Plug-in lightning and surge arrester combination, in accordance with Type 1+2/Class I+II, for 1-phase power
supply networks, with separate N and PE (L1, PE, N).
Why buy this product
Directly coordinated combination of type 1 spark gap without line follow current and type 2 varistor arrester
Particularly suitable for maximum protection of sensitive devices in harsh environments
High continuous voltage of 350 V AC for 230/400 V AC networks with high voltage fluctuations
Pluggable
Low voltage protection level of 1.5 kV
Optical, mechanical status indicator
With floating remote indication contact
Plugs can be checked with CHECKMASTER 2
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4046356950169
Custom tariff number
85363030
Country of origin
Germany
Technical data
Dimensions
Height
95.2 mm
03/08/2017 Page 1 / 7
https://www.phoenixcontact.com/us/products/2905466
Lightning/surge arrester combination type 1+2 - FLT-SECT1+T2-1S-350/25-FM - 2905466
Technical data
Dimensions
Width
71.2 mm
Horizontal pitch
4 Div.
Ambient conditions
Degree of protection
IP20 (only when all terminal points are used)
Ambient temperature (operation)
-40 °C ... 80 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
Shock (operation)
30g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (5 - 500 Hz/2.5 h/X, Y, Z)
General
IEC test classification
I + II
T1 + T2
T1
I
EN type
T1 + T2
T1
IEC power supply system
TN-S
TT
Mode of protection
L-N
L-PE
N-PE
Mounting type
DIN rail: 35 mm
Color
light grey RAL 7035
traffic grey A RAL 7042
Housing material
PA 6.6-FR 20% GF
PBT-FR
Degree of pollution
2
Flammability rating according to UL 94
V-0
Design
DIN rail module, two-section, divisible
Number of positions
2
Surge protection fault message
Optical, remote indicator contact
Protective circuit
Nominal voltage UN
240 V AC (TN-S)
03/08/2017 Page 2 / 7
https://www.phoenixcontact.com/us/products/2905466
Lightning/surge arrester combination type 1+2 - FLT-SECT1+T2-1S-350/25-FM - 2905466
Technical data
Protective circuit
240 V AC (TT)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous voltage UC
350 V AC
Rated load current IL
125 A (< 55 °C)
Residual current IPE
≤ 0.01 mA
Nominal discharge current In (8/20) µs (L-N)
25 kA
Nominal discharge current In (8/20) µs (L-PE)
25 kA
Nominal discharge current In (8/20) µs (N-PE)
100 kA
Impulse discharge current (10/350) µs (L-N), charge
12.5 As
Impulse discharge current (10/350) µs (L-N), specific energy
160 kJ/Ω
Impulse discharge current (10/350) µs (L-N), peak current value Iimp
25 kA
Impulse discharge current (10/350) µs (L-PE), charge
12.5 As
Impulse discharge current (10/350) µs (L-PE), specific energy
160 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp
25 kA
Impulse discharge current (10/350) µs (N-PE), charge
50 As
Impulse discharge current (10/350) µs (N-PE), specific energy
2500 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp
100 kA
Follow current interrupt rating Ifi (L-N)
25 kA (264 V AC)
3 kA (350 V AC)
Follow current interrupt rating Ifi (N-PE)
100 A (350 V AC)
Short-circuit current rating ISCCR
25 kA (264 V AC)
3 kA (350 V AC)
Voltage protection level Up (L-N)
≤ 1.5 kV
Voltage protection level Up (L-PE)
≤ 2.2 kV
Voltage protection level Up (N-PE)
≤ 1.5 kV
Residual voltage Ures (L-N)
≤ 1.5 kV (at In)
≤ 1.2 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
Residual voltage Ures (L-PE)
≤ 2.2 kV (at In)
≤ 2 kV (at 10 kA)
≤ 1.8 kV (at 5 kA)
≤ 1.6 kV (at 3 kA)
Residual voltage Ures (N-PE)
≤ 1.5 kV (at In)
≤ 1 kV (at 10 kA)
03/08/2017 Page 3 / 7
https://www.phoenixcontact.com/us/products/2905466
Lightning/surge arrester combination type 1+2 - FLT-SECT1+T2-1S-350/25-FM - 2905466
Technical data
Protective circuit
≤ 0.9 kV (at 5 kA)
≤ 0.8 kV (at 3 kA)
TOV behavior at UT (L-N)
415 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
TOV behavior at UT (N-PE)
1200 V AC (200 ms / withstand mode)
Response time tA (L-N)
≤ 25 ns
Response time tA (N-PE)
≤ 100 ns
Max. backup fuse with branch wiring
315 A (gG)
Max. backup fuse with V-type through wiring
125 A (gG)
Additional technical data
Maximum discharge current Imax (8/20) µs (L-N)
50 kA
Maximum discharge current Imax (8/20) µs (L-PE)
50 kA
Maximum discharge current Imax (8/20) µs (N-PE)
100 kA
Indicator/remote signaling
Switching function
PDT contact
Operating voltage
12 V AC ... 250 V AC
125 V DC (200 mA DC)
Operating current
10 mA AC ... 1 A AC
1 A DC (30 V DC)
Connection method
Plug-in/screw connection via COMBICON
Screw thread
M2
Tightening torque
0.25 Nm
Stripping length
7 mm
Conductor cross section flexible
0.14 mm² ... 1.5 mm²
Conductor cross section solid
0.14 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection data
Connection method
Screw terminal blocks
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
18 mm
Conductor cross section flexible
2.5 mm² ... 35 mm²
Conductor cross section solid
2.5 mm² ... 35 mm²
Conductor cross section AWG
13 ... 2
03/08/2017 Page 4 / 7
https://www.phoenixcontact.com/us/products/2905466
Lightning/surge arrester combination type 1+2 - FLT-SECT1+T2-1S-350/25-FM - 2905466
Technical data
UL specifications
SPD Type
4CA
Maximum continuous operating voltage MCOV (L-N)
264 V AC
Maximum continuous operating voltage MCOV (L-G)
528 V AC
Maximum continuous operating voltage MCOV (N-G)
264 V AC
Nom. voltage
240 V AC
Mode of protection
L-N
L-G
N-G
Power distribution system
1S
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-N)
1340 V
Measured limiting voltage MLV (L-G)
1550 V
Measured limiting voltage MLV (N-G)
1080 V
Nominal discharge current In (L-N)
20 kA
Nominal discharge current In (L-G)
20 kA
Nominal discharge current In (N-G)
20 kA
UL indicator/remote signaling
Operating voltage
125 V AC
Operating current
1 A AC
Tightening torque
4 lbf-in.
Conductor cross section AWG
30 ... 14
UL connection data
Conductor cross section AWG
12 ... 2
Tightening torque
40 lbf-in.
Standards and Regulations
Standards/regulations
IEC 61643-11 2011
EN 61643-11 2012
Environmental Product Compliance
REACh SVHC
UV -328 25973-55-1
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
03/08/2017 Page 5 / 7
https://www.phoenixcontact.com/us/products/2905466
Lightning/surge arrester combination type 1+2 - FLT-SECT1+T2-1S-350/25-FM - 2905466
Approvals
Approvals
Approvals
UL Recognized / KEMA-KEUR / cUL Recognized / CCA / IECEE CB Scheme / GL / EAC / cULus Recognized
Ex Approvals
Approval details
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330181
KEMA-KEUR
http://www.dekra-certification.com
2185820.01
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330181
NTR-NL 7348
CCA
IECEE CB Scheme
http://www.iecee.org/
NL-34357
GL
http://exchange.dnv.com/tari/
13946-15 HH
EAC
RU CDE.A*30.B01561
03/08/2017 Page 6 / 7
https://www.phoenixcontact.com/us/products/2905466
Lightning/surge arrester combination type 1+2 - FLT-SECT1+T2-1S-350/25-FM - 2905466
Approvals
cULus Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Phoenix Contact 2017 © - all rights reserved
http://www.phoenixcontact.com
03/08/2017 Page 7 / 7
很抱歉,暂时无法提供与“2905466”相匹配的价格&库存,您可以联系我们找货
免费人工找货