https://www.phoenixcontact.com/gb/products/2906919
Extension module - PLC-APT-PT100-IN - 2906919
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Pt 100/Pt1000 temperature transducer for PLC logic logic modules (Generation 2 only), single-channel, signal
type (Pt 100, Pt 1000) can be configured via DIP switch, Push-in connection
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4055626155500
Weight per Piece (excluding packing)
50.300 g
Custom tariff number
85389099
Country of origin
Germany
Technical data
Dimensions
Width
6.2 mm
Height
80 mm
Depth
86 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 50 °C
Ambient temperature (storage/transport)
-20 °C ... 70 °C
Supply
Rated control circuit supply voltage US
24 V DC
Rated control supply voltage range with reference to US
0.8 ... 1.1
Rated control supply current IS
14 mA
Type of protection
Reverse polarity protection
Surge protection
Operating voltage display
Green LED
07/24/2018 Page 1 / 4
https://www.phoenixcontact.com/gb/products/2906919
Extension module - PLC-APT-PT100-IN - 2906919
Technical data
Supply
Indication
Red LED
Input data
Input name
Analog input resistance
Sensor types (RTD) that can be used
Pt 100 (IEC 60751, α = 0,00385)
Connection technology
2-wire
Sensor input current
~ 900 µA
Maximum temperature coefficient
0.01 %/K
Temperature measuring range
-50 °C ... 200 °C
Maximum transmission error
1%
Surge voltage protection
> 33 V
Input name
Analog input resistance
Sensor types (RTD) that can be used
Pt 1000 (IEC 60751, α = 0.00385)
Connection technology
2-wire
Sensor input current
~ 900 µA
Maximum temperature coefficient
0.01 %/K
Temperature measuring range
-50 °C ... 200 °C
Maximum transmission error
1%
Surge voltage protection
> 33 V
Output data
Output name
Digital output
General
Operating mode
100% operating factor
Degree of protection
IP20
Mounting position
any
Assembly instructions
In rows with zero spacing
Connection data
Connection method
Push-in connection
Stripping length
8 mm
Conductor cross section solid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 14
Number of connections
4
Standards and Regulations
Designation
Air clearances and creepage distances
Standards/regulations
DIN EN 50178
Rated insulation voltage
50 V
Rated surge voltage
0.5 kV
Insulation
Basic insulation
07/24/2018 Page 2 / 4
https://www.phoenixcontact.com/gb/products/2906919
Extension module - PLC-APT-PT100-IN - 2906919
Technical data
Standards and Regulations
Degree of pollution
2
Overvoltage category
III
Conformance
CE-compliant
UL, USA/Canada
UL 508 Listed
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Block diagram
Sensor / Field
PLC logic
OUT
Logic
module
PLC-V8C/..
IN
1
Data-
5
µC D
2
+ 24V
6
Data+
3
GND
4
Classifications
eCl@ss
eCl@ss 5.0
27242201
eCl@ss 7.0
27242201
eCl@ss 8.0
27242201
eCl@ss 9.0
27242201
ETIM
ETIM 4.0
EC001420
ETIM 5.0
EC001420
ETIM 6.0
EC001420
Approvals
Approvals
Approvals
UL Listed / cUL Listed / EAC / cULus Listed
Ex Approvals
07/24/2018 Page 3 / 4
https://www.phoenixcontact.com/gb/products/2906919
Extension module - PLC-APT-PT100-IN - 2906919
Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
EAC
RU CDE.A*30.B.01082
cULus Listed