32-channel output relay module (one N/O contact) with a screw connection and a fuse (1 A). The voltage supply
and 50-pos. system connector are designed redundantly. Suitable for Yokogawa ADV551 card.
Key Commercial Data
Packing unit
1 STK
Minimum order quantity
10 STK
Custom tariff number
85369010
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
290 mm
Height
127.5 mm
Depth
44 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 50 °C
Ambient temperature (storage/transport)
-20 °C ... 70 °C
Input data
Nominal input voltage UN
24 V DC ((SELV, PELV))
Input voltage range in reference to UN
0.8 ... 1.1
Typical input current at UN
9 mA (per relay)
Type of protection
Free running
Protective circuit/component
Damping diode
Type of protection
Reverse polarity protection
Protective circuit/component
Polarity protection diode
Status display/channel
Yellow LED
09/07/2016 Page 1 / 3
https://www.phoenixcontact.com/us/products/2904937
Active module - UM-2KS50/32R/F/J/ADV551 - 2904937
Technical data
Output data
Contact type
Single contact, 1 N/O contact
Contact material
Ag alloy, hard gold-plated
Maximum switching voltage
30 V DC ((SELV, PELV))
Limiting continuous current
1A
General
Mounting position
any
Assembly instructions
In rows with zero spacing
Color
green
Designation
Air clearances and creepage distances, input
Standards/regulations
DIN EN 50178
Rated insulation voltage
63 V
Rated surge voltage
0.6 kV (basic insulation)
Degree of pollution
2
Overvoltage category
II
Designation
Air clearances and creepage distances, output
Standards/regulations
DIN EN 50178
Rated insulation voltage
63 V
Rated surge voltage
0.6 kV (basic insulation)
Degree of pollution
2
Overvoltage category
II
Designation
Air clearances and creepage distances, input/output
Standards/regulations
DIN EN 50178
Rated insulation voltage
63 V
Rated surge voltage
0.6 kV (basic insulation)
Degree of pollution
2
Overvoltage category
II
Connection data for connection 1
Connection name
Field level
Connection method
Screw connection
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 4 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12
Connection data for connection 2
Connection name
Controller level
Connection method
Yokogawa KS-compatible
09/07/2016 Page 2 / 3
https://www.phoenixcontact.com/us/products/2904937
Active module - UM-2KS50/32R/F/J/ADV551 - 2904937
Technical data
Connection data for connection 2
Stripping length
8 mm
Torque
0.5 Nm
Number of connections
2
Number of positions
50
Note
Usable system cables: Phoenix Contact YUC50, Yokogawa AKB331
Supported controller
Corresponding control
YOKOGAWA CS3000 CentumVP
Corresponding I/O card
ADV551
Standards and Regulations
Designation
Air clearances and creepage distances, input
Standards/regulations
DIN EN 50178
Degree of pollution
2
Overvoltage category
II
Designation
Air clearances and creepage distances, output
Standards/regulations
DIN EN 50178
Degree of pollution
2
Overvoltage category
II
Designation
Air clearances and creepage distances, input/output
Standards/regulations
DIN EN 50178
Degree of pollution
2
Overvoltage category
II
Classifications
eCl@ss
eCl@ss 5.1
27371001
eCl@ss 6.0
27371001
eCl@ss 8.0
27141152
eCl@ss 9.0
27141152
ETIM
ETIM 4.0
EC000196
ETIM 5.0
EC002780
Phoenix Contact 2016 © - all rights reserved