https://www.phoenixcontact.com/us/products/2905228
Type 3 surge protection device - PLT-SEC-T3-120-FM - 2905228
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Pluggable device protection, according to type 3/class III, for 1-phase power supply networks with separate N and
PE (3-conductor system: L1, N, PE), with integrated surge-proof fuse and remote indication contact. Also suitable
for DC applications.
The illustration shows version PLTSEC-T3-230-FM
Product Features
Varistor-based device protection
Can be used without separate backup fuse thanks to integrated overcurrent protection
For 1-phase power supply units (AC/DC)
Pluggable
Optical status indicator via LED
With floating remote indication contact
Plugs can be checked with CHECKMASTER 2
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
91.6 g
Custom tariff number
85363030
Country of origin
Germany
Technical data
Dimensions
Height
90 mm
Width
17.7 mm
Depth
74.5 mm
Horizontal pitch
1 Div.
Ambient conditions
09/29/2015 Page 1 / 8
https://www.phoenixcontact.com/us/products/2905228
Type 3 surge protection device - PLT-SEC-T3-120-FM - 2905228
Technical data
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 70 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
Shock (operation)
30g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (10 ... 150 Hz/20 cycles/axis/X, Y, Z)
General
Standards/specifications
EN 61643-11 2012
IEC test classification
III
T3
EN type
T3
Number of ports
One
SPD design
Combination type
Mode of protection
L-N
L-PE
N-PE
(L+) - (L-)
(L+/L-) - PE
Mounting type
DIN rail: 35 mm
Color
light grey RAL 7035
traffic grey A RAL 7042
Housing material
PA 6.6-FR 20% GF
PA 6.6-FR
Pollution degree
2
Flammability rating according to UL 94
V-0
Type
DIN rail module, two-section, divisible
Number of positions
2
Surge protection fault message
Optical, remote indicator contact
Protective circuit
Nominal voltage UN
120 V AC (TN-S)
120 V AC (TT - only in use with RCD)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous voltage UC
150 V AC
150 V DC
Rated load current IL
26 A (30 °C)
09/29/2015 Page 2 / 8
https://www.phoenixcontact.com/us/products/2905228
Type 3 surge protection device - PLT-SEC-T3-120-FM - 2905228
Technical data
Protective circuit
Residual current IPE
≤ 5 µA
Nominal discharge current In (8/20) µs
3 kA
Standby power consumption PC
≤ 150 mVA (at UREF)
≤ 175 mVA (at UC)
Reference test voltage UREF
132 V AC
Combination wave UOC
6 kV
Voltage protection level Up (L-N)
≤ 0.85 kV
Voltage protection level Up (L-PE)
≤ 0.95 kV
Voltage protection level Up (N-PE)
≤ 0.95 kV
TOV behavior at UT (L-N)
240 V AC (5 s / withstand mode)
240 V AC (120 min / withstand mode)
TOV behavior at UT (L-PE)
240 V AC (5 s / withstand mode)
240 V AC (120 min / withstand mode)
1332 V AC (200 ms / safe failure mode)
TOV behavior at UT (N-PE)
1200 V AC (200 ms / safe failure mode)
Response time tA (L-N)
≤ 25 ns
Response time tA (L-PE)
≤ 100 ns
Response time tA (N-PE)
≤ 100 ns
Short-circuit current rating ISCCR
1.5 kA AC
0.25 kA DC
Max. backup fuse with branch wiring
Not required
Maximum backup fuse for through wiring
25 A (gG / B / C)
Indicator/remote signaling
Connection name
Remote fault indicator contact
Switching function
N/C contact
Operating voltage
250 V AC
125 V DC (200 mA DC)
Operating current
3 A AC
1 A DC (30 V DC)
Connection method
Screw connection
Screw thread
M3
Tightening torque
0.8 Nm
Stripping length
8 mm
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section solid min.
0.2 mm²
09/29/2015 Page 3 / 8
https://www.phoenixcontact.com/us/products/2905228
Type 3 surge protection device - PLT-SEC-T3-120-FM - 2905228
Technical data
Indicator/remote signaling
Conductor cross section solid max.
4 mm²
AWG conductor cross section
24 ... 12
Connection data
Connection method
Screw connection
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
AWG conductor cross section
24 ... 12 (IEC)
24 ... 12 (UL)
Screw thread
M3
Tightening torque
0.8 Nm
Stripping length
8 mm
UL specifications
UL class
SPD type 4CA
Maximum continuous operating voltage MCOV
150 V AC
150 V DC
Nominal voltage
120 V DC
Mode of protection
L-N
L-G
N-G
(L+) - (L-)
(L+) - G
(L-) - G
Power distribution system
1
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-N)
780 V
Measured limiting voltage MLV (L-G)
760 V
Measured limiting voltage MLV (N-G)
760 V
Measured limiting voltage MLV (L+) - (L-)
780 V
Measured limiting voltage MLV (L+) - G
760 V
Measured limiting voltage MLV (L-) - G
760 V
Nominal discharge current In
3 kA
09/29/2015 Page 4 / 8
https://www.phoenixcontact.com/us/products/2905228
Type 3 surge protection device - PLT-SEC-T3-120-FM - 2905228
Classifications
eCl@ss
eCl@ss 5.1
27130801
eCl@ss 6.0
27130806
eCl@ss 8.0
27130803
ETIM
ETIM 5.0
EC000942
Approvals
Approvals
Approvals
KEMA-KEUR / CCA / UL Recognized / cUL Recognized / EAC / GL / cULus Recognized
Ex Approvals
UL Recognized / cUL Recognized / cULus Recognized
Approvals submitted
Approval details
KEMA-KEUR
CCA
UL Recognized
cUL Recognized
EAC
09/29/2015 Page 5 / 8
https://www.phoenixcontact.com/us/products/2905228
Type 3 surge protection device - PLT-SEC-T3-120-FM - 2905228
Approvals
GL
cULus Recognized
Accessories
Accessories
Device marking
Label - EML (20XE)R - 0803452
Label, Roll, white, unlabeled, can be labeled with: THERMOMARK ROLL, THERMOMARK ROLL X1, THERMOMARK X,
THERMOMARK S1.1, Mounting type: Adhesive, Lettering field: continuous x 20 mm
Label - EML (20XE)R YE - 0803453
Label, Roll, yellow, unlabeled, can be labeled with: THERMOMARK ROLL, THERMOMARK ROLL X1, THERMOMARK
X, THERMOMARK S1.1, Mounting type: Adhesive, Lettering field: continuous x 20 mm
End block
End clamp - CLIPFIX 35 - 3022218
Quick mounting end clamp for NS 35/7,5 DIN rail or NS 35/15 DIN rail, with marking option, width: 9.5 mm, color: gray
Marker pen
09/29/2015 Page 6 / 8
https://www.phoenixcontact.com/us/products/2905228
Type 3 surge protection device - PLT-SEC-T3-120-FM - 2905228
Accessories
Marker pen - X-PEN 0,35 - 0811228
Marker pen without ink cartridge, for manual labeling of markers, labeling extremely wipe-proof, line thickness 0.35 mm
Spare parts
Type 3 surge protection plug - PLT-SEC-T3-120-P - 2905234
Replacement plug for type 3 device protection from the PLUGTRAB SEC T3 product range. 120 V nominal voltage.
Drawings
Diagram
Dimensional drawing
90
17,7
I [A]
30
20
20
30
40
50
60
70
80
T [°C]
67
74,5
10
90
Nominal current depending on ambient temperature
09/29/2015 Page 7 / 8
https://www.phoenixcontact.com/us/products/2905228
Type 3 surge protection device - PLT-SEC-T3-120-FM - 2905228
Product drawing
Circuit diagram
L
5
6
11
12
11
12
IN
OUT
PLUGTRAB
T3
PLT-SEC
T3-230-P
1
2
PE 3
N
4
Phoenix Contact 2015 © - all rights reserved
http://www.phoenixcontact.com
09/29/2015 Page 8 / 8