QUINT4-BUFFER/24DC/40 - Buffer module
2908283
https://www.phoenixcontact.com/us/products/2908283
Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user
documentation. Our general terms of use for downloads are valid.
QUINT buffer module with maintenance-free capacitor-based energy storage for DIN rail mounting, input: 24 V DC, output: 24 V DC/40
A, including mounted UTA 107 universal DIN rail adapter.
Product description
Bridge failures lasting several seconds with the buffer modules from the QUINT range for DIN rails. The QUINT BUFFER combines an electronic
switch-over unit and maintenance-free, capacitor-based energy storage in the same housing.
Your advantages
• Space savings, thanks to the compact design
• Maintenance-free due to electrolytic capacitors
• Thanks to soft start, can also be used with power supplies in the low power range
Commercial data
Item number
2908283
Packing unit
1 pc
Minimum order quantity
1 pc
Sales key
CM21
Product key
CMUIE3
Catalog page
Page 345 (C-4-2019)
GTIN
4055626309200
Weight per piece (including packing)
1,416 g
Weight per piece (excluding packing)
1,328 g
Customs tariff number
85322900
Country of origin
CN
Jan 8, 2024, 9:13 AM
Page 1 (10)
QUINT4-BUFFER/24DC/40 - Buffer module
2908283
https://www.phoenixcontact.com/us/products/2908283
Technical data
Input data
Input voltage range
22.5 V DC ... 30 V DC
Fixed backup threshold
< 22 V DC
Voltage type of supply voltage
DC
Current consumption Imax (UN, IOUT = IStat.Boost, Icharge = max)
46 A (max.)
Current consumption INo-Load(UN, IOUT = 0, Icharge = 0)
0.2 A (No-load)
Current consumption Icharge (UN, IOUT = 0, Icharge = max)
0.8 A (charging process)
Buffer time
0.2 s (40 A)
2 s (4 A)
Output data
Efficiency
> 98 % (with charged energy storage device)
Connection in parallel
no
Connection in series
No
Mains operation
Output voltage
24 V DC (depending on the input voltage)
Output current IN
40 A
Power loss nominal load max.
40 °C Derating: 0.56 %/K / > 60 °C Derating:
2.5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 70 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 4000 m
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 %
Standards and regulations
Electrical safety
Standard designation
Electrical safety
Standards/specifications
IEC 60950-1/VDE 0805 (SELV)
Approvals
UL
Identification
UL Listed UL 508
UL
Identification
UL/C-UL Recognized UL 60950-1
EMC data
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission
EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1
EN 61000-6-2
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Noise emission
EN 55016
EN 61000-6-3
Electrostatic discharge
Standards/regulations
EN 61000-4-2
Electrostatic discharge
Contact discharge
6 kV (Test Level 3)
Discharge in air
8 kV (Test Level 3)
Comments
Criterion A
Electromagnetic HF field
Standards/regulations
EN 61000-4-3
Electromagnetic HF field
Frequency range
80 MHz ... 6 GHz
Jan 8, 2024, 9:13 AM
Page 4 (10)
QUINT4-BUFFER/24DC/40 - Buffer module
2908283
https://www.phoenixcontact.com/us/products/2908283
Test field strength
10 V/m
Comments
Criterion A
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Fast transients (burst)
Input
2 kV (Test Level 3 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
2 kV (Test Level 3 - asymmetrical)
Comments
Criterion A
Surge voltage load (surge)
Input
1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output
1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion A
Conducted interference
Standards/regulations
EN 61000-4-6
Conducted interference
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V
Criteria
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected
by the device itself.
Jan 8, 2024, 9:13 AM
Page 5 (10)
QUINT4-BUFFER/24DC/40 - Buffer module
2908283
https://www.phoenixcontact.com/us/products/2908283
Drawings
Block diagram
+
+
-
1.1
2.1
Inrush
3.1
1.2
3.2
2.2
=
=
Charge
=
Discharge
=
C
3.3
3.4
13
UIn OK
14
Ready
SGnd
Jan 8, 2024, 9:13 AM
Page 6 (10)
QUINT4-BUFFER/24DC/40 - Buffer module
2908283
https://www.phoenixcontact.com/us/products/2908283
Approvals
To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/2908283
cUL Recognized
UL Recognized
Approval ID: FILE E 211944
Approval ID: FILE E 211944
EAC
Approval ID: RU S-DE.BL08.W.00764
UL Listed
cUL Listed
cUL Listed
UL Listed
Approval ID: FILE E 123528
Approval ID: FILE E 123528
Approval ID: FILE E 199827
Approval ID: FILE E 199827
cULus Recognized
cULus Listed
cULus Listed
Jan 8, 2024, 9:13 AM
Page 7 (10)
QUINT4-BUFFER/24DC/40 - Buffer module
2908283
https://www.phoenixcontact.com/us/products/2908283
Classifications
ECLASS
ECLASS-11.0
27040692
ECLASS-12.0
27040692
ECLASS-13.0
27040692
ETIM
ETIM 9.0
EC002850
UNSPSC
UNSPSC 21.0
26111700
Jan 8, 2024, 9:13 AM
Page 8 (10)
QUINT4-BUFFER/24DC/40 - Buffer module
2908283
https://www.phoenixcontact.com/us/products/2908283
Environmental product compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”
Jan 8, 2024, 9:13 AM
Page 9 (10)
QUINT4-BUFFER/24DC/40 - Buffer module
2908283
https://www.phoenixcontact.com/us/products/2908283
Accessories
UWA 130 - Mounting adapter
2901664
https://www.phoenixcontact.com/us/products/2901664
2-piece universal wall adapter for
securely mounting the device in the
event of strong vibrations. The profiles
that are screwed onto the side of the
device are screwed directly onto the
mounting surface. The universal wall
adapter is attached on the left/right.
UWA 182/52 - Mounting adapter
2938235
https://www.phoenixcontact.com/us/products/2938235
Universal wall adapter for securely
mounting the device in the event of
strong vibrations. The device is
screwed directly onto the mounting
surface. The universal wall adapter is
attached on the top/bottom.
Phoenix Contact 2024 © - all rights reserved
https://www.phoenixcontact.com
Phoenix Contact USA
586 Fulling Mill Road
Middletown, PA 17057, United States
(+717) 944-1300
info@phoenixcon.com
Jan 8, 2024, 9:13 AM
Page 10 (10)
很抱歉,暂时无法提供与“2908283”相匹配的价格&库存,您可以联系我们找货