must be observed.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
This document is valid for the products listed in the “Ordering data”.
MACX MCR-EX-IDS-2I-2I(-SP)
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 5
5
Safety regulations and installation notes................................................................................ 10
5.1
Installation notes ............................................................................................................... 10
5.2
Intrinsic safety ................................................................................................................... 10
5.3
Installation in Zone 2........................................................................................................... 10
5.4
Potentially dust-explosive areas ............................................................................................ 11
5.5
UL note ........................................................................................................................... 11
5.6
Safety-related applications (SIL) ............................................................................................ 11
6
Installation ............................................................................................................................. 12
6.1
Connection notes .............................................................................................................. 12
6.2
Electrostatic discharge ........................................................................................................ 12
6.3
Structure ......................................................................................................................... 12
6.4
Basic circuit diagram with connection terminal blocks ................................................................. 13
6.5
Input ............................................................................................................................... 13
6.6
Output (intrinsically safe) ..................................................................................................... 13
6.7
Power supply .................................................................................................................... 13
6.8
Dimensions ...................................................................................................................... 13
6.9
Mounting ......................................................................................................................... 14
6.10 Connecting the cables ........................................................................................................ 14
6.11 Startup ............................................................................................................................ 14
7
Comparison of the safety data ............................................................................................... 15
8
Safety-related applications .................................................................................................... 16
8.1
Safety function .................................................................................................................. 16
8.2
Safety integrity requirements ................................................................................................ 17
8.3
Conditions ....................................................................................................................... 20
8.4
Installation and startup ........................................................................................................ 20
8.5
Notes on operation ............................................................................................................. 21
8.6
Recurring checks ............................................................................................................... 21
8.7
Repair ............................................................................................................................. 21
8.8
Standards ........................................................................................................................ 22
8.9
Abbreviations ................................................................................................................... 22
109174_en_02
PHOENIX CONTACT
2/22
MACX MCR-EX-IDS-2I-2I(-SP)
3
Ordering data
Description
Type
Order No.
Pcs./Pkt.
2865421
1
2-channel Ex i output signal conditioner, HART. Isolates MACX MCR-EX-IDS-2I-2I-SP 2904931
and transmits 0/420 mA signals with intrinsic safety to a
load in the Ex area. Galvanic 4-way electrical isolation, line
fault detection, SIL 2 (SC3) in accordance with IEC 61508,
Push-in connection.
1
Accessories
Pcs./Pkt.
2-channel Ex i output signal conditioner, HART. Isolates MACX MCR-EX-IDS-2I-2I
and transmits 0/420 mA signals with intrinsic safety to a
load in the Ex area. Galvanic 4-way electrical isolation, line
fault detection, SIL 2 (SC3) in accordance with IEC 61508,
screw connection.
Type
Order No.
DIN rail connector (TBUS), 5-pos., for bridging the supply ME 6,2 TBUS-2 1,5/5-ST-3,81 2695439
voltage, can be snapped onto NS 35/... DIN rails
GY
according to EN 60715
10
Power and fault signaling module with screw connection, MACX MCR-PTB
including corresponding ME 17,5 TBUS 1,5/ 5-ST-3,81
GY DIN rail connector
2865625
1
Power and fault signaling module with Push-in
connection, including corresponding ME 17,5 TBUS 1,5/
5-ST-3,81 GY DIN rail connector
MACX MCR-PTB-SP
2924184
1
Universal termination carrier for connecting 16 MACX
Analog Ex i signal conditioners to digital or analog I/O
cards, via D-SUB connector, 37-pos. (1:1 connection),
with HART multiplexer connection
TC-D37SUB-AIO16-EX-PSUNI
2902932
1
Universal termination carrier for connecting 16 MACX
Analog Ex i signal conditioners to digital or analog I/O
cards, via D-SUB connector, 37-pos. (1:1 connection)
TC-D37SUB-ADIO16-EX-PUNI
2924854
1
Insulating sleeve, color: white
MPS-IH WH
0201663
10
Insulating sleeve, color: red
MPS-IH RD
0201676
10
Insulating sleeve, color: blue
MPS-IH BU
0201689
10
Insulating sleeve, color: yellow
MPS-IH YE
0201692
10
Insulating sleeve, color: green
MPS-IH GN
0201702
10
Insulating sleeve, color: gray
MPS-IH GY
0201728
10
Insulating sleeve, color: black
MPS-IH BK
0201731
10
Test plugs, with solder connection up to 1 mm² conductor MPS-MT
cross section, color: gray
0201744
10
Plastic label, Sheet, white, unlabeled, can be labeled with: UC-EMLP (11X9)
BLUEMARK ID COLOR, BLUEMARK ID, BLUEMARK
CLED, PLOTMARK, CMS-P1-PLOTTER, mounting type:
adhesive, lettering field size: 11 x 9 mm, Number of
individual labels: 10
0819291
10
109174_en_02
PHOENIX CONTACT
3/22
MACX MCR-EX-IDS-2I-2I(-SP)
Accessories
Type
Order No.
Pcs./Pkt.
Plastic label, Sheet, yellow, unlabeled, can be labeled
with: BLUEMARK ID COLOR, BLUEMARK ID,
BLUEMARK CLED, PLOTMARK, CMS-P1-PLOTTER,
mounting type: adhesive, lettering field size: 11 x 9 mm,
Number of individual labels: 10
UC-EMLP (11X9) YE
0822602
10
Plastic label, can be ordered: by sheet, white, labeled
according to customer specifications, mounting type:
adhesive, lettering field size: 11 x 9 mm
UC-EMLP (11X9) CUS
0824547
1
Plastic label, can be ordered: by sheet, yellow, labeled
according to customer specifications, mounting type:
adhesive, lettering field size: 11 x 9 mm
UC-EMLP (11X9) YE CUS
0824548
1
Plastic label, Sheet, silver, unlabeled, can be labeled with: UC-EMLP (11X9) SR
BLUEMARK ID COLOR, BLUEMARK ID, BLUEMARK
CLED, PLOTMARK, CMS-P1-PLOTTER, mounting type:
adhesive, lettering field size: 11 x 9 mm, Number of
individual labels: 10
0828094
10
Plastic label, can be ordered: by sheet, silver, labeled
according to customer specifications, mounting type:
adhesive, lettering field size: 11 x 9 mm, Number of
individual labels: 10
0828098
1
Plastic label, Card, white, unlabeled, can be labeled with: US-EMLP (11X9)
BLUEMARK ID COLOR, BLUEMARK ID,
THERMOMARK PRIME, THERMOMARK CARD 2.0,
THERMOMARK CARD, mounting type: adhesive,
lettering field size: 11 x 9 mm, Number of individual labels:
135
0828789
10
Plastic label, Card, yellow, unlabeled, can be labeled with: US-EMLP (11X9) YE
BLUEMARK ID COLOR, BLUEMARK ID,
THERMOMARK PRIME, THERMOMARK CARD 2.0,
THERMOMARK CARD, mounting type: adhesive,
lettering field size: 11 x 9 mm, Number of individual labels:
135
0828871
10
Plastic label, Card, silver, unlabeled, can be labeled with: US-EMLP (11X9) SR
BLUEMARK ID COLOR, BLUEMARK ID,
THERMOMARK PRIME, THERMOMARK CARD 2.0,
THERMOMARK CARD, mounting type: adhesive,
lettering field size: 11 x 9 mm, Number of individual labels:
135
0828872
10
Device marker, Sheet, white, unlabeled, can be labeled
LS-EMLP (11X9) WH
with: TOPMARK NEO, TOPMARK LASER, mounting
type: adhesive, lettering field size: 11 x 9 mm, Number of
individual labels: 255
0831678
10
Device marker, Sheet, silver, unlabeled, can be labeled
LS-EMLP (11X9) SR
with: TOPMARK NEO, TOPMARK LASER, mounting
type: adhesive, lettering field size: 11 x 9 mm, Number of
individual labels: 255
0831705
10
Device marker, Sheet, yellow, unlabeled, can be labeled LS-EMLP (11X9) YE
with: TOPMARK NEO, TOPMARK LASER, mounting
type: adhesive, lettering field size: 11 x 9 mm, Number of
individual labels: 255
0831732
10
109174_en_02
UC-EMLP (11X9) SR CUS
PHOENIX CONTACT
4/22
MACX MCR-EX-IDS-2I-2I(-SP)
4
Technical data
Input data
Current input signal
0.2 mA ... 20 mA (Function)
4 mA ... 20 mA (Safety)
0 mA ... 24 mA (Underload/overload range)
Input current
≤ 30 mA
Input impedance in the event of a line fault at the output
> 1 MΩ (If there is a line fault)
Line fault detection
Response threshold of input current >0.2 mA
Voltage drop
< 2.4 V (at 20 mA)
Output
Output description
Current output intrinsically safe
Current output signal
0.2 mA ... 20 mA (Function)
4 mA ... 20 mA (Safety)
0 mA ... 24 mA (Underload/overload range)
Transmission Behavior
1:1 to input signal
Load
100 Ω ... 700 Ω (20 mA)
100 Ω ... 650 Ω (20.5 mA)
100 Ω ... 500 Ω (24 mA)
Output ripple
< 20 mVrms
Non-load voltage
≤ 27 V
Wire-break detection
Load >10 kΩ
Short-circuit detection
Load 30 V DC,
usable in DC circuits, slow-blow) in the installation.
To protect the device against mechanical or electrical
damage, install it in suitable housing with an appropriate
degree of protection according to IEC/EN 60529.
During maintenance work, disconnect the device from
all effective power sources.
If the device is not used as described in the
documentation, the intended protection can be
negatively affected.
Thanks to its housing, the device has basic insulation to
the neighboring devices, for 300 Veff. If several devices
are installed next to each other, this has to be taken into
account, and additional insulation has to be installed if
necessary! If the neighboring device is equipped with
basic insulation, no additional insulation is necessary.
The voltages applied at the input, output, and power
supply are extra-low voltages (ELV). Depending on the
application, it can be the case that a voltage that is
dangerous to the touch (>30 V AC / >60 V DC) against
the ground could be present on the device. In this case,
a safe galvanic isolation exists between the input side
and the output side.
109174_en_02
Electrostatic discharge
NOTE: Electrostatic discharge
The device contains components that can be
damaged or destroyed by electrostatic discharge.
When handling the device, observe the necessary
safety precautions against electrostatic discharge
(ESD) according to EN 61340-5-1 and IEC 613405-1.
6.3
Structure
Figure 1
Structure
1
1.1
4
1.2
1.1
2.1
PH
FlacOENI
32 hsmX CO
82 ar NT
5 Bl kts AC
om tr. 8 T Gm
be
rg,
bH
Ge
& Co
rm
.KG
an
y
Iso
lati
on
ww
3.1
w.ph
Dri
oe
nix
co
ve
r
ntac
t.c
3.2
/ A
us
Iso
lati
2.1
on
str
en
tärk
er
1.2
1.1 2.2
2.1 3.2
3.1
PW
2.2
3.1
ww
w.ph
Dri
oe
nix
co
ve
r
ntac
t.c
3.2
om
/ A
us
ga
ng
nve
rs
1.2
PH
FlacOENI
32 hsmX CO
82 ar NT
5 Bl kts AC
om tr. 8 T Gm
be
rg,
bH
Ge
& Co
rm
.KG
an
y
om
ga
3
2.2
ng
str
en
nve
rs
tärk
er
R
PW
4.2
4.1 5.2
5.1
1
2
3
4
1.2
1.1 2.2
2.1 3.2
3.1
2
R
4.2
4.1 5.2
5.1
COMBICON plug-in, screw, or push-in connection
terminal with integrated test socket
Green “PWR” LED, power supply
Snap-on foot for DIN rail mounting
Connection for DIN rail connector
PHOENIX CONTACT
12/22
MACX MCR-EX-IDS-2I-2I(-SP)
6.4
Basic circuit diagram with connection terminal
blocks
Figure 2
Basic circuit diagram
Sensor / Field
OUT
-
4.2
P
+
4.1
P
5.2
+
-
CH1
3.1
5.2
2.2
–
–
6.6
–
–
Never connect the supply voltage directly to the
DIN rail connector. It is not permitted to draw
power from the DIN rail connector or from
individual modules.
+
-
2.2
+
Supply via the MACX Analog Ex module
2.1
1.2
1.1
Where the total current consumption of the aligned modules
does not exceed 400 mA, the power can be supplied directly
at the connection terminal blocks of the module.
Up to 16 modules can be supplied depending on the current
consumption of the modules.
GND +24V
Div. 1,2
6.5
3.2
+
+24V
NOTE
3.1
2.1
Power
Zone 0,1,2
Zone 20,21,22
+
4.1
GND
The supply voltage can be supplied via terminal points 1.1
and 1.2 or via the DIN rail connector.
AO
3.2
CH2
+
+
5.1
5.1
Power supply
PLC / DCS
IN
4.2
6.7
Zone 2
Div. 2
We recommend connecting a 630 mA fuse (normal-blow or
slow-blow) upstream.
Input
Channel 1 on terminal blocks 3.1 (+) and 3.2 (-)
Channel 2 on terminal blocks 2.1 (+) and 2.2 (-)
Output (intrinsically safe)
Channel 1 on terminal blocks 4.1 (+) and 4.2 (-)
Channel 2 on terminal blocks 5.1 (+) and 5.2 (-)
Supply via power and error message module
The MACX MCR-PTB (Order No. 2865625) or the MACX
MCR-PTB-SP (Order No. 2924184) supply and error
message module is used to provide the supply voltage to the
DIN rail connector.
Simple or redundant diode-decoupled power supply is
possible.
Depending on the current consumption of the modules, up
to 150 individual modules can be supplied by a supply that
is protected by a fuse.
The module has integrated error evaluation. An auxiliary
supply failure or fuse fault is indicated at a relay contact and
displayed via a flashing LED.
6.8
Dimensions
Figure 3
Dimensions
116 (SP)
112,5
12,5
7
114,5
99
109174_en_02
PHOENIX CONTACT
13/22
MACX MCR-EX-IDS-2I-2I(-SP)
6.9
Mounting
Figure 4
6.10
Mounting and removing
Connecting the cables
Screw Connection
Figure 5
Screw connection
AWG 24-14
2
0,2-2,5 mm
MACX MCR-...
A
7 mm
B
•
•
•
•
•
•
•
Mount the device on a 35 mm DIN rail according to
EN 60715.
When using the DIN rail connector, first insert it in the 35
mm DIN rail according to EN 60715 (A - C).
DIN rails with a height of 7.5 mm or more can be used.
The DIN rail connector is used to bridge the power
supply and communication.
The snap-in direction of the device and DIN rail
connector must be observed: snap-on foot on the
bottom and plug on the left.
Install the module in a suitable housing to meet the
requirements for the protection class.
Strip the wire by approximately 7 mm and crimp ferrules
to the end of the wires.
Insert the wire into the corresponding connection
terminal block.
Use a screwdriver to tighten the screw in the opening
above the connection terminal block.
Tightening torque: 0.6 Nm
Push-in connection:
Figure 6
•
•
•
•
Push-in connection
Strip the wire by approximately 8 mm and crimp ferrules
to the end of the wires.
Insert the wire into the corresponding connection
terminal block.
Push in the pushbutton with a screwdriver to release.
6.11
109174_en_02
0,5-0,6 Nm
5-7 lb In
Startup
Before startup, check that the device is operating and
wired correctly, in particular with regard to the wiring
and marking of the intrinsically safe circuits.
PHOENIX CONTACT
14/22
MACX MCR-EX-IDS-2I-2I(-SP)
7
Comparison of the safety data
WARNING: Explosion hazard
Compare the safety data before connecting a
device located in the Ex i area to this device.
Proof of intrinsic safety (mixed intrinsically safe
circuit)
Condition for the mixed intrinsically safe circuit with external
concentrated capacitances (Ci) and/or external
concentrated inductances (Li):
– Li