https://www.phoenixcontact.com/us/products/2940113
Reversing load relay - CM 90-ELR-W3/5-R - 2940113
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Electronic reversing load relay, for direct driving of 3-phase equipment in the 3-phase network, with light indicator
and protection circuit, output: 400 V AC/ 3 x 5 A
Key commercial data
Packing unit
1 PCE
Weight per Piece (excluding packing)
662.9 GRM
Custom tariff number
85364900
Country of origin
Germany
Technical data
Dimensions
Width
90 mm
Height
75 mm
Depth
116 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 55 °C
Ambient temperature (storage/transport)
-20 °C ... 70 °C
Degree of protection
IP20
Input data
Input name
Device supply
Nominal supply voltage
24 V DC
Switch-over frequency
2.5 Hz (RL / LL)
Protective circuit
Protection against polarity reversal Polarity protection diode
Surge protection
Input name
Control input right/left
Output data
Output name
AC output
Nominal output voltage
400 V AC +10 % -20 %
12/6/13 Page 1 / 5
https://www.phoenixcontact.com/us/products/2940113
Reversing load relay - CM 90-ELR-W3/5-R - 2940113
Technical data
Output data
Nominal output voltage range
320 V AC ... 440 V AC
Periodic peak reverse voltage
1000 V
Mains frequency
50 Hz
60 Hz
Continuous load current
3x 5 A (see derating curve)
Load current
min. 150 mA
Leakage current
7 mA
Residual voltage
1.7 V
Surge current
230 A (t = 10 ms)
Protective circuit/component
RCV circuit
Surge voltage protection
750 V
Output name
Reply output: Alarm Contact
Nominal output voltage
24 V DC +25% -20%
Continuous load current
100 mA
Protective circuit/component
Decoupling diode
Type of protection
Free running
Protective circuit/component
Damping diode
Status display
LED
Output name
Reply output: "right / left"
Number of outputs
2
Nominal output voltage
24 V DC +25% -20%
Continuous load current
100 mA
Protective circuit/component
Decoupling diode
Type of protection
Free running
Protective circuit/component
Damping diode
Status display
LED
Connection data
Connection method
Screw connection
Stripping length
8 mm
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Screw thread
M3
12/6/13 Page 2 / 5
https://www.phoenixcontact.com/us/products/2940113
Reversing load relay - CM 90-ELR-W3/5-R - 2940113
Technical data
General
Test voltage input/output
3.5 kV AC
Mounting position
Vertical (horizontal DIN rail)
Assembly instructions
Can be aligned with spacing = 20 mm
Operating mode
100% operating factor
Standards/regulations
IEC 60664
IEC 60664 A
DIN VDE 0110
DIN VDE 0106-101
DIN VDE 0160 (in relevant parts)
IEC 801-5
Classifications
eCl@ss
eCl@ss 4.0
27371102
eCl@ss 4.1
27371102
eCl@ss 5.0
27371601
eCl@ss 5.1
27371601
eCl@ss 6.0
27371601
eCl@ss 7.0
27371601
ETIM
ETIM 2.0
EC000066
ETIM 3.0
EC000066
ETIM 4.0
EC000066
ETIM 5.0
EC002055
UNSPSC
UNSPSC 6.01
30211915
UNSPSC 7.0901
39121514
UNSPSC 11
39121514
UNSPSC 12.01
39121514
UNSPSC 13.2
39121514
Drawings
12/6/13 Page 3 / 5
https://www.phoenixcontact.com/us/products/2940113
Reversing load relay - CM 90-ELR-W3/5-R - 2940113
Diagram
Circuit diagram
12/6/13 Page 4 / 5
https://www.phoenixcontact.com/us/products/2940113
© Phoenix Contact 2013 - all rights reserved
http://www.phoenixcontact.com
12/6/13 Page 5 / 5