https://www.phoenixcontact.com/gb/products/2907780
Digital display - FA MCR-FD-TUI-UI-2REL-UP - 2907780
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Multifunctional process indicator in field housing for monitoring and displaying analog measurement data.
Universal inputs permit connection of current, voltage, RTDs, and TCs. Two relay change-over contact
outputs and one analog output.
Product Description
Multifunctional process indicator in field housing for monitoring and displaying analog measurement data.
Dual-conductor sensors can be powered with the integrated measuring transducer supply. Universal inputs permit connection of current, voltage,
RTDs, and TCs. Limit values can be monitored and relays can be switched. The analog output allows you to transmit process signals. A color
change in the event of a fault supports the detection of alarm conditions. 5-digit, 7-segment LC display, with backlight, 1 universal input, 2 relays,
min./max. value memory, linearization table, digital status output (open collector)
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4055626232140
Weight per Piece (excluding packing)
1,439.100 g
Custom tariff number
90291000
Country of origin
Germany
Technical data
Dimensions
Width
199 mm
Height
160 mm
Depth
96 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 50 °C (The readability of the display is no longer guaranteed at
temperatures below -30 °C (-22 °F).)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
< 2000 m (Above sea level)
Degree of protection
IP67
04/17/2018 Page 1 / 6
https://www.phoenixcontact.com/gb/products/2907780
Digital display - FA MCR-FD-TUI-UI-2REL-UP - 2907780
Technical data
Input data
Description of the input
Universal input
Number of inputs
1
Current input signal
0 mA ... 20 mA +10 %
4 mA ... 20 mA +10 %
Max. input current
< 150 mA
Input signal
Current
Input resistance current input
10 Ω
Transmitter supply voltage
> 16 V (22 mA)
Transmitter supply voltage range
22.8 V ... 27.6 V (No-load)
Transmitter supply current
< 30 mA (Short-circuit and overload protection)
Available input sources
Resistance thermometers
Sensor types (RTD) that can be used
Pt, Ni, Cu sensors
Connection technology
2, 3, 4-wire
Description of the input
Universal input
Voltage input signal
0 V ... 10 V
2 V ... 10 V
0 V ... 5 V
0 V ... 1 V
1 V ... 5 V
-1 V ... 1 V
-10 V ... 10 V
-30 V ... 30 V
-100 mV ... 100 mV
max. input voltage
± 35 V (≥ 1 V)
Input signal
Voltage
Input resistance of voltage input
> 1 MΩ
Available input sources
Thermocouples
Sensor types that can be used (TC)
J, K, T, N, B, S, R, U. L, C, D
Output data
Output name
Current output
Number of outputs
1
Configurable/programmable
Yes
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. output current
< 22 mA
Load/output load current output
≤ 500 Ω (22 mA)
Ripple
< 10 mVPP (500 Ω)
D/A resolution
13 bit
Output name
Voltage output
Voltage output signal
0 V ... 10 V
04/17/2018 Page 2 / 6
https://www.phoenixcontact.com/gb/products/2907780
Digital display - FA MCR-FD-TUI-UI-2REL-UP - 2907780
Technical data
Output data
2 V ... 10 V
0 V ... 5 V
1 V ... 5 V
Max. output voltage
< 11 V
Ripple
< 10 mVPP (1000 Ω)
D/A resolution
13 bit
Switching output
Output name
Relay output
Contact type
2 PDT
Minimum switching voltage
12 V
Maximum switching voltage
30 V DC (3 A)
230 V AC (3 A)
Min. switching current
10 mA
Output name
Transistor output, active
Output description
Open collector output
Number of outputs
1
Contact type
Transistor
Maximum switching voltage
28 V
Max. switching current
3A
200 mA
Power supply
Supply voltage range
24 V AC/DC ... 230 V AC/DC (-20 % ... +10 %, 50 Hz ... 60 Hz)
Power consumption
≤ 6.9 W
General
Test voltage
2500 V
Protection class
II
Overvoltage category
II
Degree of pollution
2
Test voltage input/output
500 V
Test voltage input/power supply
2500 V
Test voltage output/power supply
2500 V
Noise emission
IEC 61326, class A
Noise immunity
IEC 61326 / NAMUR NE 21
Housing material
PBT GF30
Mounting position
Max. viewing angle range +/- 45° from the centre line of the display in
every direction
Conformance
CE-compliant
UL, USA/Canada
UL 61010 Recognized
CSA
CSA GP
04/17/2018 Page 3 / 6
https://www.phoenixcontact.com/gb/products/2907780
Digital display - FA MCR-FD-TUI-UI-2REL-UP - 2907780
Technical data
Standards and Regulations
Noise emission
IEC 61326, class A
Noise immunity
IEC 61326 / NAMUR NE 21
Conformance
CE-compliant
UL, USA/Canada
UL 61010 Recognized
CSA
CSA GP
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Block diagram
Pictogram
Sensor / Field
PWR 1.1
IN+
OUT
IN
2-wire
US
US
US
1.4
Out IOut I+ 1.4
4-wire
Out I- 2.4
>1V Out U+ 1.3
4-wire
2.4
Out UOut U+
2.3
4-wire
Out U- 2.4
1.3
2.3
R.13 R.13
R.22
2.3
2.4
R.21
4.1
1.1
4.2
1.2
4.3
4.4
1.4
2x
2.1
2.2
4.3
+
Passive
4.4
R.12 R.12
R.11 R.11
-
POWER U,I
DI
OUT
IN
R.22
R.23
2.4
R.21
2.2
2.3
2.4
2x
DI
R.23
2.1
Power
24V...230V AC/DC
U,I
POWER
L/+
N/PE
Classifications
eCl@ss
eCl@ss 4.0
27210301
eCl@ss 4.1
27210301
eCl@ss 5.0
27210301
eCl@ss 5.1
27210301
eCl@ss 6.0
27210301
eCl@ss 7.0
27210301
eCl@ss 8.0
27210301
eCl@ss 9.0
27210301
ETIM
ETIM 2.0
EC001426
ETIM 3.0
EC001426
ETIM 4.0
EC001426
04/17/2018 Page 4 / 6
https://www.phoenixcontact.com/gb/products/2907780
Digital display - FA MCR-FD-TUI-UI-2REL-UP - 2907780
Classifications
ETIM
ETIM 5.0
EC001426
ETIM 6.0
EC001426
UNSPSC
UNSPSC 13.2
39121522
Approvals
Approvals
Approvals
CSA / UL Recognized / cUL Recognized / EAC / cULus Recognized
Ex Approvals
Approval details
CSA
http://www.csagroup.org/services-industries/product-listing/
2879105
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 198586
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 198586
EAC
RU CDE.A*30.B.01082
cULus Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Accessories
Accessories
Mounting material
04/17/2018 Page 5 / 6
https://www.phoenixcontact.com/gb/products/2907780
Digital display - FA MCR-FD-TUI-UI-2REL-UP - 2907780
Accessories
Mounting kit - FA MCR-FD-PM - 2908739
Tube mounting set for FA MCR-FD-TUI-UI-2REL-UP (2907780) and FA MCR-EX-FD-TUI-UI-2REL-UP (2907781)
multifunctional process displays. Can also be used for simplified wall mounting.
Programming adapter
Programming adapter - MCR-PAC-T-USB - 2309000
Programming adapter with USB and T port interface, 2.4 m for programming FA MCR-..., MCR-...-LP-..., and MCR-...HT-... modules
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
04/17/2018 Page 6 / 6