https://www.phoenixcontact.com/us/products/2904957
Safety relays - PSR-MS55-1NO-1DO-24DC-SC - 2904957
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Safety relay for monitoring non-equivalent signal generators up to SILCL 3, Cat. 4, PL e, 2-channel, nonequivalent operation, manual, monitored start, 1 enabling current path, US = 24 V DC, fixed screw terminal block
Why buy this product
Up to Cat.4/PL e according to ISO 13849-1, SILCL 3 according to IEC 62061
Low housing width of just 6.8 mm
Two-channel non-equivalent control
1 enabling current path, 1 digital signal output
Manual and monitored activation
Key Commercial Data
Packing unit
1 STK
Weight per Piece (excluding packing)
80.000 g
Custom tariff number
85371099
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
6.8 mm
Height
93.1 mm
Depth
102.5 mm
Ambient conditions
09/07/2016 Page 1 / 6
https://www.phoenixcontact.com/us/products/2904957
Safety relays - PSR-MS55-1NO-1DO-24DC-SC - 2904957
Technical data
Ambient conditions
Ambient temperature (operation)
-40 °C ... 60 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)
75 % (on average, 85% infrequently, non-condensing)
Shock
15g
Vibration (operation)
10 Hz ...150 Hz, 2g
Maximum altitude
≤ 2000 m (Above sea level)
Input data
Rated control circuit supply voltage US
24 V DC -15 % / +10 %
Power consumption at US
typ. 1 W
Rated control supply current IS
typ. 42 mA
Inrush current
4.5 A (Δt = 120 µs at Us)
Current consumption
< 5 mA (with Us/Ix to S12)
< 5 mA (with Us/Ix to S13)
< 10 mA (with Us/Ix at the start circuit)
Voltage at input/start and feedback circuit
24 V DC -15 % / +10 %
Typical response time
< 175 ms
Typical release time
< 20 ms (when controlled via A1 or S12 and S13.)
Recovery time
< 500 ms
Status display
2 x green LEDs
Maximum switching frequency
0.5 Hz
Max. permissible overall conductor resistance
150 Ω
Filter time
1 ms (at A1 in the event of voltage dips at Us)
max. 1.5 ms (at S12, S13; test pulse width)
min. 7.5 ms (at S12, S13; test pulse rate)
Test pulse rate = 5 x Test pulse width
Output data
Contact type
1 enabling current path
Contact material
AgSnO2
Minimum switching voltage
12 V AC/DC
Maximum switching voltage
250 V AC/DC (Observe the load curve)
Limiting continuous current
6 A (observe derating)
Inrush current, minimum
3 mA
Maximum inrush current
6A
Sq. Total current
36 A (observe derating)
Switching capacity
min. 60 mW
2
09/07/2016 Page 2 / 6
https://www.phoenixcontact.com/us/products/2904957
Safety relays - PSR-MS55-1NO-1DO-24DC-SC - 2904957
Technical data
Output data
Output fuse
6 A gL/gG (N/O contact)
4 A gL/gG (for low-demand applications)
Alarm outputs
Number of outputs
1 (digital, PNP)
Voltage
22 V DC (Us - 2 V)
Current
max. 100 mA
Maximum inrush current
500 mA (Δt = 1 ms at Us)
Short-circuit protection
no
General
Relay type
Electromechanical relay with forcibly guided contacts in accordance with
IEC/EN 61810-3 (EN 50205)
Mechanical service life
10 x 10 cycles
Nominal operating mode
100% operating factor
Net weight
69 g
Mounting type
DIN rail mounting
Mounting position
vertical or horizontal
Degree of protection
IP20
Min. degree of protection of inst. location
IP54
Control
Two-channel
Housing material
PBT
Housing color
yellow
6
Connection data
Connection method
Screw connection
pluggable
no
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
26
Conductor cross section AWG max.
12
Stripping length
12 mm
Screw thread
M3
Safety-related characteristic data
Stop category
0
Designation
IEC 61508 - High demand
Safety Integrity Level (SIL)
3
09/07/2016 Page 3 / 6
https://www.phoenixcontact.com/us/products/2904957
Safety relays - PSR-MS55-1NO-1DO-24DC-SC - 2904957
Technical data
Safety-related characteristic data
Designation
IEC 61508 - Low demand
Safety Integrity Level (SIL)
3
Designation
EN ISO 13849
Performance level (PL)
e (4 A DC13; 5 A AC15; 8760 switching cycles/year)
Category
4
Designation
EN 62061
Safety Integrity Level Claim Limit (SIL CL)
3
Standards and Regulations
Shock
15g
Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
DIN EN 50178
Rated insulation voltage
250 V AC
Rated surge voltage/insulation
Safe isolation, reinforced insulation 6 kV between input circuit and enabling
current path
Basic insulation 4 kV between all current paths and housing
Degree of pollution
2
Overvoltage category
III
Vibration (operation)
10 Hz ...150 Hz, 2g
Conformance
CE-compliant
Drawings
Block diagram
A1
S12 S13
PSR-MS55
Block diagram
S34
IN
PWR
13
PSR-MS55
A1
S13 S34
K1
13
1
K1/K2
2
3
K2
24V DC
K1
9
A2
M1
K1
14
8
4
K2
K2
5
7
6
8
A2
S12
M1
14
Key:
1 = Input circuit
2 = Voltage limitation
3 = Start circuit
4 = Control circuit channel 1
5 = Control circuit signal output
6 = Control circuit channel 2
7 = Start channel 1 and 2
09/07/2016 Page 4 / 6
https://www.phoenixcontact.com/us/products/2904957
Safety relays - PSR-MS55-1NO-1DO-24DC-SC - 2904957
8 = Channel 1
9 = Diagnostics
K1, K2 = Force-guided elementary relays
Circuit diagram
24V DC
L
S3
S2
K1
11 12
13 14
K2
A1
S34
S12
S13
( )
( )
( )
13
K1
PSR-MS55
( )
A2
M1
K2
14
M
K1
K2
0V
N
Classifications
eCl@ss
eCl@ss 5.1
27371901
eCl@ss 6.0
27371819
eCl@ss 8.0
27371819
eCl@ss 9.0
27371819
ETIM
ETIM 5.0
EC001449
Approvals
Approvals
Approvals
UL Listed / cUL Listed / Functional Safety / EAC / cULus Listed
Ex Approvals
Approval details
09/07/2016 Page 5 / 6
https://www.phoenixcontact.com/us/products/2904957
Safety relays - PSR-MS55-1NO-1DO-24DC-SC - 2904957
Approvals
UL Listed
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324
Functional Safety 44-205-13755202
EAC 7500651.22.01.00244
cULus Listed
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
09/07/2016 Page 6 / 6
很抱歉,暂时无法提供与“2904957”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+1524.580701+197.22779