https://www.phoenixcontact.com/us/products/2906820
Surge protection device - TTC-6-1X2-M-EX-24DC-UT-I - 2906820
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection with integrated status indicator and disconnect knife for a 2-wire floating Ex i signal circuit, e.g.,
0(4) ... 20 mA current loop, HART-compatible.
Your advantages
Space-saving and inexpensive with a narrow overall width of just 6.2 mm
Signaling without additional auxiliary power, thanks to the mechanical status indicator
Optional remote signaling module monitors up to 40 items, without additional wiring
Signal circuits easily interrupted for maintenance work, thanks to vertical knife disconnection
Safe behavior in the event of overload, thanks to the integrated disconnect device
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4055626135830
Weight per Piece (excluding packing)
60.000 g
Custom tariff number
85363010
Country of origin
Germany
Technical data
Dimensions
Height
105.8 mm
Width
6.2 mm +0.1 mm
Depth
83.5 mm (incl. DIN rail 7.5 mm)
Ambient conditions
06/28/2020 Page 1 / 10
https://www.phoenixcontact.com/us/products/2906820
Surge protection device - TTC-6-1X2-M-EX-24DC-UT-I - 2906820
Technical data
Ambient conditions
Ambient temperature (operation)
-40 °C ... 85 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 %
Altitude
≤ 2000 m (amsl (above mean sea level))
Degree of protection
IP20
General
Housing material
PBT
Flammability rating according to UL 94
V-0
Color
sky blue RAL 5015
Mounting type
DIN rail: TH 35 - 7.5 mm
Type
DIN rail module, one-piece
Direction of action
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/ShieldEarth Ground
Protective circuit
IEC test classification
C1
C2
C3
D1
Nominal voltage UN
24 V DC
Maximum continuous voltage UC
30 V DC
Rated current
600 mA (40 °C)
Operating effective current IC at UC
≤ 5 µA
Residual current IPE
≤ 1 µA
Nominal discharge current In (8/20) µs (line-line)
5 kA
Nominal discharge current In (8/20) µs (line-earth)
5 kA
Pulse discharge current Iimp (10/350) µs (line-line)
0.5 kA
Pulse discharge current Iimp (10/350) µs (line-earth)
0.5 kA
Total discharge current Itotal (8/20) µs
10 kA
Voltage protection level Up (line-line)
≤ 55 V (C1 - 1 kV/500 A)
≤ 65 V (C2 - 10 kV / 5 kA)
≤ 55 V (C3 - 100 A)
Voltage protection level Up (line-earth)
≤ 900 V (C1 - 1 kV/500 A)
≤ 1.05 kV (C2 - 10 kV / 5 kA)
≤ 1.4 kV (C3 - 100 A)
Voltage protection level Up static (line-line)
≤ 50 V (C1 - 1 kV/500 A)
≤ 65 V (C2 - 10 kV / 5 kA)
06/28/2020 Page 2 / 10
https://www.phoenixcontact.com/us/products/2906820
Surge protection device - TTC-6-1X2-M-EX-24DC-UT-I - 2906820
Technical data
Protective circuit
Voltage protection level Up static (line-earth)
≤ 900 V (C1 - 1 kV/500 A)
≤ 1.05 kV (C2 - 10 kV / 5 kA)
Response time tA (line-line)
≤ 1 ns
Response time tA (line-earth)
≤ 100 ns
Input attenuation aE, sym.
typ. 0.3 dB (≤ 250 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm system
typ. 940 kHz
Capacity (line-line)
typ. 2 nF
Resistance per path
1.65 Ω ±20 %
Surge protection fault message
optical
Max. required back-up fuse
630 mA (FF)
Impulse durability (line-line)
C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
Impulse durability (line-earth)
C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-line)
≤ 700 ms
Pulse reset time (line-earth)
≤ 30 ms
Connection data
Connection method
Screw connection
Screw thread
M3
Tightening torque
0.5 Nm ... 0.6 Nm
Stripping length
8 mm
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section solid
0.2 mm² ... 4 mm²
Conductor cross section AWG
24 ... 12
Standards and Regulations
Standards/specifications
EN 60079-0 2012 + A11:2013
EN 60079-11 2012
EN 61643-21 2001 + A1:2009 + A2:2013
IEC 60079-0 2011 (modified) + corrigendum 2012 + corrigendum 2013
IEC 60079-11 2008
IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
General
Maximum inner capacitance Ci
negligible
06/28/2020 Page 3 / 10
https://www.phoenixcontact.com/us/products/2906820
Surge protection device - TTC-6-1X2-M-EX-24DC-UT-I - 2906820
Technical data
General
Max. internal inductance Li
negligible
Max. input current Ii
400 mA (T4 / ≤ 50 °C)
350 mA (T6 / ≤ 35 °C)
Max. input voltage Ui
30 V DC
Insulation voltage to ground
> 180 V DC
Ambient temperature (operation)
-40 °C ... 35 °C (T6 / 85 °C)
-40 °C ... 50 °C (T4 / 135 °C)
Conformity / approvals
UL, USA/Canada
Class I, Div. 2, Groups A, B, C, D T4
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Diagram
06/28/2020 Page 4 / 10
https://www.phoenixcontact.com/us/products/2906820
Surge protection device - TTC-6-1X2-M-EX-24DC-UT-I - 2906820
Dimensional drawing
Pictogram
06/28/2020 Page 5 / 10
https://www.phoenixcontact.com/us/products/2906820
Surge protection device - TTC-6-1X2-M-EX-24DC-UT-I - 2906820
Circuit diagram
Classifications
eCl@ss
eCl@ss 10.0.1
27130807
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130800
eCl@ss 7.0
27130807
eCl@ss 8.0
27130807
eCl@ss 9.0
27130807
ETIM
ETIM 2.0
EC000943
ETIM 3.0
EC000943
ETIM 4.0
EC000943
ETIM 5.0
EC000943
ETIM 6.0
EC000943
ETIM 7.0
EC000943
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
UNSPSC 18.0
39121620
06/28/2020 Page 6 / 10
https://www.phoenixcontact.com/us/products/2906820
Surge protection device - TTC-6-1X2-M-EX-24DC-UT-I - 2906820
Classifications
UNSPSC
UNSPSC 19.0
39121620
UNSPSC 20.0
39121620
UNSPSC 21.0
39121620
Approvals
Approvals
Approvals
DNV GL / CSA / UL Listed / CSAus / cCSAus
Ex Approvals
IECEx / ATEX / UL Listed / cUL Listed / INMETRO / cULus Listed
Approval details
DNV GL
https://approvalfinder.dnvgl.com/
TAE000027G
CSA
http://www.csagroup.org/services-industries/product-listing/
70136717
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 138168
CSAus
http://www.csagroup.org/services-industries/product-listing/
70136717
cCSAus
06/28/2020 Page 7 / 10
https://www.phoenixcontact.com/us/products/2906820
Surge protection device - TTC-6-1X2-M-EX-24DC-UT-I - 2906820
Accessories
Accessories
End block
End clamp - CLIPFIX 35-5 - 3022276
Quick mounting end clamp for NS 35/7,5 DIN rail or NS 35/15 DIN rail, with marking option, with parking option for
FBS...5, FBS...6, KSS 5, KSS 6, width: 5.15 mm, color: gray
Labeled terminal marker
Zack Marker strip, flat - ZBF 6 CUS - 0825027
Zack Marker strip, flat, Strip, can be ordered: Strip, white, labeled according to customer specifications, mounting type:
snap into flat marker groove, for terminal block width: 6.2 mm, lettering field size: 5.15 x 6.15 mm, Number of individual
labels: 10
Zack Marker strip, flat - ZBF 6,QR:FORTL.ZAHLEN - 0808765
Zack Marker strip, flat, Strip, white, labeled, Printed vertically: consecutive numbers 1 ... 10, 11 ... 20, etc. up to 91 ...
100, mounting type: snap into flat marker groove, for terminal block width: 6.2 mm, lettering field size: 5.15 x 6.15 mm,
Number of individual labels: 10
Marker pen
Marker pen - X-PEN 0,35 - 0811228
Marker pen without ink cartridge, for manual labeling of markers, labeling extremely wipe-proof, line thickness 0.35 mm
Terminal marking
06/28/2020 Page 8 / 10
https://www.phoenixcontact.com/us/products/2906820
Surge protection device - TTC-6-1X2-M-EX-24DC-UT-I - 2906820
Accessories
Zack Marker strip, flat - ZBF 6:UNBEDRUCKT - 0808710
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: PLOTMARK, CMS-P1-PLOTTER, mounting type:
snap into flat marker groove, for terminal block width: 6.2 mm, lettering field size: 5.15 x 6.15 mm, Number of individual
labels: 10
Zack Marker strip, flat - ZBF 6/WH-100:UNBEDRUCKT - 0808736
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: PLOTMARK, CMS-P1-PLOTTER, mounting type:
snap into flat marker groove, for terminal block width: 6.2 mm, lettering field size: 5.15 x 6.15 mm, Number of individual
labels: 10
Additional products
Remote signaling set - TTC-6-FMRS-UT - 2907810
Module set for the optical monitoring and floating remote signaling of neighboring surge protective devices of the
TERMITRAB complete product range.
Separating plate - TTC-EX-PP - 1011977
Partition plate for NS-35/7,5 DIN rails to ensure a clearance of 50 mm between the remote signaling module and surge
protection in TTC-EX systems.
Shield connection - SSA 3-6 - 2839295
Shield fast connection for 3 ... 6 mm cable diameter. Potential connecting cable: 200 mm, 1 mm², color: black
06/28/2020 Page 9 / 10
https://www.phoenixcontact.com/us/products/2906820
Surge protection device - TTC-6-1X2-M-EX-24DC-UT-I - 2906820
Accessories
Shield connection - SSA 5-10 - 2839512
Shield fast connection for 5 ... 10 mm cable diameter. Potential connecting cable: 200 mm, 1 mm², color: black
Phoenix Contact 2020 © - all rights reserved
http://www.phoenixcontact.com
06/28/2020 Page 10 / 10