Extract from the online
catalog
EMG 45-ELR3/1,5
Order No.: 2942739
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2942739
Electronic load relay, for direct driving of equipment in the 3-phase
network, with light indicator and protection circuit, output: 320 V AC ....
440 V AC/3x 1.5 A
Commercial data
GTIN (EAN)
4
017918
080822
sales group
G410
Pack
5 pcs.
Customs tariff
85364900
Catalog page information
Page 173 (IF-2009)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Technical data
Input data
Input name
Control input right/left
Nominal input voltage UN
24 V DC
Input voltage range in reference to UN
0.8 ... 1.2
Typical input current at UN
20 mA
Switching threshold "0" signal in reference to UN
< 0.3
Switching threshold "1" signal in reference to UN
> 0.8
Reaction time in normal load operation
20 ms
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 1 / 5
Feb 3, 2011
EMG 45-ELR3/1,5 Order No.: 2942739
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2942739
Transmission frequency
1 Hz (With ohmic load)
1 Hz (At cos φ = 0.5)
Input name
Device supply
Protective circuit
Protection against polarity reversal Series polarity protection
diode
Surge protection
Status display
Yellow LED
Output data, load relay
Output name
AC output
Nominal output voltage
400 V AC
Nominal output voltage range
320 V AC ... 440 V AC
Periodic peak reverse voltage
600 V (load relay is not suitable for the construction of reversing
circuits.)
Mains frequency
50 Hz
60 Hz
Continuous load current
max. 1.5 A (see derating curve)
Leakage current
Typ. 7 mA
Residual voltage
Typ. 1 V
Surge current
100 A (tp = 10 ms, at 25 °C)
Type of protection
RC element
Protective circuit/component
RC element
Type of protection
Surge protection
Connection data
Type of connection
Screw connection
Stripping length
8 mm
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Screw thread
M3
General data
Width
45 mm
Height
75 mm
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 2 / 5
Feb 3, 2011
EMG 45-ELR3/1,5 Order No.: 2942739
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2942739
Depth
82.5 mm
Test voltage input/output
3.5 kV
Ambient temperature (operation)
-20 °C ... 55 °C
Ambient temperature (storage/transport)
-20 °C ... 70 °C
Mounting position
Vertical (horizontal DIN rail)
Assembly instructions
Can be aligned with > 20 mm spacing
Operating mode
100% operating factor
Degree of protection
IP20
Name
Air and creepage distances between the power circuits
Standards/regulations
EN 50178
Basic insulation
Name
Power station requirements
EMC regulations
Standards/regulations
EN 61000-6-2
EN 61000-6-4
Certificates / Approvals
Certification
GOST
Diagrams/Drawings
Block diagram
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 3 / 5
Feb 3, 2011
EMG 45-ELR3/1,5 Order No.: 2942739
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2942739
Diagram
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 4 / 5
Feb 3, 2011
EMG 45-ELR3/1,5 Order No.: 2942739
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2942739
Address
PHOENIX CONTACT Deutschland GmbH
Flachsmarktstr. 8
32825 Blomberg,Germany
Phone +49 5235 3 12000
Fax +49 5235 3 41200
http://www.phoenixcontact.de
© 2011 Phoenix Contact
Technical modifications reserved;
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 5 / 5
Feb 3, 2011
很抱歉,暂时无法提供与“2942739”相匹配的价格&库存,您可以联系我们找货