Primary-switched QUINT DC/DC converter for DIN rail mounting with SFB (selective fuse breaking) technology,
input: 12 V DC, output: 12 V DC/8 A
Product Description
QUINT DC/DC converter with maximum functionality
DC/DC converters alter the voltage level, regenerate the voltage at the end of long cables or enable the creation of independent supply systems by
means of electrical isolation.
QUINT DC/DC converters magnetically and therefore quickly trip circuit breakers with six times the nominal current, for selective and therefore costeffective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical
operating states before errors occur.
Your advantages
Reliable starting of difficult loads, thanks to the static POWER BOOST power reserve with up to 125% nominal current permanently
Preventive function monitoring indicates critical operating states before errors occur
Constant voltage: output voltage regenerated even at the end of long cables
Support conversion to various voltage levels
Electrical isolation: for setting up independent supply systems
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4046356908412
Weight per Piece (excluding packing)
860.000 g
Custom tariff number
85044030
Country of origin
China
Technical data
Dimensions
08/21/2020 Page 1 / 8
https://www.phoenixcontact.com/us/products/2905007
DC/DC converters - QUINT-PS/12DC/12DC/8 - 2905007
Technical data
Dimensions
Width
32 mm
Height
130 mm
Depth
125 mm
Width with alternative assembly
122 mm
Height with alternative assembly
130 mm
Depth with alternative assembly
35 mm
Installation distance right/left
0 mm / 0 mm (≤ 70 °C)
Installation distance right/left (active)
15 mm / 15 mm (≤ 70 °C)
Installation distance top/bottom
50 mm / 50 mm (≤ 70 °C)
Installation distance top/bottom (active)
50 mm / 50 mm (≤ 70 °C)
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested)
-40 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2
Input data
Nominal input voltage range
12 V DC
Input voltage range
9 V DC ... 18 V DC
Current consumption
12 A (12 V, IBOOST)
Inrush current
< 6 A (typical)
Mains buffering time
typ. 3 ms (12 V DC)
Input fuse
25 A (internal (device protection))
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
12 V DC ±1 %
Setting range of the output voltage (USet)
5 V DC ... 18 V DC (> 12 V DC, constant capacity restricted)
Nominal output current (IN)
8 A (-25 °C ... 60 °C)
POWER BOOST (IBoost)
10 A (-25°C ... 40°C permanent, UOUT = 12 V DC )
Selective Fuse Breaking (ISFB)
48 A (12 ms)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
yes
08/21/2020 Page 2 / 8
https://www.phoenixcontact.com/us/products/2905007
DC/DC converters - QUINT-PS/12DC/12DC/8 - 2905007
Technical data
Output data
Feedback voltage resistance
25 V DC
Protection against overvoltage at the output (OVP)
< 25 V DC
Max. capacitive load
unlimited
Active current limitation
15 A
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple
< 20 mVPP
Peak switching voltages nominal load
< 10 mVPP (20 MHz)
Maximum power dissipation in no-load condition
1.5 W
Power loss nominal load max.
11.8 W
General
Net weight
0.8 kg
Efficiency
> 89 %
MTBF (IEC 61709, SN 29500)
> 1614000 h (25 °C)
> 920000 h (40 °C)
Insulation voltage input/output
1.5 kV (type test)
1 kV (routine test)
Degree of protection
IP20
Protection class
III
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions