https://www.phoenixcontact.com/gb/products/2908672
Hybrid motor starter - ELR H3-IES-PT/500AC-9-IOL - 2908672
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Networkable hybrid motor starter for starting 3~ AC motors up to 500 V AC and 9 A output current,
with adjustable overload shutdown, emergency stop function up to SIL 3/PL e, and Push-in connection.
Connection to IO-Link.
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4055626321271
Weight per Piece (excluding packing)
282.700 g
Custom tariff number
85371098
Country of origin
Germany
Note
Made to Order (non-returnable)
Technical data
Note
Type of note
Notes on operation
Note
If this device is to be used in combination with the CrossPowerSystem
power distribution board, the device mount for the 16 A fuse (order
designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is
required in order to attach the hybrid motor starter to the power
distribution board.
Device supply
Rated control circuit supply voltage US
24 V DC
Control supply voltage range
19.2 V DC ... 30 V DC
Rated control supply current IS
65 mA
Type of protection
Surge protection
Reverse polarity protection
Input data
Input name
Enable input
04/16/2018 Page 1 / 8
https://www.phoenixcontact.com/gb/products/2908672
Hybrid motor starter - ELR H3-IES-PT/500AC-9-IOL - 2908672
Technical data
Input data
Rated actuating voltage UC
24 V DC
Triggering voltage range
19.2 V DC ... 30 V DC
Rated actuating current IC
7 mA
Switching threshold
9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level
< 5 V DC (For EMERGENCY STOP)
Typical turn-off time
< 30 ms
Output data load output
Output name
AC output
Rated operating voltage Ue
500 V AC
Operating voltage range
42 V AC ... 550 V AC
Rated operating current Ie
9 A (AC-51)
7 A (AC-53a)
Mains frequency
50/60 Hz
Load current range
1.5 A ... 9 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2
Class 10A
Cooling time
20 min. (for auto reset)
Leakage current
0 mA
Type of protection
Surge protection
Overspeed tripping
Operate threshold
> 60 A
Response time
< 0.5 s
General
Switching frequency
≤ 2 Hz (Load-dependent)
Mounting position
vertical (horizontal DIN rail, motor output below)
Mounting type
DIN rail mounting
Assembly instructions
alignable, for spacing see derating
Operating mode
100% operating factor
Maximum power dissipation
7W
Minimum power dissipation
0.88 W
Operating voltage display
Green LED
Status display
Yellow LED
Indication
Red LED
Connection data, input side
Connection name
Control circuits
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
04/16/2018 Page 2 / 8
https://www.phoenixcontact.com/gb/products/2908672
Hybrid motor starter - ELR H3-IES-PT/500AC-9-IOL - 2908672
Technical data
Connection data, input side
Conductor cross section AWG
24 ... 14
Connection data, output side
Connection name
Load circuit
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Ambient conditions
Ambient temperature (operation)
-5 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Degree of protection
IP20
Dimensions
Width
22.5 mm
Height
126.8 mm
Depth
113.7 mm
UL data
SCCR
100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA
7.6 A (480 V AC)
Group installation
20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and
stranded)
30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid
and stranded)
Category code
NLDX / NRNT
Horsepower ratings
2 hp (120 V AC / 208 V AC)
5 hp (277 V AC / 480 V AC)
Insulation characteristics
Rated insulation voltage
550 V
Rated surge voltage
6 kV
Overvoltage category
III
Degree of pollution
2
Designation
Insulation characteristics between the control input and control supply
voltage, and auxiliary circuit to the main circuit
Insulation
Safe isolation (IEC 60947-1)
Designation
Isolation characteristics between the control input and control supply
voltage to auxiliary circuit
Insulation
Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
04/16/2018 Page 3 / 8
https://www.phoenixcontact.com/gb/products/2908672
Hybrid motor starter - ELR H3-IES-PT/500AC-9-IOL - 2908672
Technical data
Standards and Regulations
Designation
Standards/regulations
Standards/regulations
IEC 60947-1
EN 60947-4-2
IEC 61508
ISO 13849
Approvals/conformities
Safety Integrity Level according to IEC 61508
≤ 3 (Safe shutdown)
Category acc. to EN ISO 13849
≤ 3 (Safe shutdown)
Performance level according to ISO 13849
e (Safe shutdown)
UL certificate
NLDX.E228652
NRNT.E172140
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Block diagram
ENEN+
Reset
Enable
+
Logic
µP
A2/LNC
NC
IO-Link
A1/L+
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
C/Q
Classifications
eCl@ss
eCl@ss 5.0
27024002
eCl@ss 5.1
27024002
eCl@ss 6.0
27024002
eCl@ss 7.0
27024002
eCl@ss 8.0
27024002
eCl@ss 9.0
27024002
ETIM
ETIM 2.0
EC001037
ETIM 3.0
EC001037
ETIM 4.0
EC001037
04/16/2018 Page 4 / 8
https://www.phoenixcontact.com/gb/products/2908672
Hybrid motor starter - ELR H3-IES-PT/500AC-9-IOL - 2908672
Classifications
ETIM
ETIM 5.0
EC001037
ETIM 6.0
EC001037
UNSPSC
UNSPSC 6.01
30211915
UNSPSC 7.0901
39121514
UNSPSC 11
39121514
UNSPSC 12.01
39121514
UNSPSC 13.2
25173902
Approvals
Approvals
Approvals
UL Listed / UL Listed / cUL Listed / cUL Listed / EAC / cULus Listed
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 172140
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 228652
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 172140
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 228652
EAC
RU CDE.A*30.B.01082
04/16/2018 Page 5 / 8
https://www.phoenixcontact.com/gb/products/2908672
Hybrid motor starter - ELR H3-IES-PT/500AC-9-IOL - 2908672
Approvals
cULus Listed
Accessories
Accessories
Adapter
Adapter - EM-CPS-DA-22,5F/16A - 1002668
®
Device adapter with fuse holder for 16 A fuse (10x38/Class CC), CrossLink interface and fixed DIN rail
Assembly adapter
Power distribution board - EM-CPS-225 - 1002634
®
Modular power distribution board with CrossLink interface, 125 A, 3-pos., touch-proof and protection against polarity
reversal, width: 225 mm
Power distribution board - EM-CPS-405 - 1002635
®
Modular power distribution board with CrossLink interface, 125 A, 3-pos., touch-proof and protection against polarity
reversal, width: 405 mm
Connection module - EM-CPS-TB3/63A - 1002633
Connection module with integrated spring-loaded terminals for cables up to 16 mm², 3-pos.,
Cover
04/16/2018 Page 6 / 8
https://www.phoenixcontact.com/gb/products/2908672
Hybrid motor starter - ELR H3-IES-PT/500AC-9-IOL - 2908672
Accessories
Covering hood - BRIDGE COVER - 2906240
The BRIDGE COVER covering hood is used to cover unused plugs on the CONTACTRON bridge that may
subsequently be used to extend the system. The hood can be used with the screw and Push-in version of the bridge.
Loop bridge
Jumper - BRIDGE-PT 2 - 2904490
3-phase loop bridge for 2 CONTACTRON modules, with push-in connection and 22.5 mm housing width, connecting
cable: 3 m, with ferrules included.
Jumper - BRIDGE-PT 3 - 2904491
3-phase loop bridge for 3 CONTACTRON modules, with push-in connection and 22.5 mm housing width, connecting
cable: 3 m, with ferrules included.
Jumper - BRIDGE-PT 4 - 2904492
3-phase loop bridge for 4 CONTACTRON modules, with push-in connection and 22.5 mm housing width, connecting
cable: 3 m, with ferrules included.
Jumper - BRIDGE-PT 5 - 2904493
3-phase loop bridge for 5 CONTACTRON modules, with push-in connection and 22.5 mm housing width, connecting
cable: 3 m, with ferrules included.
04/16/2018 Page 7 / 8
https://www.phoenixcontact.com/gb/products/2908672
Hybrid motor starter - ELR H3-IES-PT/500AC-9-IOL - 2908672
Accessories
Jumper - BRIDGE-PT 6 - 2904494
3-phase loop bridge for 6 CONTACTRON modules, with push-in connection and 22.5 mm housing width, connecting
cable: 3 m, with ferrules included.
Jumper - BRIDGE-PT 7 - 2904495
3-phase loop bridge for 7 CONTACTRON modules, with push-in connection and 22.5 mm housing width, connecting
cable: 3 m, with ferrules included.
Jumper - BRIDGE-PT 8 - 2904496
3-phase loop bridge for 8 CONTACTRON modules, with push-in connection and 22.5 mm housing width, connecting
cable: 3 m, with ferrules included.
Jumper - BRIDGE-PT 9 - 2904497
3-phase loop bridge for 9 CONTACTRON modules, with push-in connection and 22.5 mm housing width, connecting
cable: 3 m, with ferrules included.
Jumper - BRIDGE-PT 10 - 2904498
3-phase loop bridge for 10 CONTACTRON modules, with push-in connection and 22.5 mm housing width, connecting
cable: 3 m, with ferrules included.
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
04/16/2018 Page 8 / 8