https://www.phoenixcontact.com/us/products/2905137
Extension module - PLC-V8C/PT-24DC/EM - 2905137
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
PLC logic extension logic module with 16 I/Os for plug-in connection to 8 PLC-INTERFACE terminal blocks for
extending the basic module (a maximum of two extension modules can be connected to a basic module), push-in
connection
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
140.0 g
Custom tariff number
85389099
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Power supply
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 26.4 V DC
Maximum input current at UN
65 mA
Protective circuit
Protection against polarity reversal
Surge protection
Status display
Green LED
Input data (digital)
Number of inputs
8 (2 configurable as analog)
Description of the input
EN 61131-2, type 3
Input voltage
24 V DC
Signal level "0" signal
11 V
10/29/2015 Page 1 / 7
https://www.phoenixcontact.com/us/products/2905137
Extension module - PLC-V8C/PT-24DC/EM - 2905137
Technical data
Input data (digital)
Input current "0" signal
< 1 mA
Input current "1" signal
typ. 2.5 mA
Status display
Yellow LED
Input data (analog)
Number of inputs
2 (IN6 and IN7 are configurable as analog)
Input voltage range
0 V ... 10 V
Input resistance
> 3.5 kΩ
Input data (PLC-INTERFACE)
Number of inputs
≤8
Description of the input
technical data depends on the PLC used
Input voltage
19 V DC
Typical current consumption
4 mA
Input resistance
< 100 mΩ
Output data
Number of outputs
≤8
Nominal output voltage
24 V DC
Nominal current
9 mA
General
Color
green
Mounting position
any
Assembly instructions
Can be plugged onto 8 x PLC-INTERFACE
Operating mode
100% operating factor
Degree of protection
IP20
Standards/regulations
Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
DIN EN 50178
Rated insulation voltage
50 V
Rated surge voltage
0.8 kV
Insulation
Basic insulation
Pollution degree
2
Overvoltage category
III
Connection data (supply and digital inputs)
Connection method
Push-in connection
Stripping length
9 mm
Conductor cross section solid
0.14 mm² ... 1.5 mm²
10/29/2015 Page 2 / 7
https://www.phoenixcontact.com/us/products/2905137
Extension module - PLC-V8C/PT-24DC/EM - 2905137
Technical data
Connection data (supply and digital inputs)
Conductor cross section flexible
0.14 mm² ... 1.5 mm²
0.25 mm² ... 0.5 mm² (Ferrule with plastic sleeve)
0.25 mm² ... 1.5 mm² (Ferrules without plastic sleeve)
AWG conductor cross section
26 ... 16
Number of connections
1
Number of positions
10
Note
Device supply and 8 x inputs
Connection data (PLC V8C bus)
Connection method
Insulation displacement connection
Number of connections
1
Number of positions
4
Ambient conditions
Ambient temperature (operation)
-20 °C ... 45 °C
Ambient temperature (storage/transport)
-20 °C ... 70 °C
Max. permissible relative humidity (operation)
95 %
Dimensions
Width
50 mm
Height
111 mm
Depth
87 mm
Classifications
eCl@ss
eCl@ss 5.1
27242608
eCl@ss 6.0
27242608
eCl@ss 8.0
27242216
ETIM
ETIM 4.0
EC001417
ETIM 5.0
EC001417
Approvals
Approvals
10/29/2015 Page 3 / 7
https://www.phoenixcontact.com/us/products/2905137
Extension module - PLC-V8C/PT-24DC/EM - 2905137
Approvals
Approvals
UL Listed / cUL Listed / EAC / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
EAC
cULus Listed
Drawings
10/29/2015 Page 4 / 7
https://www.phoenixcontact.com/us/products/2905137
Extension module - PLC-V8C/PT-24DC/EM - 2905137
Dimensional drawing
Circuit diagram
24V
0V
24 V
0 V IN 0 IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7
DI
DI
AI
87
AI
Internal Logic
40
24V
66
106
111
IN OUT
IN OUT
IN OUT
IN OUT
IN OUT
IN OUT
IN OUT
IN OUT
IO8
IO9
IO10
IO11
IO12
IO13
IO14
IO15
A2
A2
A2
A2
13
13
13
13
BB
BB
BB
BB
BB
BB
BB
BB
A1
A1
A1
A1
14
14
14
14
24V
0V
10/29/2015 Page 5 / 7
https://www.phoenixcontact.com/us/products/2905137
Extension module - PLC-V8C/PT-24DC/EM - 2905137
Circuit diagram
Circuit diagram
A1
230 V
N
BB
A2
PLC-V8C...
A1
13
A2 (-)
A1
BB
A2
12
24 V
0V
A1
A2 (-)
2966676 PLC-OSC- 24DC/ 24DC/ 2/ACT
14
2966171 PLC-RSC- 24DC/21
13
2966333 PLC-RSC-230UC/ 1AU/SEN
14
2904690 PLC-OSC-24DC/48DC/100/V8C/SEN
PLC-V8C...
230 V
N
14
11
14
BB
13
24 V
0V
Basic circuit diagram: inputs via PLC-INTERFACE with the example of one Basic circuit diagram: outputs via PLC-INTERFACE with the example of an
input terminal block with relay (230 V AC) and one input terminal block with output terminal block with relay, 1 PDT, and an output terminal block with
solid-state relay (24 V DC).
solid-state relay.
Connection diagram
IO 15
IO 13
IO 14
IO 11
IO 12
A2
13
BB
14
13
BB
14
13
BB
14
13
BB
14
IO 10
A2
A1
A2
A1
Contacting for
Extension module
24 V
0V
IN 0
IN 1
IN 2
IN 3
IN 4
IN 5
IN 6
IN 7
IO 8
A1
IO 9
PLC-V8C/.../EM
A2
A1
Contacting for
Basic or
Extension module
24 V
0V
24 V
0V
10/29/2015 Page 6 / 7
https://www.phoenixcontact.com/us/products/2905137
Extension module - PLC-V8C/PT-24DC/EM - 2905137
Circuit diagram
24 V
USB
0 V IN 0 IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7
Memory
DI
DI
AI
PLC-V8C/.../EM
PLC-V8C/.../EM
Internal Logic
T-BUS
PLC-V8C/.../BM
AI
24V
IN OUT
IN OUT
IO8
IO9
IN OUT
IO10
IN OUT
IO11
IN OUT
IN OUT
IO12
IO13
IN OUT
IO14
IN OUT
IO15
PLC-INTERFACE
Phoenix Contact 2015 © - all rights reserved
http://www.phoenixcontact.com
10/29/2015 Page 7 / 7
很抱歉,暂时无法提供与“2905137”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+801.655471+104.17718