4-way power supply doubler with plug-in connection technology. HART-transparent, 0(4) mA ... 20 mA input
signal, 0(4) mA ... 20 mA output signals. The device can be used in both signal and power supply doubler
modes. Push-in connection technology.
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4046356999441
Weight per Piece (excluding packing)
120.000 g
Sales Key
CK1411
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
6.2 mm
Height
110.5 mm
Depth
120.5 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Degree of protection
IP20
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Input data
07/16/2019 Page 1 / 12
https://www.phoenixcontact.com/au/products/2905629
Repeater power supply - MINI MCR-2-RPSS-I-2I-PT - 2905629
Technical data
Input data
Description of the input
Current input (sensor circuit)
Number of inputs
1
Current input signal
4 mA ... 20 mA ()
0 mA ... 20 mA ()
Input resistance current input
90 Ω (+1.6 V)
Transmitter supply voltage
> 19.5 V
Output data
Output name
Current output
Number of outputs
2
Current output signal
4 mA ... 20 mA (repeater power supply and isolator operation)
0 mA ... 20 mA (isolator operation)
Max. output current
25 mA
Load/output load current output
≤ 500 Ω (per channel)
Ripple
< 20 mVPP (at 500 Ω)
Transmission Behavior
1:1 to input signal
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail according to
EN 60715))
Typical current consumption
40 mA ()
65 mA ()
75 mA ()
130 mA ()
Power consumption
1.6 W (at IOUT = 20 mA, 500 Ω load)
Connection data
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section solid
0.14 mm² ... 2.5 mm² (with ferrule)
0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12 (flexible)
General
No. of channels
2
Maximum transmission error
0.05 % (of final value)
Maximum temperature coefficient
0.0075 %/K
Limit frequency (3 dB)
> 1 kHz (typ.)
Step response (10-90%)
< 400 µs (typ.)
Electrical isolation
Reinforced insulation in accordance with IEC 61010-1
07/16/2019 Page 2 / 12
https://www.phoenixcontact.com/au/products/2905629
Repeater power supply - MINI MCR-2-RPSS-I-2I-PT - 2905629
Technical data
General
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
300 V
Test voltage, input/output/supply
3 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color
gray
Housing material
PBT
Mounting position
any
Assembly instructions
The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T5
Class I, Zone 2, Group IIC T5
Certificate of classification
DNV GL TAA000021E
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Data communication (bypass)
Limit frequency (3 dB)
approx. 1 kHz
EMC data
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Standards/regulations
EN 61000-4-2
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
Designation
Conducted interferences
07/16/2019 Page 3 / 12
https://www.phoenixcontact.com/au/products/2905629
Repeater power supply - MINI MCR-2-RPSS-I-2I-PT - 2905629
Technical data
Standards and Regulations
Standards/regulations
EN 61000-4-6
Electrical isolation
Reinforced insulation in accordance with IEC 61010-1
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T5
Class I, Zone 2, Group IIC T5
DNV GL-Temperature
B
DNV GL-Humidity
B
DNV GL-Vibration
A
DNV GL-EMC
A
DNV GL-Enclosure
Required protection according to the Rules shall be provided upon
installation on board
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Block diagram
IN
Sensor / Field
PWR IN+
OUT
TI+
+ 1
1
2
PLC / DCS
TI+
5 +
PWR OUT+
/IN –
2-wire
OUT I-
Pictogram
5
OUT 1 I+
– 2
pas.
6 –
6
OUT1
OUT 1 I-
IN I- / IN I+
TI+
+ 3
PWR+
OUT 2 I+
POWER
8 –
– 4
OUT I–
3
OUT I+
2
I
OUT2
FM
POWER
pas.
4-wire
I
IN
FM
PWR–
PWR+
US
PWR-
OUT 2 I–
1
I
7 +
4
Zone 2
Classifications
eCl@ss
eCl@ss 4.0
27210120
eCl@ss 4.1
27210120
07/16/2019 Page 4 / 12
https://www.phoenixcontact.com/au/products/2905629
Repeater power supply - MINI MCR-2-RPSS-I-2I-PT - 2905629
Classifications
eCl@ss
eCl@ss 5.0
27210120
eCl@ss 5.1
27210100
eCl@ss 6.0
27210100
eCl@ss 7.0
27210120
eCl@ss 8.0
27210120
eCl@ss 9.0
27210120
ETIM
ETIM 4.0
EC002653
ETIM 5.0
EC002653
ETIM 6.0
EC002653
ETIM 7.0
EC002653
Approvals
Approvals
Approvals
UL Listed / cUL Listed / DNV GL / cULus Listed
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
DNV GL
https://approvalfinder.dnvgl.com/
TAA000021E
cULus Listed
07/16/2019 Page 5 / 12
https://www.phoenixcontact.com/au/products/2905629
Repeater power supply - MINI MCR-2-RPSS-I-2I-PT - 2905629
Accessories
Accessories
Communication module
Communication module - MINI MCR-2-V8-MOD-RTU - 2905634
Eight MINI Analog Pro signal conditioners and measuring transducers can be quickly and easily integrated into a
Modbus/RTU network via a communication adapter.
Communication module - MINI MCR-2-V8-MOD-TCP - 2905635
Eight MINI Analog Pro signal conditioners and measuring transducers can be quickly and easily integrated into a
Modbus/TCP network via a communication adapter.
Communication module - MINI MCR-2-V8-PB-DP - 2905636
Eight MINI Analog Pro signal conditioners and measuring transducers can be quickly and easily integrated into a
PROFIBUS DP network via a communication adapter.
Device marking
Marker for end clamp - UCT-EM (30X5) - 0801505
Marker for end clamp, Sheet, white, unlabeled, can be labeled with: TOPMARK NEO, TOPMARK LASER,
BLUEMARK ID COLOR, BLUEMARK ID, BLUEMARK CLED, THERMOMARK PRIME, THERMOMARK CARD 2.0,
THERMOMARK CARD, mounting type: snapped into marker carrier, lettering field size: 30 x 5 mm
Marker for end clamp - UCT-EM (30X5) YE - 0830340
Marker for end clamp, Sheet, yellow, unlabeled, can be labeled with: TOPMARK NEO, TOPMARK LASER,
BLUEMARK ID COLOR, BLUEMARK ID, BLUEMARK CLED, THERMOMARK PRIME, THERMOMARK CARD 2.0,
THERMOMARK CARD, mounting type: snapped into marker carrier, lettering field size: 30 x 5 mm
07/16/2019 Page 6 / 12
https://www.phoenixcontact.com/au/products/2905629
Repeater power supply - MINI MCR-2-RPSS-I-2I-PT - 2905629
Accessories
Plastic label - UC-EMLP (15X5) - 0819301
Plastic label, Sheet, white, unlabeled, can be labeled with: BLUEMARK ID COLOR, BLUEMARK ID, BLUEMARK
CLED, PLOTMARK, CMS-P1-PLOTTER, mounting type: adhesive, lettering field size: 15 x 5 mm
Plastic label - UC-EMLP (15X5) YE - 0822615
Plastic label, Sheet, yellow, unlabeled, can be labeled with: BLUEMARK ID COLOR, BLUEMARK ID, BLUEMARK
CLED, PLOTMARK, CMS-P1-PLOTTER, mounting type: adhesive, lettering field size: 15 x 5 mm
Plastic label - UC-EMLP (15X5) SR - 0828095
Plastic label, Sheet, silver, unlabeled, can be labeled with: BLUEMARK ID COLOR, BLUEMARK ID, BLUEMARK
CLED, PLOTMARK, CMS-P1-PLOTTER, mounting type: adhesive, lettering field size: 15 x 5 mm
Plastic label - US-EMLP (15X5) - 0828790
Plastic label, Card, white, unlabeled, can be labeled with: BLUEMARK ID COLOR, BLUEMARK ID, THERMOMARK
PRIME, THERMOMARK CARD 2.0, THERMOMARK CARD, mounting type: adhesive, lettering field size: 15 x 5 mm
Plastic label - US-EMLP (15X5) YE - 0828873
Plastic label, Card, yellow, unlabeled, can be labeled with: BLUEMARK ID COLOR, BLUEMARK ID, THERMOMARK
PRIME, THERMOMARK CARD 2.0, THERMOMARK CARD, mounting type: adhesive, lettering field size: 15 x 5 mm
07/16/2019 Page 7 / 12
https://www.phoenixcontact.com/au/products/2905629
Repeater power supply - MINI MCR-2-RPSS-I-2I-PT - 2905629
Accessories
Plastic label - US-EMLP (15X5) SR - 0828874
Plastic label, Card, silver, unlabeled, can be labeled with: BLUEMARK ID COLOR, BLUEMARK ID, THERMOMARK
PRIME, THERMOMARK CARD 2.0, THERMOMARK CARD, mounting type: adhesive, lettering field size: 15 x 5 mm
DIN rail connector
DIN rail bus connectors - ME 6,2 TBUS-2 1,5/5-ST-3,81 GN - 2869728
DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos.
Evaluation unit
Monitoring module - MINI MCR-2-FM-RC - 2904504
Fault monitoring module with plug-in connection technology for evaluating and reporting group errors from the
FM system and for monitoring the supply voltages. Error message via N/C contact. Screw connection technology,
standard configuration
Monitoring module - MINI MCR-2-FM-RC-PT - 2904508
Fault monitoring module with plug-in connection technology for evaluating and reporting group errors from the FM
system and for monitoring the supply voltages. Error message via N/C contact. Push-in connection technology,
standard configuration
Labeled device marker
Marker for end clamp - UCT-EM (30X5) CUS - 0801589
Marker for end clamp, can be ordered: by sheet, white, labeled according to customer specifications, mounting type:
snapped into marker carrier, lettering field size: 30 x 5 mm
07/16/2019 Page 8 / 12
https://www.phoenixcontact.com/au/products/2905629
Repeater power supply - MINI MCR-2-RPSS-I-2I-PT - 2905629
Accessories
Marker for end clamp - UCT-EM (30X5) YE CUS - 0830348
Marker for end clamp, can be ordered: by sheet, yellow, labeled according to customer specifications, mounting type:
snapped into marker carrier, lettering field size: 30 x 5 mm
Plastic label - UC-EMLP (15X5) CUS - 0824550
Plastic label, can be ordered: by sheet, white, labeled according to customer specifications, mounting type: adhesive,
lettering field size: 15 x 5 mm
Plastic label - UC-EMLP (15X5) YE CUS - 0824551
Plastic label, can be ordered: by sheet, yellow, labeled according to customer specifications, mounting type:
adhesive, lettering field size: 15 x 5 mm
Plastic label - UC-EMLP (15X5) SR CUS - 0828099
Plastic label, can be ordered: by sheet, silver, labeled according to customer specifications, mounting type: adhesive,
lettering field size: 15 x 5 mm
Plastic label - US-EMLP (15X5) CUS - 0830076
Plastic label, can be ordered: By card, white, labeled according to customer specifications, mounting type: adhesive,
lettering field size: 15 x 5 mm
07/16/2019 Page 9 / 12
https://www.phoenixcontact.com/au/products/2905629
Repeater power supply - MINI MCR-2-RPSS-I-2I-PT - 2905629
Accessories
Plastic label - US-EMLP (15X5) YE CUS - 0830077
Plastic label, can be ordered: By card, yellow, labeled according to customer specifications, mounting type: adhesive,
lettering field size: 15 x 5 mm
Plastic label - US-EMLP (15X5) SR CUS - 0830078
Plastic label, can be ordered: By card, silver, labeled according to customer specifications, mounting type: adhesive,
lettering field size: 15 x 5 mm
Power module
Power terminal block - MINI MCR-2-PTB - 2902066
Power terminal with plug-in connection technology for delivering the supply voltage to the DIN rail connector.
Monitoring of the supply voltages in combination with the fault monitoring module. Screw connection technology
Power terminal block - MINI MCR-2-PTB-PT - 2902067
Power terminal with plug-in connection technology for delivering the supply voltage to the DIN rail connector.
Monitoring of the supply voltages in combination with the fault monitoring module. Push-in connection technology
Power supply
Power supply unit - MINI-SYS-PS-100-240AC/24DC/1.5 - 2866983
Primary-switched MINI POWER supply for DIN rail mounting, input: 1-phase, output: 24 V DC/1.5 A
07/16/2019 Page 10 / 12
https://www.phoenixcontact.com/au/products/2905629
Repeater power supply - MINI MCR-2-RPSS-I-2I-PT - 2905629
Accessories
Power supply unit - MINI-PS-100-240AC/24DC/1.5/EX - 2866653
Primary-switched power supply MINI POWER for DIN rail mounting, input: 1-phase, output: 24 V DC/1,5 A, for the
potentially explosive area
Programming cable
Cable adapter - GW HART USB MODEM - 1003824
USB HART modem cable for communication between a PC and HART devices, cable length: 1m.
System adapter
System adapter - MINI MCR-2-V8-FLK 16 - 2901993
Eight MINI Analog Pro signal conditioners and measuring transducers can be connected to a controller with minimal
cabling effort and without any errors using system adapters and system cabling.
Terminal marking
Marker strip - SK 5,0 WH:REEL - 0805221
Marker strip, Roll, white, unlabeled, can be labeled with: THERMOMARK ROLL 2.0, THERMOMARK ROLL,
THERMOMARK ROLL X1, THERMOMARK ROLLMASTER 300/600, THERMOMARK X1.2, mounting type:
adhesive, for terminal block width: 5 mm, lettering field size: continuous x 5 mm
DIN rail bus connectors - ME 6,2 TBUS-2 1,5/5-ST-3,81 GY - 2695439
DIN rail connector (TBUS), 5-pos., for bridging the supply voltage, can be snapped onto NS 35/... DIN rails according
to EN 60715
07/16/2019 Page 11 / 12
https://www.phoenixcontact.com/au/products/2905629
Phoenix Contact 2019 © - all rights reserved
http://www.phoenixcontact.com
07/16/2019 Page 12 / 12