Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Please be informed that the data shown in this PDF document is generated from our Online Catalog. Please find the complete data in the user
documentation. Our General Terms of Use for Downloads are valid.
Primary-switched power supply unit, QUINT POWER, Push-in connection, DIN rail mounting,
input: 1-phase, output: 24 V DC / 2.5 A
Product Description
In the power range of up to 100 W, QUINT POWER provides superior system availability in the smallest size. Preventative function monitoring and
exceptional power reserves are available for applications in the low-power range.
Your advantages
• Starting of heavy loads with dynamic boost
• Preventive function monitoring indicates critical operating states before errors occur
• High efficiency and long service life, with low power dissipation and low heating
• Space savings in the control cabinet, thanks to a narrow, slim-line design
• Free selection between Push-in and screw connection
Commercial Data
Item number
2909576
Packing unit
1 pc
Minimum order quantity
1 pc
Sales Key
CMP
Product Key
CMPI13
Catalog Page
Page 249 (C-4-2019)
GTIN
4055626356495
Weight per Piece (including packing)
311.1 g
Weight per Piece (excluding packing)
311.1 g
Customs tariff number
85044030
Country of origin
VN
Oct 20, 2022, 9:37 AM
Page 1 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Technical Data
Input data
AC operation
Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
Electric strength, max.
300 V AC 30 s
Typical national grid voltage
120 V AC
230 V AC
Voltage type of supply voltage
AC/DC
Inrush current
typ. 10 A (at 25 °C)
Inrush current integral (I2t)
< 0.1 A2s
Inrush current limitation
4.3 A (after 1 ms)
< 10 A
Frequency range (fN)
50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time
typ. 54 ms (120 V AC)
typ. 54 ms (230 V AC)
Current consumption
0.85 A (100 V AC)
0.7 A (120 V AC)
0.39 A (230 V AC)
0.37 A (240 V AC)
Nominal power consumption
71 VA
Protective circuit
Transient surge protection; Varistor
Typical response time
500 ms
Input fuse
3.15 A (slow-blow, internal)
Discharge current to PE
< 0.25 mA (264 V AC, 60 Hz)
0.22 mA (264 V AC, 60 Hz)
DC operation
Input voltage range
110 V DC ... 250 V DC -20 % ... +40 %
Voltage type of supply voltage
AC/DC
Current consumption
0.75 A (110 V DC)
0.33 A (250 V DC)
Output data
Efficiency
typ. 91.9 % (120 V AC)
typ. 92.6 % (230 V AC)
Output characteristic
U/I Advanced
Nominal output voltage
24 V DC
Setting range of the output voltage (USet)
24 V DC ... 28 V DC (constant capacity)
Nominal output current (IN)
2.5 A
Static Boost (IStat.Boost)
3.125 A (≤ 40 °C)
Dynamic Boost (IDyn.Boost)
5 A (≤60 °C (5 s), Input 60 °C (2.5%/K)
Oct 20, 2022, 9:37 AM
Page 2 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Feedback voltage resistance
≤ 35 V DC
Protection against overvoltage at the output (OVP)
≤ 32 V DC
Control deviation
< 0.5 % (Static load change 10 % ... 90 %)
< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.1 % (change in input voltage ±10 %)
Residual ripple
< 40 mVPP (with nominal values)
Short-circuit-proof
yes
No-load proof
yes
Output power
60 W
75 W
120 W
Maximum no-load power dissipation
< 1 W (230 V AC)
< 1 W (120 V AC)
Power loss nominal load max.
< 5 W (230 V AC)
< 5 W (120 V AC)
Crest factor
typ. 1,69 (120 V AC)
typ. 1,82 (230 V AC)
Rise time
50 ms (UOut = 10 % ... 90 %)
Connection in parallel
yes, for redundancy and increased capacity
Connection in series
yes
Signal (configurable)
Digital
0 V DC 24 V DC 30 mA
Default
24 V DC 30 mA 24 V DC for UOut > 0.9 x USet
Connection data
Input
Connection method
Push-in connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.
0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
10 mm
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Output
Connection method
Push-in connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Oct 20, 2022, 9:37 AM
Page 3 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.
0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
10 mm
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Signal
Connection method
Push-in connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.
0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
10 mm
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
LED signaling
Types of signaling
LED
Floating signal contact
Active signal output Out1 (digital, configurable)
Active signal output Out2 (analog, configurable)
Remote contact
Signal ground SGnd
Signal output
POut
> PThr (LED lights up yellow, output power > PThr, depending on
the rotary selector switch setting)
UOut
> 0.9 x USet (LED lights up green)
Electrical properties
Number of phases
1.00
Insulation voltage input/output
4 kV AC (type test)
3 kV AC (routine test)
Switching frequency
4 kHz ... 70 kHz (Auxiliary converter stage)
30 kHz ... 150 kHz (PFC stage)
70 kHz ... 150 kHz (Main converter stage)
Oct 20, 2022, 9:37 AM
Page 4 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Product properties
Product type
Power supply
MTBF (IEC 61709, SN 29500)
> 1347000 h (25 °C)
> 734000 h (40 °C)
> 295000 h (60 °C)
Environmental protection directive
RoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection class
II
Degree of pollution
2
Life expectancy (electrolytic capacitors)
Current
2.5 A
Temperature
40 °C
Time
148000 h
Additional text
120 V AC
Life expectancy (electrolytic capacitors)
Current
2.5 A
Temperature
40 °C
Time
153000 h
Additional text
230 V AC
Life expectancy (electrolytic capacitors)
Current
2.5 A
Temperature
25 °C
Time
419000 h
Additional text
120 V AC
Life expectancy (electrolytic capacitors)
Current
2.5 A
Temperature
25 °C
Time
432000 h
Additional text
230 V AC
Dimensions
Dimensional drawing
Oct 20, 2022, 9:37 AM
Page 5 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Width
32 mm
Height
106 mm
Depth
90 mm
Installation dimensions
Installation distance right/left
0 mm / 0 mm
Installation distance top/bottom
30 mm / 30 mm
Mounting
Mounting type
DIN rail mounting
Assembly instructions
DIN rail mounting
With protective coating
No
Material specifications
Flammability rating according to UL 94 (housing / terminal
blocks)
V0
Housing material
Plastic
Type of housing
Polycarbonate
Hood version
Polycarbonate
Environmental and real-life conditions
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Ambient temperature (start-up type tested)
-40 °C
Maximum altitude
≤ 5000 m (> 2000 m, observe derating)
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-227)
Vibration (operation)
< 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz: 2.3 g 90 Min. (in
accordance with IEC 60068-2-6)
Standards and regulations
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Electrical safety
IEC 61010-2-201 (SELV)
Standard – Safety extra-low voltage
IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation
IEC 61558-2-16
IEC 61010-2-201
Standard - safety for equipment for measurement, control, and
laboratory use
IEC 61010-1
Standard - Safety of transformers
EN 61558-2-16
Standard - power supply devices for low voltage with DC output
EN 61204-3
Oct 20, 2022, 9:37 AM
Page 6 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Overvoltage category
EN 61010-1
II (≤ 5000 m)
EN 62477-1
III (≤ 2000 m)
Approval data
SIQ
CB-Scheme (IEC 61010-1, IEC 61010-2-201)
UL approvals
UL Listed UL 61010-1
UL Listed UL 61010-2-201
UL 1310 Class 2 Power Units
ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
EMC data
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission
EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity
EN 61000-6-1
EN 61000-6-2
EMC requirements, power plant
IEC 61850-3
EN 61000-6-5
Conducted noise emission
EN 55016
EN 61000-6-3 (Class B)
Interference emission
Interference emission in accordance with EN 61000-6-3
(residential and commercial) and EN 61000-6-4 (industrial)
Noise emission
Additional basic standard EN 61000-6-5 (immunity in power
station), IEC/EN 61850-3 (energy supply)
Noise emission
EN 55016
EN 61000-6-3 (Class B)
Noise immunity
Immunity in accordance with EN 61000-6-1 (residential),
EN 61000-6-2 (industrial), and EN 61000-6-5 (power station
equipment zone), IEC/EN 61850-3 (power supply)
Harmonic currents
Frequency range
0 kHz ... 2 kHz
Flicker
Frequency range
0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations
EN 61000-4-2
Electrostatic discharge
Contact discharge
8 kV (Test Level 4)
Discharge in air
8 kV (Test Level 3)
Comments
Criterion A
Electromagnetic HF field
Oct 20, 2022, 9:37 AM
Page 7 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Standards/regulations
EN 61000-4-3
Electromagnetic HF field
Frequency range
80 MHz ... 1 GHz
Test field strength
20 V/m
Frequency range
1 GHz ... 6 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Fast transients (burst)
Input
4 kV (Test Level 4 - asymmetrical)
Output
4 kV (Test Level 4 - asymmetrical)
Signal
4 kV (Test Level 4 - asymmetrical)
Comments
Criterion B
Surge voltage load (surge)
Standards/regulations
EN 61000-4-5
Input
2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output
1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal
2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Comments
Criterion A
Conducted interference
Standards/regulations
EN 61000-4-6
Conducted interference
I/O/S
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations
EN 61000-4-8
Frequency
16.67 Hz
50 Hz
60 Hz
Test field strength
100 A/m
Additional text
60 s
Comments
Criterion A
Frequency
50 Hz
60 Hz
Oct 20, 2022, 9:37 AM
Page 8 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Test field strength
1 kA/m
Additional text
3s
Frequency
0 Hz
Test field strength
300 A/m
Additional text
DC, 60 s
Voltage dips
Standards/regulations
EN 61000-4-11
Voltage
100 V AC
Frequency
60 Hz
Voltage dip
70 %
Number of periods
0.5 / 1 / 25 periods
Additional text
Test Level 2
Comments
Criterion B
Voltage dip
40 %
Number of periods
5 / 10 / 50 periods
Additional text
Test Level 2
Comments
Criterion B
Voltage dip
0%
Number of periods
0.5 / 1 / 5 / 50 periods
Additional text
Test Level 2
Comments
Criterion B
Pulse-shape magnetic field
Standards/regulations
EN 61000-4-9
Test field strength
1000 A/m
Comments
Criterion A
Attenuated sinusoidal oscillations (ring wave)
Standards/regulations
EN 61000-4-12
Input
2 kV (symmetrical)
4 kV (asymmetrical)
Comments
Criterion B
Asymmetrical conducted disturbance variables
Standards/regulations
EN 61000-4-16
Test level 1
16.67 Hz 50 Hz 60 Hz (Test Level 3)
Voltage
30 V (Permanent)
Test level 2
16.67 Hz 50 Hz 60 Hz (Test Level 4)
Voltage
300 V (1 s)
Comments
Criterion A
Attenuated oscillating wave
Standards/regulations
EN 61000-4-18
Input/Output/Signal
1 kV (symmetrical)
2.5 kV (asymmetrical)
Oct 20, 2022, 9:37 AM
Page 9 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Comments
Criterion B
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected
by the device itself.
Criterion C
Temporary adverse effects on the operating behavior, which the
device corrects automatically or which can be restored by
actuating the operating elements.
Oct 20, 2022, 9:37 AM
Page 10 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Power Factor
Drawings
1,00
0,90
0,80
0,70
0,60
0,50
0,40
0,30
0,20
0,10
0,00
Diagram
= UIn: 120 V AC/UOut: 24 V DC
= UIn: 230 V AC/UOut: 24 V DC
0
1
2
3
4
5
IOut [A]
IIn [A]
Diagram
1,0
0,8
0,6
0,4
0,2
0,0
0
= UIn: 120V AC/UOut: 24 V DC
= UIn: 230V AC/UOut: 24 V DC
1
2
3
4
5
IOut [A]
Oct 20, 2022, 9:37 AM
Page 11 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Dimensional drawing
QUINT POWER Ord.No.2909576
3.1 2.1 2.2 2.3
SIG
Output DC 24V 2.5A
+ − −
UOut
24-28V
Signal (SIG)
POut>PThr
Boost > 100%
> 75%
> 50%
99
159
79,5
30
32
DC OK
Input AC 100-240V
N/− L/+
1.1 1.2
Oct 20, 2022, 9:37 AM
Page 12 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
Eta [%]
https://www.phoenixcontact.com/in/products/2909576
95
93
91
89
87
85
83
81
79
77
75
0
Diagram
= UIn: 120V AC/UOut: 24 V DC
= UIn: 230V AC/UOut: 24 V DC
0,5
1
1,5
2
2,5
3
3,5
4
4,5
5
IOut [A]
Oct 20, 2022, 9:37 AM
Page 13 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Schematic diagram
Housing
(+)
L
Input
Signaling
A
N
(-)
A
Output
+
Block diagram
N/L/+
1.1
1.2
2.1
active
PFC
2.2
2.3
3.1
OVP
+
-
SIG
SIG
C
DC OK POut
Oct 20, 2022, 9:37 AM
Page 14 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Approvals
IECEE CB Scheme
Approval ID: SI-8860
EAC
Approval ID: RU S-DE.BL08.W.00764
UL Listed
cUL Listed
EAC
Approval ID: FILE E 123528
Approval ID: FILE E 123528
Approval ID: RU S-DE.BL08.W.00764
IECEE CB Scheme
Approval ID: SI-8860
cUL Listed
UL Listed
Approval ID: FILE E 123528
Approval ID: FILE E 123528
EAC
EAC
Approval ID: RU S-DE.BL08.W.00764
Approval ID: RU S-DE.BL08.W.00764
DNV
Approval ID: TAA00000BV
DNV
Approval ID: TAA00000BV
Oct 20, 2022, 9:37 AM
Page 15 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
cUL Listed
UL Listed
UL Listed
cUL Listed
Approval ID: FILE E 199827
Approval ID: FILE E 199827
Approval ID: FILE E 199827
Approval ID: FILE E 199827
Oct 20, 2022, 9:37 AM
Page 16 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Classifications
ECLASS
ECLASS-9.0
27040701
ECLASS-10.0.1
27040701
ECLASS-11.0
27040701
ETIM
ETIM 8.0
EC002540
UNSPSC
UNSPSC 21.0
39121000
Oct 20, 2022, 9:37 AM
Page 17 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”
Oct 20, 2022, 9:37 AM
Page 18 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Accessories
Screwdriver
Screwdriver - SF-SL 0,4X2,0-60 - 1212546
https://www.phoenixcontact.com/in/products/1212546
Screwdriver, flat bladed, size: 0.4 x 2.0 x 60 mm, 2-component grip, with non-slip
grip
Electronic circuit breaker
Electronic circuit breaker - CBMC E4 24DC/1-10A NO - 2906032
https://www.phoenixcontact.com/in/products/2906032
Multi-channel electronic circuit breaker for protecting four loads at 24 V DC in the
event of overload and short circuit. With electronic locking of the set nominal
currents. For installation on DIN rails.
Oct 20, 2022, 9:37 AM
Page 19 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Electronic circuit breaker
Electronic circuit breaker - CBMC E4 24DC/1-4A NO - 2906031
https://www.phoenixcontact.com/in/products/2906031
Multi-channel electronic circuit breaker for protecting four loads at 24 V DC in the
event of overload and short circuit. With electronic locking of the set nominal
currents. For installation on DIN rails.
Electronic circuit breaker
Electronic circuit breaker - CBMC E4 24DC/1-4A NO-C - 2908713
https://www.phoenixcontact.com/in/products/2908713
Multi-channel electronic circuit breaker that can be preconfigured, for protecting
four loads at 24 V DC in the event of overload and short circuit. With electronic
locking of the set nominal currents. For installation on DIN rails.
Oct 20, 2022, 9:37 AM
Page 20 (21)
Power supply unit - QUINT4-PS/1AC/24DC/2.5/PT
2909576
https://www.phoenixcontact.com/in/products/2909576
Type 3 surge protection device
Type 3 surge protection device - PLT-SEC-T3-230-FM-PT - 2907928
https://www.phoenixcontact.com/in/products/2907928
Type 2/3 surge protection, consisting of protective plug and base element with
Push-in connection. For single-phase power supply network with integrated
status indicator and remote signaling. Nominal voltage: 230 V AC/DC
Type 3 surge protection device
Type 3 surge protection device - PLT-SEC-T3-24-FM-PT - 2907925
https://www.phoenixcontact.com/in/products/2907925
Type 3 surge protection, consisting of protective plug and base element, with
integrated status indicator and remote signaling for single-phase power supply
networks. Nominal voltage: 24 V AC/DC
Phoenix Contact 2022 © - all rights reserved
https://www.phoenixcontact.com
PHOENIX CONTACT (I) Pvt. Ltd.
A-58/2, Okhla Industrial Area, Phase - II, New Delhi-110 020
+91.1275.71420
info@phoenixcontact.co.in
Oct 20, 2022, 9:37 AM
Page 21 (21)