https://www.phoenixcontact.com/us/products/2904952
Safety relays - PSR-MS30-1NO-24DC-SC - 2904952
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Safety relay for emergency stop and safety doors up to SILCL 3, Cat. 4, PL e, 1 or 2-channel operation,
automatic start, cross-circuit detection, 1 enabling current path, US = 24 V DC, fixed screw terminal block
Your advantages
Up to Cat.4/PL e according to ISO 13849-1, SILCL 3 according to IEC 62061
Low housing width of just 6.8 mm
Two-channel control
1 enabling current path
Automatic activation
Cross-circuit detection
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4046356905008
Weight per Piece (excluding packing)
80.000 g
Custom tariff number
85371098
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
05/16/2020 Page 1 / 9
https://www.phoenixcontact.com/us/products/2904952
Safety relays - PSR-MS30-1NO-24DC-SC - 2904952
Technical data
Dimensions
Width
6.8 mm
Height
93.1 mm
Depth
102.5 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 60 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)
75 % (on average, 85% infrequently, non-condensing)
Maximum altitude
≤ 2000 m (Above sea level)
Power supply
Designation
A1/A2
Rated control circuit supply voltage US
24 V DC -15 % / +10 %
20.4 V DC ... 26.4 V DC
Rated control supply current IS
typ. 42 mA
Power consumption at US
typ. 1 W
Inrush current
4.5 A (Δt -15 mA (with Us/Ix to S22/0V)
Current consumption
< 5 mA (with Us/Ix to S12)
< 5 mA (with Us/Ix to S22)
> -5 mA (with Us/Ix to S22/0V)
Filter time
max. 1.5 ms (at S12, S22; test pulse width)
min. 7.5 ms (at S12, S22; test pulse rate)
Test pulse rate = 5 x Test pulse width
05/16/2020 Page 2 / 9
https://www.phoenixcontact.com/us/products/2904952
Safety relays - PSR-MS30-1NO-24DC-SC - 2904952
Technical data
Digital inputs
Max. permissible overall conductor resistance
150 Ω
Input name
Start circuit
S35
Description of the input
non-safety-related
NPN
Number of inputs
1
Input voltage range "1" signal
20.4 V DC ... 26.4 V DC
Inrush current
< 10 mA
Current consumption
< 10 mA
Max. permissible overall conductor resistance
150 Ω
Protective circuit/component
Suppressor diode
Relay outputs: enabling current path
Output name
Enabling current path
13/14
Output description
safety-related N/O contacts
Number of outputs
1 (undelayed)
Contact type
1 enabling current path
Contact material
AgSnO2
Switching voltage
min. 12 V AC/DC
max. 250 V AC/DC (Observe the load curve)
Limiting continuous current
6 A (observe derating)
Inrush current
min. 3 mA
max. 6 A
Sq. Total current
36 A (observe derating)
Switching capacity
min. 60 mW
Switching frequency
max. 0.5 Hz
Mechanical service life
10x 10 cycles
Output fuse
6 A gL/gG (N/O contact)
2
6
4 A gL/gG (for low-demand applications)
Times
Typical pickup time at US
< 250 ms (when controlled via A1)
Typical response time at US
< 175 ms
Typical release time at US
< 20 ms (when controlled via A1 or S12 and S22.)
Recovery time
< 500 ms
General
05/16/2020 Page 3 / 9
https://www.phoenixcontact.com/us/products/2904952
Safety relays - PSR-MS30-1NO-24DC-SC - 2904952
Technical data
General
Relay type
Electromechanical relay with forcibly guided contacts in accordance with
IEC/EN 61810-3 (EN 50205)
Nominal operating mode
100% operating factor
Net weight
69 g
Mounting position
vertical or horizontal
Mounting type
DIN rail mounting
Assembly instructions
See derating curve
Degree of protection
IP20
Min. degree of protection of inst. location
IP54
Housing material
PBT
Housing color
yellow
Operating voltage display
1 x green LED
Status display
2 x green LEDs
Connection data
Connection method
Screw connection
pluggable
no
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
26
Conductor cross section AWG max.
12
Stripping length
12 mm
Screw thread
M3
Safety-related characteristic data
Stop category
0
Designation
IEC 61508 - High demand
Safety Integrity Level (SIL)
3
Designation
IEC 61508 - Low demand
Safety Integrity Level (SIL)
3
Designation
EN ISO 13849
Performance level (PL)
e (4 A DC13; 5 A AC15; 8760 switching cycles/year)
Category
4
Designation
EN 62061
Safety Integrity Level Claim Limit (SIL CL)
3
Standards and Regulations
05/16/2020 Page 4 / 9
https://www.phoenixcontact.com/us/products/2904952
Safety relays - PSR-MS30-1NO-24DC-SC - 2904952
Technical data
Standards and Regulations
Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
DIN EN 50178
Rated insulation voltage
250 V AC
250 V AC
Rated surge voltage/insulation
Safe isolation, reinforced insulation 6 kV between input circuit and enabling
current path
Basic insulation 4 kV between all current paths and housing
Degree of pollution
2
Overvoltage category
III
Shock
15g
Vibration (operation)
10 Hz ... 150 Hz, 2g
Conformance
CE-compliant
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
05/16/2020 Page 5 / 9
https://www.phoenixcontact.com/us/products/2904952
Safety relays - PSR-MS30-1NO-24DC-SC - 2904952
Application drawing
05/16/2020 Page 6 / 9
https://www.phoenixcontact.com/us/products/2904952
Safety relays - PSR-MS30-1NO-24DC-SC - 2904952
Block diagram
Block diagram
Key:
1 = Current limitation
2 = Input circuit
3 = Voltage limitation
05/16/2020 Page 7 / 9
https://www.phoenixcontact.com/us/products/2904952
Safety relays - PSR-MS30-1NO-24DC-SC - 2904952
4 = Control circuit channel 1
5 = Control circuit channel 2
6 = Start channel 1 and 2
7 = Channel 1
K1, K2 = Force-guided elementary relays
Classifications
eCl@ss
eCl@ss 4.0
40020600
eCl@ss 4.1
40020600
eCl@ss 5.0
27371900
eCl@ss 5.1
27371900
eCl@ss 6.0
27371800
eCl@ss 7.0
27371819
eCl@ss 8.0
27371819
eCl@ss 9.0
27371819
ETIM
ETIM 5.0
EC001449
ETIM 6.0
EC001449
ETIM 7.0
EC001449
UNSPSC
UNSPSC 13.2
39121501
UNSPSC 18.0
39122205
UNSPSC 19.0
39122205
UNSPSC 20.0
39122205
UNSPSC 21.0
39122205
Approvals
Approvals
Approvals
UL Listed / cUL Listed / Functional Safety / EAC / Functional Safety / cULus Listed
Ex Approvals
Approval details
05/16/2020 Page 8 / 9
https://www.phoenixcontact.com/us/products/2904952
Safety relays - PSR-MS30-1NO-24DC-SC - 2904952
Approvals
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 140324
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 140324
Functional Safety
44-205-13755202
EAC
RU CDE.A*30.B.01082
Functional Safety
44-780-13755207
cULus Listed
Accessories
Accessories
Terminal marking
Zack Marker strip, flat - ZBF 6:UNBEDRUCKT - 0808710
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: PLOTMARK, CMS-P1-PLOTTER, mounting type:
snap into flat marker groove, for terminal block width: 6.2 mm, lettering field size: 5.15 x 6.15 mm, Number of individual
labels: 10
Phoenix Contact 2020 © - all rights reserved
http://www.phoenixcontact.com
05/16/2020 Page 9 / 9