Relay module, with soldered-in industrial relay, contact: 2 PDTs, for multi-input fault warnings, with input diode
array in P polarity (6 diodes 1N4007) and capacitor parallel to the coil as well as a multi-input light indicator, input
voltage 230 V AC
The illustration shows version EMG
45-REL/IR-G 24/HWR
Key commercial data
Packing unit
1 pc
GTIN
Weight per Piece (excluding packing)
130.64 GRM
Custom tariff number
85364900
Country of origin
Germany
Technical data
Dimensions
Width
45 mm
Height
75 mm
Depth
82.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 50 °C
Ambient temperature (storage/transport)
-20 °C ... 70 °C
Coil side
Nominal input voltage UN
230 V AC
Input voltage range in reference to UN
0.9 ... 1.1
Typical input current at UN
approx. 16 mA
10/22/2014 Page 1 / 4
https://www.phoenixcontact.com/us/products/2952185
Relay Module - EMG 45-REL/IR-W230/HWR - 2952185
Technical data
Coil side
Typical response time
5 ms ... 15 ms
Typical release time range
15 ms ... 25 ms
Coil resistance
19.5 kΩ
Nominal power consumption
approx. 1 VA
Operating voltage display
LED red
Protective circuit
Decoupling diodes Decoupling diodes
Capacitor Capacitor
Diode type
1 N 4007
Max. operating voltage of diodes
250 V AC
Peak reverse voltage per diode
1300 V
Reverse current per diode
30 µA
Conducting state voltage per diode
approx. 0.8 V
Conducting state current per diode
0.7 A (with single load)
0.2 A (with simultaneous loads)
Contact side
Contact type
Single contact, 2-PDT
Contact material
AgNi
Maximum switching voltage
250 V AC
110 V DC
Maximum inrush current
5A
Limiting continuous current
3A
Interrupting rating (ohmic load) max.
750 VA
General
Type of note
Notes on operation
Note
During installation, the system must be connected in phase.
Test voltage relay winding/relay contact
2 kV AC (50 Hz, 1 min.)
Mechanical service life
> 10 cycles
Standards/regulations
DIN VDE 0110b, Gr. C for 250 V DC
7
DIN EN 50178/DIN VDE 0160 (in relevant parts)
Pollution degree
2
Surge voltage category
II
Mounting position
any
Assembly instructions
In rows with zero spacing
Connection data
Connection method
Screw connection
Stripping length
8 mm
10/22/2014 Page 2 / 4
https://www.phoenixcontact.com/us/products/2952185
Relay Module - EMG 45-REL/IR-W230/HWR - 2952185
Technical data
Connection data
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section AWG/kcmil max
12
Conductor cross section AWG/kcmil min.
24
Screw thread
M3
Classifications
eCl@ss
eCl@ss 4.0
27371102
eCl@ss 4.1
27371102
eCl@ss 5.0
27371001
eCl@ss 5.1
27371001
eCl@ss 6.0
27371001
eCl@ss 7.0
27371001
eCl@ss 8.0
27371001
ETIM
ETIM 2.0
EC000196
ETIM 3.0
EC000196
ETIM 4.0
EC000196
ETIM 5.0
EC000196
UNSPSC
UNSPSC 6.01
30211916
UNSPSC 7.0901
39121515
UNSPSC 11
39121515
UNSPSC 12.01
39121515
UNSPSC 13.2
39121515
Drawings
10/22/2014 Page 3 / 4
https://www.phoenixcontact.com/us/products/2952185
Relay Module - EMG 45-REL/IR-W230/HWR - 2952185
Circuit diagram
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
10/22/2014 Page 4 / 4
很抱歉,暂时无法提供与“2952185”相匹配的价格&库存,您可以联系我们找货
免费人工找货