TRIO-UPS-2G/3AC/24DC/20 - Uninterruptible power
supply
2906367
https://www.phoenixcontact.com/pc/products/2906367
Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user
documentation. Our general terms of use for downloads are valid.
TRIO UPS - UPS with integrated power supply, USB (Modbus/RTU), DIN rail mounting, Push-in connection, input: 3-phase, output: 24
V DC / 20 A
Product description
Supply DC loads reliably and save space with the TRIO uninterruptible power supplies. An input grid is no longer necessary for startup. Connected
industrial PCs can be shut down easily via the integrated USB interface.
Your advantages
• Space saving: Combination of UPS module and power supply in the same housing
• Long buffer times, thanks to large selection of VRLA energy storage systems
• USB interface for connection to higher-level controllers such as industrial PCs
• Startup from energy storage possible, even without mains input
• Universal range of possible applications, thanks to a comprehensive package of approvals and an extended temperature range
• Easy installation, thanks to push-in connection technology
Commercial data
Item number
2906367
Packing unit
1 pc
Minimum order quantity
1 pc
Product key
CMUO33
Catalog page
Page 355 (C-4-2019)
GTIN
4055626068053
Weight per piece (including packing)
2,081 g
Weight per piece (excluding packing)
1,733 g
Customs tariff number
85044095
Country of origin
CN
Jan 8, 2024, 9:09 AM
Page 1 (19)
TRIO-UPS-2G/3AC/24DC/20 - Uninterruptible power
supply
2906367
https://www.phoenixcontact.com/pc/products/2906367
Technical data
Input data
Input voltage range
3x 400 V AC ... 500 V AC -20 % ... +15 %
2x 400 V AC ... 500 V AC -10 % ... +10 %
Voltage type of supply voltage
AC
Inrush current
< 17.5 A
2
Inrush current integral (I t)
< 0.76 A2s
Frequency range (fN)
50 Hz ... 60 Hz (±10 %)
Mains buffering time
≥ 25 ms (400 V AC)
Switch-on time
typ. 200 ms
Typical current consumption
3x 1.3 A (400 V AC)
Input fuse
6.3 A (slow-blow, internal)
Signal Bat.-Start
Connection labeling
3.6
Signalization designation
Bat.-Start
Low signal
Connection to SGnd with < 2.7 kΩ
High signal
Open (> 200 kΩ between Bat.-Start and SGnd)
Signal Remote
Connection labeling
3.5
Signalization designation
Remote
Low signal
Connection to SGnd with < 2.7 kΩ
High signal
Open (> 35 kΩ between Remote and SGnd)
Output data
Efficiency
typ. 93 % (400 V AC)
typ. 92 % (480 V AC)
typ. 94 % (Battery operation)
Derating
> 60 °C (2.5%/K of POut nom.)
Crest factor
2.5 (400 V AC)
2.6 (480 V AC)
Switch-over time
< 20 ms
UPS connection in parallel
yes, with diode module uncoupled
UPS connection in series
no
Energy storage device connection in parallel
yes
Feedback voltage resistance
≤ 35 V DC
Protection against overvoltage at the output (OVP)
< 30 V DC
Residual ripple
< 20 mV
Control deviation
< 0.3 % (change in load, static 10 % ... 90 %)
< 5.9 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.05 % (change in input voltage ±10 %)
Rise time
< 30 ms
Jan 8, 2024, 9:09 AM
Page 2 (19)
TRIO-UPS-2G/3AC/24DC/20 - Uninterruptible power
supply
2906367
https://www.phoenixcontact.com/pc/products/2906367
Permissible backup fuse
B10
Mains operation
Output voltage
24 V DC
Output voltage range
24 V DC ... 28 V DC (> 24 V constant capacity)
Output current IN
20 A
Dynamic Boost (IDyn.Boost)
30 A
Output power POUT (UN, IOUT = IN)
480 W
Maximum no-load power dissipation
< 3.6 W (400 V AC)
Power loss nominal load max.
< 36 W (480 V AC)
Battery operation
Output voltage
UBAT -0.1 V DC
Output voltage range
18 V DC ... 30 V DC
Output current IN
20 A
Signal Alarm
Connection labeling
3.2
Signalization designation
Alarm
Type of signaling
LED red
Switching output
Transistor output, active
Output voltage
24 V DC
Continuous load current
20 mA
LED status indicator
red
Signal Battery mode
Connection labeling
3.3
Signalization designation
Battery mode
Type of signaling
Yellow LED
Switching output
Transistor output, active
Output voltage
24 V DC
Continuous load current
20 mA
LED status indicator
yellow
Signal DC OK
Connection labeling
3.1
Signalization designation
DC OK
Type of signaling
Green LED
Switching output
Transistor output, active
Output voltage
24 V DC
Continuous load current
20 mA
LED status indicator
green
Signal Ready
Connection labeling
3.4
Signalization designation
Ready
Switching output
Transistor output, active
Jan 8, 2024, 9:09 AM
Page 3 (19)
TRIO-UPS-2G/3AC/24DC/20 - Uninterruptible power
supply
2906367
https://www.phoenixcontact.com/pc/products/2906367
Output voltage
24 V DC
Continuous load current
20 mA
Energy storage
Nominal voltage UN
24 V DC
End-of-charge voltage
max. 30 V DC
Charging current (Configurable)
0.2 A ... 3 A (-25 °C ... 40 °C)
Charging current (Reduced)
3 A ... 0 A (40 °C ... 65 °C)
Charging current (Preset)
2.1 A (-25 °C ... 40 °C)
Charging current ()
3A
Nominal capacity range
4 Ah ... 40 Ah
Battery technology
VRLA-AGM
Charge characteristic curve
IU0U
Connection data
Input
Position
1.x
Conductor connection
Connection method
Push-in connection
rigid
0.2 mm² ... 4 mm²
flexible
0.2 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve
0.25 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve
0.25 mm² ... 1.5 mm²
rigid (AWG)
24 ... 12
Stripping length
10 mm
Output
Position
2.x
Conductor connection
Connection method
Push-in connection
rigid
0.2 mm² ... 10 mm²
flexible
0.2 mm² ... 6 mm²
flexible with ferrule without plastic sleeve
0.25 mm² ... 6 mm²
flexible with ferrule with plastic sleeve
0.25 mm² ... 4 mm²
rigid (AWG)
24 ... 8
Stripping length
15 mm
Signal
Position
3.x
Conductor connection
Connection method
Push-in connection
rigid
0.2 mm² ... 1.5 mm²
flexible
0.2 mm² ... 1.5 mm²
Jan 8, 2024, 9:09 AM
Page 4 (19)
TRIO-UPS-2G/3AC/24DC/20 - Uninterruptible power
supply
2906367
https://www.phoenixcontact.com/pc/products/2906367
flexible with ferrule without plastic sleeve
0.2 mm² ... 1.5 mm²
flexible with ferrule with plastic sleeve
0.2 mm² ... 0.75 mm²
rigid (AWG)
24 ... 16
Stripping length
8 mm
Battery
Position
4.x
Conductor connection
Connection method
Push-in connection
rigid
0.2 mm² ... 10 mm²
flexible
0.2 mm² ... 6 mm²
flexible with ferrule without plastic sleeve
0.25 mm² ... 6 mm²
flexible with ferrule with plastic sleeve
0.25 mm² ... 4 mm²
rigid (AWG)
24 ... 8
Stripping length
15 mm
Interfaces
Interface
USB (Modbus/RTU)
Number of interfaces
1
Connection method
MINI-USB Type B
Locking
Screw
Electrical properties
Number of phases
3.00
Insulation voltage input/output
4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE
500 V AC
500 V AC (routine test)
Insulation voltage input / PE
type test
2 kV AC (routine test)
Product properties
Product type
DC UPS with integrated power supply
Product family
TRIO UPS
MTBF (IEC 61709, SN 29500)
> 1108720 h (400 V AC, at 25°C)
> 680194 h (400 V AC, at 40°C)
> 323816 h (400 V AC, at 60°C)
Insulation characteristics
Protection class
I
Degree of pollution
2
Life expectancy (electrolytic capacitors)
Current
20 A
Temperature
40 °C
Jan 8, 2024, 9:09 AM
Page 5 (19)
TRIO-UPS-2G/3AC/24DC/20 - Uninterruptible power
supply
2906367
https://www.phoenixcontact.com/pc/products/2906367
Time
71552 h
Additional text
400 V AC
Dimensions
Item dimensions
Width
88 mm
Height
130 mm
Depth
160 mm
Item dimensions with alternative mounting
Width
160 mm
Height
130 mm
Depth
88 mm
Installation dimensions
Installation distance right/left
0 mm / 0 mm
Installation distance top/bottom
50 mm / 50 mm
Mounting
Mounting type
DIN rail mounting
Assembly instructions
alignable: horizontally 0 mm, vertically 50 mm
Mounting position
horizontal DIN rail NS 35, EN 60715
Material specifications
Flammability rating according to UL 94 (housing / terminal
blocks)
V0
Housing material
Metal
Hood version
PC
Side element version
Aluminum
Environmental and real-life conditions
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 4000 m (> 2000 m, observe derating)
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (At +25°C, non-condensing)
Shock
30g, 18 ms in accordance with IEC 60068-2-27
Vibration (operation)
很抱歉,暂时无法提供与“2906367”相匹配的价格&库存,您可以联系我们找货