Power Optocoupler Terminal Block up to 10 A
DEK-OV...
1. Brief Description
The Phoenix Contact Interface DEK terminals offer
complete interface functions in terminal block housings
with a width of only 6.2 mm (0.244 in.) These powerful
interfaces do not only share the design of the terminal
blocks but also their highly convenient application due
to the use of standard terminal accessories.
The DEK family offers the suitable solution for every
industrial voltage valuefor signal input as well as
output.
High switching power is a standard feature of DEKOV optocoupler terminals.
For applications with high switching frequency where
electro-mechanical relays rapidly reach the end of their
service life you can now apply the wear-resistant power
optocoupler DEK-OV terminal block.
Integrated LEDs clearly signal the switching state of
electronic terminal blocks and thus create a very good
overview of the coupling level and the system.
Due to colored EB-DIK jumpering, terminals for
supply and measuring signals the wiring is easy and
efficient.
Integrated protection circuits such as free-wheeling
diodes, diodes against polarity reversal and surge
voltage elements protect coupling components and
thus provide optimum system availability.
Powerful Optocoupler Terminals
Powerful interface modules are required to switch
actuators and controlling devices such as contactors,
solenoid valves or motors directly using cost-efficient
digital output cards (low power, no galvanic isolation
but high-pos.).
The Phoenix Contact DEK-OV interface terminals
offer a complete output interface based on terminal
blocks with a width of only 6.2 mm (0.244 in.).
The key features of this power optocoupler include:
– Wear-resistant switching up to 24 V DC/10 A and
240 V AC/800 mA,
– Status display per LED,
– Galvanic isolation between input and
output 2,5 kV,
– integrated protective circuit at the output,
– Zero voltage switch at AC output,
– Assembly and labeling is the same as for terminal
blocks,
– Jumpering with the EB-DIK jumpers,
– Ambient temperature range – 20 °C (-40˚F) up to
+ 60 °C (140˚F),
– Also available as actuator type.
Headquarters: © Phoenix Contact GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany
Phone +49 - 52 35 - 3 00 • Fax +49 - 52 35 - 34 12 00 • www.phoenixcontact.com
Local contact: www.phoenixcontact.com/salesnetwork
Power optocoupler terminal blocks up to 10 A
2. Technical Data
DC output 3 A
A1+
14
A2-
13+
A2-
A
A2
+
56
DC output 10 A
A1
0
AC output
13
NullspannungsZero voltage
Schalter
swich
A1
13
“…6“
80
14
A2
DEK-OV...
Output up to 10 A max.
8
M3
Connection data
Terminal width 6.2 mm (0.244 in.)
solid
[mm2]
stranded
0.2-2.5
0.2-2.5
AWG
24-14
Input
voltage
Description
Power optocoupler terminal block,
Input: Common mode voltage
output: Common mode voltage
Power optocoupler terminal block, acutator
principle,
Input: Common mode voltage
Output: Common mode voltage
Power optocoupler terminal block,
Input: Common mode voltage
output: AC voltage
(1) Insertion jumper1), for
average and lower level
Can be disconnected
Type
Order No.
Pcs.
pkt.
5 V DC
12 V DC
24 V DC
5 V DC
12 V DC
24 V DC
DEK-OV- 5DC/24DC/3
DEK-OV-12DC/24DC/3
DEK-OV-24DC/24DC/3
DEK-OV- 5DC/24DC/10
DEK-OV-12DC/24DC/10
DEK-OV-24DC/24DC/10
29 41 36 1
29 41 38 7
29 41 37 4
29 61 75 2
29 61 74 9
29 64 32 2
10
10
10
10
10
10
24 V DC
DEK-OV-24DC/24DC/3/AKT
29 64 29 6
10
5 V DC
12 V DC
24 V DC
DEK-OV- 5DC/240AC/800
DEK-OV-12DC/240AC/800
DEK-OV-24DC/240AC/800
29 64 62 3
29 64 63 6
29 64 64 9
10
10
10
Color: Red
Red
Red
Red
Red
2-pos.
3-pos.
4-pos.
5-pos.
10-pos.
EB 2-DIK RD
EB 3-DIK RD
EB 4-DIK RD
EB 5-DIK RD
EB 10-DIK RD
Imax: 26 A
26 A
26 A
26 A
26 A
27 16 69 3
27 16 74 5
27 16 75 8
27 16 76 1
27 16 77 4
100
100
100
100
10
blue
blue
blue
blue
blue
2-pos.
3-pos.
4-pos.
5-pos.
10-pos.
EB 2-DIK BU
EB 3-DIK BU
EB 4-DIK BU
EB 5-DIK BU
EB 10-DIK BU
26 A
26 A
26 A
26 A
26 A
27 16 64 8
27 16 65 1
27 16 66 4
27 16 67 7
27 16 68 0
100
100
100
100
10
blue
Red
white
80-pos.
80-pos.
80-pos.
EB 80-DIK BU
EB 80-DIK RD
EB 80-DIK WH
26 A
26 A
26 A
27 15 94 0
27 15 95 3
27 15 78 8
5
5
5
PHOENIX CONTACT page 2 from 3
Power Optocoupler Terminal Blocks up to 10 A – DEK-OV
Technical Data
Input data (Input)
Operating voltage range [V DC] ± 20 %
Switching level1-signal ("H")
0-signal ("L")
Current at nominal voltage [mA]
Transmission frequency flimit [Hz] (ohmic load)
Input wiring
DC 3 A
DC 10 A
AC
5
12
24
5
12
24
5
12
24
0.8 x UN
0.4 x UN
11
9
7
5
5
4
10
11
11
300
100
10
Operating indicator (LED yellow), protection against polarity reversal
(10 A and AC type surge voltage protection)
Output data (Output)
Operating voltage range
Periodical peak off-state voltage
Maximum continuous load current
Minimum load current
Surge current
Residual voltage at maximum load current
Leakage in the off-state
Max. phase shift (inductive load)
I2t value I2 x t (t = 10 ms)
Switching time ton/toff
Output circuit
3… 30 V DC
5… 30 V DC
10-253 V AC, 50/60 Hz
–
–
600 V
3 A (see ’Derating’) 10 A (see ’Derating’) 0.8 A (see ’Derating’)
–
–
10 mA
–
–
30 A (t =10 ms)
Approx. 0.2 V
< 50 mV