https://www.phoenixcontact.com/us/products/2904959
Repeater power supply - MACX PL-EX-RPSSI-2I - 2904959
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Ex i measuring transducer power supply and input signal conditioner, HART-transparent. Transfers supplied or
active 0/4 - 20 mA electrically isolated signals from the Ex area to two loads in the safe area. 4-way electrical
isolation, PLd, screw connection
Product Features
Key commercial data
Packing unit
1 pc
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
12.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
05/18/2015 Page 1 / 5
https://www.phoenixcontact.com/us/products/2904959
Repeater power supply - MACX PL-EX-RPSSI-2I - 2904959
Technical data
Ambient conditions
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Degree of protection
IP20
Input data
Signal input
Repeater power supply operation
Current input signal
4 mA ... 20 mA
Transmitter supply voltage
> 16 V (20 mA)
> 15.1 V (23 mA)
Voltage drop
approx. 3.9 V
Signal input
Signal conditioner operation
Current input signal
4 mA ... 20 mA
Voltage drop
approx. 3.9 V
Output data
Signal output
Repeater power supply operation
Current output signal
4 mA ... 20 mA (active)
Load/output load current output
< 450 Ω (20 mA)
< 380 Ω (23 mA)
Output ripple
< 20 mVrms
Output behavior in the event of an error
0 mA (Cable break in the input)
≥ 23 mA (Cable short-circuit in the input)
Signal output
Signal conditioner operation
Current output signal
4 mA ... 20 mA (active)
Load/output load current output
< 450 Ω (20 mA)
< 380 Ω (23 mA)
Output ripple
< 20 mVrms
Output behavior in the event of an error
0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Power supply
Designation
Repeater power supply operation
Supply voltage range
19.2 V DC ... 30 V DC (24 V DC (-20% ... +25%))
Max. current consumption
< 75 mA (24 V DC / 20 mA)
Power consumption
< 1.45 W (24 V DC/ 20 mA)
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
05/18/2015 Page 2 / 5
https://www.phoenixcontact.com/us/products/2904959
Repeater power supply - MACX PL-EX-RPSSI-2I - 2904959
Technical data
Connection data
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
7 mm
Screw thread
M3
Connection method
Screw connection
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
General
Maximum transmission error
< 0.1 % (of final value)
Transmission error, typical
< 0.05 % (of final value)
Maximum temperature coefficient
< 0.01 %/K
Step response (10-90%)
< 1.3 ms (for 4 mA ... 20 mA step)
Status display
Green LED (PWR supply voltage)
Inflammability class according to UL 94
V0
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Housing material
PA 66-FR
Color
yellow
Designation
Input/output/power supply
Electrical isolation
300 Vrms (Rated insulation voltage (surge voltage category II; pollution
degree 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Designation
Input/output
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Designation
Input/power supply
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Designation
Output 1/output 2
Electrical isolation
1.5 kV AC (50 Hz, 1 min., test voltage)
Conformance
CE-compliant, additionally EN 61326
ATEX
II (1) G [Ex ia Ga] IIC/IIB
II (1) D [Ex ia Da] IIIC
II 3 (1)G Ex nA [ia Ga] IIC/IIB T4 Gc
IECEx
[Ex ia Ga] IIC/IIB
[Ex ia Da]
Ex nA [ia Ga] IIC/IIB T4 Gc
UL, USA / Canada
UL 61010
Class I Div 2; IS for Class I, II, III Div 1
05/18/2015 Page 3 / 5
https://www.phoenixcontact.com/us/products/2904959
Repeater power supply - MACX PL-EX-RPSSI-2I - 2904959
Technical data
Data communication (bypass)
HART function
Yes
Protocols supported
HART
Safety data
Operation
Repeater power supply operation
Max. output voltage Uo
25.2 V
Max. output current Io
93 mA
Max. output power Po
587 mW
Group
IIC
Max. external inductivity Lo
2 mH
Max. external capacity Co
107 nF
Group
IIB
Max. external inductivity Lo
4 mH
Max. external capacity Co
820 nF
Safety-related maximum voltage Um
253 V AC (125 V DC)
Operation
Signal conditioner operation
Input voltage Ui
≤ 30 V
Input current Ii
≤ 150 mA
Max. internal inductance Li
negligible
Max. internal capacitance Ci
negligible
Classifications
eCl@ss
eCl@ss 5.1
27210121
eCl@ss 6.0
27200206
eCl@ss 8.0
27210121
ETIM
ETIM 4.0
EC002653
ETIM 5.0
EC002653
Approvals
Approvals
Approvals
UL Listed / cUL Listed / GL / cULus Listed
05/18/2015 Page 4 / 5
https://www.phoenixcontact.com/us/products/2904959
Repeater power supply - MACX PL-EX-RPSSI-2I - 2904959
Approvals
Ex Approvals
IECEx / ATEX / UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
UL Listed
cUL Listed
GL
cULus Listed
Drawings
Block diagram
OUT
IN
Sensor / Field
PLC / DCS
AI
passive
4.2 - 4.2
4.1
+
3.2
3.2
3.1
3.1
OUT 1
4.1
or
+
2.2
passive
OUT 2
2.1
5.2 - 5.2
5.1
+
GND
5.1
+24V
1.2
2.2
2.1
+
1.1
Power
GND +24V
Zone 0,1,2
Zone 20,21,22
Zone 2
Div. 1,2
Div. 2
Phoenix Contact 2015 © - all rights reserved
http://www.phoenixcontact.com
05/18/2015 Page 5 / 5