ELR 3/9-400(/SI)
ELR 3/9-500
Electronic Load Relay for
3-Phase Networks
Data Sheet
m
01/2005
co
Features
Standard Version of ELR 3/9-400 and ELR 3/9-500
Electronic load relays offer the advantage of a virtually
unlimited service life along with the same functions as
mechanical contactors. The optocoupler technology
used enables contactless, bounce-free, and wearresistant switching of loads in 3-phase networks. In
comparison with conventional electromechanical
components, 50 cycles per hour represents a
considerable increase in cost-effectiveness.
The ELR 3/9... is the fully electronic alternative to
mechanical contactors. It features a compact design
and low control power. A further advantage is the highquality, safe screw connection technology.
nt
s.
Electronic Load Relay
ne
Version With Fuse ELR 3/9-400/SI
om
po
Contactless switching with Triacs at zero voltage
crossing does not generate any additional highfrequency disturbing pulses. This means that the ELR
can be used close to modules and electronic devices
with low electromagnetic compatibility (EMC).
on
l
in
ec
Other key features include:
– Reliable Phoenix Contact connection technology
for conductor cross sections up to
6 mm2 (10 AWG)
– Easy to assemble housing technology for use on
EN DIN rails with a width of just 62 mm (2.441 in.)
– Easy to read status indication using clearly visible
LEDs
All electronic load relays have a very low input power
and can thus be controlled directly with any PLC or
automation device. An additional RCV protective
circuit for the outputs enables permanently safe
operation even with inductive loads.
102147_00_en
In addition to the advantages of electronic load relays
already mentioned, this component also provides
effective short-circuit protection. If the permissible
current is exceeded, very fast fuses in the standard
size of 6.3 mm x 32 mm (0.248 x 1.260 in.) disconnect
the connected load. This provides optimum protection
of the power semiconductor in the electronic load
relay.
Easily-accessible fuse holders enable fuses to be
replaced quickly.
In accordance with DIN VDE 0110 and
DIN VDE 0636, a conductor cross section
of 1.5 mm2 (16 AWG), which must be
fitted with one fuse each (10 A slow-blow
as mains protection), is required to
connect the electronic load relay to the
3-phase network.
1
ELR 3/9-400(/SI)/ELR 3/9-500
Technical Data
Input Data (Input)
Control voltage
Nominal current at UN
Input wiring
ELR 3/9-400(/SI)
ELR 3/9-500
24 V DC ±20%
8 mA, approximately (typical)
LED, diode for protection against polarity
reversal, surge protection
Output Data (Output)
Operating voltage (conductor voltage)
50 Hz/60 Hz
Operating voltage range
Reverse voltage
Maximum continuous load current
Load current depending on the ambient operating
temperature
ELR 3/9-400(/SI)
400 V AC
co
m
ELR 3/9-500
500 V AC
nt
s.
110 V AC - 440 V AC
110 V AC - 550 V AC
800 V
1200 V
3x9A
Load current [A]
Ambient operating temperature [°C]
Figure 1
Load current depending on the ambient
operating temperature
on
l
in
ec
om
po
ne
Operating time: 100% operating factor
2
102147_00_en
ELR 3/9-400(/SI)/ELR 3/9-500
Output Data (Output) (Continued)
Power dissipation depending on the load current
ELR 3/9-400(/SI)
ELR 3/9-500
m
co
Power dissipation [W]
Operating time: 100% operating factor
nt
s.
1.5
4.5
7.5
Current per phase [A]
Figure 2
Power dissipation depending on the
load current
16 A FF
–
6.3 x 32 mm
(0.248 x 1.260 in.) (.../SI)
Transmission frequency:
on
l
in
ec
om
With ohmic load
With cos ϕ 0.5
Surge current
Minimum load current
Residual voltage at IN
Residual current in the OFF state
Output wiring
po
ne
Fuse for short circuit
General Data
Housing dimensions (length x width x height)
Insulating housing version
Test voltage I/O
Ambient operating temperature range
Standards/specifications
102147_00_en
10 Hz
10 Hz (depending on the connected motor)
230 A (t = 10 ms)
150 mA
1.7 V, typical
6 mA, typical
RCV circuit
RCV circuit
Short-circuit protection
(.../SI)
84 mm x 62 mm x 110 mm (3.307 x 2.441 x 4.331 in.)
84 mm x 62 mm x 117 mm (3.307 x 2.441 x 4.606 in.) (.../SI)
Polycarbonate (PC), color: green
2.5 kVrms
-20°C to +60°C (-4°F to +140°F)
EN 61000-4-4/DIN EN 61000-4-4/VDE 0847-4-4;
EN 61000-4-5/DIN EN 61000-4-5/VDE 0847-4-5;
IEC 60664/IEC 60664 A/DIN VDE 0110, basic insulation
3
ELR 3/9-400(/SI)/ELR 3/9-500
General Data (Continued)
Degree of protection according to
IEC 60529/EN 60529/DIN VDE 0470-1
Mounting position
Mounting
IP20
Vertical (DIN rail horizontal)
Can be mounted with spacing ≥ 20 mm (0.787 in.)
Figure 3
s.
co
m
Connection Data
Connection data
AWG
Stripping
Length L [mm]
25 - 10 8 mm (0.31 in.)
ne
Stranded
[mm2]
0.2 - 4
po
Solid
[mm2]
0.2 - 6
nt
The following cable cross sections can be connected:
on
l
in
ec
om
Block Diagram
Figure 4
4
Block diagram
102147_00_en
ELR 3/9-400(/SI)/ELR 3/9-500
Ordering Data
Order Designation
Order No.
Electronic load relay
for directly controlling devices in a
3-phase network,
with LED and protective circuit.
ELR 3/9-400
29 41 70 1
ELR 3/9-500
29 41 71 4
ELR 3/9-400/SI
Replacement fuse for
ELR 3/9-400/SI (pack of 10)
SI 16A FF
29 41 72 7
nt
For marking systems and assembly material, see CLIPLINE catalog.
29 40 99 3
s.
co
Electronic load relay
for directly controlling devices in a
3-phase network,
with LED, protective circuit, and fuse.
m
Description
on
l
in
ec
© PHOENIX CONTACT 01/2005 Technical modifications reserved
om
po
ne
Make sure you always use the latest documentation.
It can be downloaded from www.download.phoenixcontact.com.
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
+49 - 52 35 - 30 0
+49 - 52 35 - 34 12 00
www.phoenixcontact.com
Worldwide Locations:
www.phoenixcontact.com/salesnetwork
5
102147_00_en
很抱歉,暂时无法提供与“2941714”相匹配的价格&库存,您可以联系我们找货
免费人工找货