https://www.phoenixcontact.com/gb/products/2906239
Voltage measuring transducers - MACX MCR-VAC - 2906239
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MACX MCR voltage transducer, for AC voltages from 0 V ... 20 V AC to 0 ... 660 V AC, output signal: 0 V ...
10 V/0(4) ... 20 mA
Why buy this product
Adjustable voltage ranges
Bidirectional output signals
3-way isolation
ZERO/SPAN adjustment ±20%
Tool-free parameterization of measured values
Teach-in configuration of the measured value range
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4055626051000
Weight per Piece (excluding packing)
226.200 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
04/17/2018 Page 1 / 5
https://www.phoenixcontact.com/gb/products/2906239
Voltage measuring transducers - MACX MCR-VAC - 2906239
Technical data
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C (non-condensing)
Maximum altitude
≤ 2000 m
Input data
Input voltage range
0 V ... 550 V AC
Input resistance
5500 kΩ
Input voltage range
0 V ... 370 V AC
Input resistance
3700 kΩ
Input voltage range
0 V ... 250 V AC
Input resistance
2500 kΩ
Input voltage range
0 V ... 170 V AC
Input resistance
1700 kΩ
Input voltage range
0 V ... 120 V AC
Input resistance
1200 kΩ
Input voltage range
0 V ... 80 V AC
Input resistance
800 kΩ
Input voltage range
0 V ... 54 V AC
Input resistance
800 kΩ
Input voltage range
0 V ... 36 V AC
Input resistance
800 kΩ
Input voltage range
0 V ... 24 V AC
Input resistance
240 kΩ
Nom. voltage
+ 660 V AC
Output data
Output name
Voltage output
Voltage output signal
0 V ... 10 V
2 V ... 10 V
Max. output voltage
≤ 11 V
Load/output load voltage output
> 10 kΩ
Ripple
50 mV
Output name
Current output
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. output current
≤ 22 mA
Load/output load current output
< 500 Ω
Power supply
Nominal supply voltage
24 V DC (-20 % ... +25 %)
Supply voltage range
19.2 V DC ... 30 V DC
Max. current consumption
< 45 mA
04/17/2018 Page 2 / 5
https://www.phoenixcontact.com/gb/products/2906239
Voltage measuring transducers - MACX MCR-VAC - 2906239
Technical data
Connection data
Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Stripping length
8 mm
Screw thread
M3
Connection technology
Screw connection
General
Maximum transmission error
< 1 % (from a measuring range final value, 45 ... 65 Hz)
< 1.3 % (from a measuring range final value, 65 ... 405 Hz)
Maximum temperature coefficient
< 0.015 %/K
Frequency measuring range
45 Hz ... 405 Hz
Alignment zero
± 20 %
Alignment span
± 20 %
Step response (10-90%)
< 180 ms
Test voltage
5.3 kV AC (50 Hz, 1 min.)
Degree of pollution
2
Standards/regulations
IEC 61010-1
IEC 61010-2-030
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color
gray
Mounting position
any
Assembly instructions
Can be aligned with spacing = 10 mm
Conformance
CE-compliant
UL, USA/Canada
UL 61010 Listed
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Frequency range
45 Hz ... 405 Hz
Standards/regulations
IEC 61010-1
IEC 61010-2-030
Low Voltage Directive
Conformance with Low Voltage Directive
Conformance
CE-compliant
UL, USA/Canada
UL 61010 Listed
04/17/2018 Page 3 / 5
https://www.phoenixcontact.com/gb/products/2906239
Voltage measuring transducers - MACX MCR-VAC - 2906239
Technical data
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Block diagram
OUT
IN
550 V 4.1
370 V 4.2
250 V 4.3
170 V 4.4
3.1
RMS
3.3
3.2
3.4
120 V 5.1
80 V
5.2
54 V
36 V
5.3
24 V
5.4
N
1.3
1.4
OUT I
OUT U
GNDI
GNDU
+24 VDC
GND
Classifications
eCl@ss
eCl@ss 5.0
27210190
eCl@ss 5.1
27210190
eCl@ss 6.0
27210125
eCl@ss 7.0
27210125
eCl@ss 8.0
27210125
eCl@ss 9.0
27210125
ETIM
ETIM 4.0
EC002477
ETIM 5.0
EC002477
ETIM 6.0
EC002477
Approvals
Approvals
Approvals
UL Listed / cUL Listed / cULus Listed
Ex Approvals
04/17/2018 Page 4 / 5
https://www.phoenixcontact.com/gb/products/2906239
Voltage measuring transducers - MACX MCR-VAC - 2906239
Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330267
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330267
cULus Listed
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
04/17/2018 Page 5 / 5
很抱歉,暂时无法提供与“2906239”相匹配的价格&库存,您可以联系我们找货
免费人工找货