https://www.phoenixcontact.com/au/products/2906234
Current transformer - PACT RCP-4000A-UIRO-PT-D95 - 2906234
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Set consisting of a 4-way signal conditioner with push-in connection technology and a Rogowski coil 300 mm
in length/95 mm in diameter for AC current measurement on busbars and power lines.
The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4055626048284
Weight per Piece (excluding packing)
400.600 g
Country of origin
Germany
Sales Key
CK4A12
Technical data
Dimensions
Width
6.2 mm
Height
110.5 mm
Depth
120.5 mm
Ambient conditions
Ambient temperature (operation)
-30 °C ... 80 °C (Measuring coil)
-40 °C ... 70 °C (Measuring transducer)
Ambient temperature (storage/transport)
-40 °C ... 80 °C (Measuring coil)
-40 °C ... 85 °C (Measuring transducer)
Maximum altitude
> 4000 m
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Measuring coil degree of protection
IP67 (not assessed by UL)
Measuring transducer degree of protection
IP20
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
07/16/2019 Page 1 / 5
https://www.phoenixcontact.com/au/products/2906234
Current transformer - PACT RCP-4000A-UIRO-PT-D95 - 2906234
Technical data
Measuring transducer supply
Nominal supply voltage
24 V DC
Nominal supply voltage range
9.6 V DC ... 30 V DC
Power consumption
≤ 1 W (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
Measuring coil input data
Frequency measuring range
40 Hz ... 20000 Hz
Position error
100 kΩ
Measuring coil signal output
Output signal (at 50 Hz)
100 mV (no load, at 1,000 A)
Output voltage (in no-load operation)
VOUT = M * dI/dt
Output voltage (sinusoidal, in no-load operation)
100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I =
1,000 A))
Measuring transducer signal output
Current output signal
0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
0 mA ... 10 mA (via DIP switch)
2 mA ... 10 mA (via DIP switch)
0 mA ... 21 mA (can be set via software)
Voltage output signal
0 V ... 10 V (via DIP switch)
2 V ... 10 V (via DIP switch)
0 V ... 5 V (via DIP switch)
1 V ... 5 V (via DIP switch)
0 V ... 10.5 V (can be set via software)
Load/output load current output
≤ 600 Ω (20 mA)
General data, measuring coil
Length of measuring coil
300 mm
Diameter of measuring coil
8.3 mm ±0.2 mm
Length of signal cable
3000 mm
Conductor structure signal line
2x 0.22 mm (Signal (tinned))
1x 0.22 mm (Shielding (tinned))
Coil material
Elastollan
Housing material
PC
07/16/2019 Page 2 / 5
https://www.phoenixcontact.com/au/products/2906234
Current transformer - PACT RCP-4000A-UIRO-PT-D95 - 2906234
Technical data
General data, measuring coil
Insulation
double insulation
Rated insulation voltage
1000 V AC (rms CAT III)
600 V AC (rms CAT IV)
Test voltage
10.45 kV (DC / 1 min.)
Basic accuracy
很抱歉,暂时无法提供与“2906234”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+4509.122701+564.17262