PLC-OS…/SEN
PLC INTERFACE With Solid-State Relay,
Sensor Version
INTERFACE
Data Sheet
103152_en_01
1
© PHOENIX CONTACT - 03/2008
Description
In applications as the interface between the PLC and
sensors (e.g., proximity switches, limit switches or auxiliary
contacts), as a rule only one N/O contact is required. In this
case, the PLC-OS…/SEN input module can be used, which
is specially optimized for these applications and consists of
a 6.2 mm basic terminal block and plug-in miniature solidstate relay with screw or spring-cage connection.
1.1
No Need for Power Terminal Blocks
Unlike conventional input relays, all sensor connections,
including the supply voltage for the sensors and switches,
are connected directly to the PLC INTERFACE module. The
PLC-OS…/SEN can thus be used directly as a terminal strip
with integrated interface function for the incoming sensor
cables, without the need for additional modular terminal
blocks (see also INTERFACE catalog).
– Elimination of the need for modular terminal blocks for
the sensor/switch supply, signal, and sensor ground
– Space savings of around 80%
– Time saving of around 60%
– Reduction in wiring due to plug-in bridges
1.2
Optimum Use of Plug-In Bridges
The PLC INTERFACE module achieves maximum
efficiency with the user-friendly FBST plug-in bridge system.
The PLC-OS…/SEN makes effective use of the bridging
options for the power supply for sensors/switches, for the
supply/sensor ground at the A2 connection, and for the
common supply potential of the PLC at connection 13.
Especially effective here are the 500 mm long colorinsulated continuous plug-in bridges that can easily be cut to
the required length and quickly inserted in the bridge shafts.
They eliminate the need for complicated and timeconsuming loop bridges – the reduction in wiring by
eliminating the need for modular terminal blocks and the use
of all bridging options is around 60%.
1.3
–
–
–
–
–
–
–
–
Additional Advantages
Switching power of up to 24 V DC/3 A, depending on
the type
IP67-protected fully encapsulated optical electronics
Available with input or power solid-state relays as an
option
Integrated input circuit
Solid-state relay can be replaced using an engagement
lever
Wear-resistant switching
Resistant to vibrations and shocks
Inflammability class V0 according to UL94
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is valid for all products listed on the following page:
PLC-OS…/SEN
2
Ordering Data
PLC INTERFACE With Solid-State Relay, Sensor Version
Description
Type
PLC INTERFACE, comprising PLC-BSC...SEN
basic terminal block and plug-in solid-state relay
(see INTERFACE catalog), with screw
connection, for mounting on 3
PLC INTERFACE, comprising PLC-BSP...SEN
basic terminal block and plug-in solid-state relay
(see INTERFACE catalog), with spring-cage
connection, for mounting on 3
1
Order No.
Pcs./Pck.
2966773
10
120 V AC/110 V DC PLCOSC-120UC/48DC/100/SEN
2966799
10
230 V AC/220 V DC1 PLCOSC-230UC/48DC/100/SEN
2966809
10
2967578
10
120 V AC/110 V DC PLCOSP-120UC/48DC/100/SEN
2967581
10
230 V AC/220 V DC1 PLCOSP-230UC/48DC/100/SEN
2967594
10
24 V DC PLCOSC- 24DC/48DC/100/SEN
24 V DC PLCOSP- 24DC/48DC/100/SEN
The PLC-ATP BK insulating plate must be installed for voltages greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules
(see "Accessories"). FBST 8-PLC... or FBST 500... is then used for potential bridging.
With the 120 V and 230 V modules, an OPT-60DC/... 60 V solid-state relay is normally used due to the input circuit integrated in the basic terminal
block.
For the protection of input and output, inductive loads must be dampened with an effective protective circuit.
Accessories
Description
Type
Order No.
Pcs./Pck.
Insulating plate
PLC-ATP BK
2966841
25
The PLC-ATP BK insulating plate should be used in the following cases: always fit at the start and end of a PLC terminal strip for voltages
greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules (FBST 8-PLC... or FBST 500... can be used for
potential bridging) and for safe isolation between adjacent modules.
For additional accessories such as power terminal blocks and plug-in bridges, please refer to the INTERFACE catalog or www.phoenixcontact.com.
3
Technical Data
Input Data
...24DC...
...120UC...
...230UC...
24 V DC
120 V AC/110 V DC
230 V AC/220 V DC
Nominal input voltage
Permissible range (with reference to UN)
0.8 ... 1.2 x UN
0.8 ... 1.1 x UN
1 signal ("H")
0.8 x UN
0.8 x UN
0 signal ("L")
0.4 x UN
0.3 x UN
Switching level
Typical input current at UN
8 mA
Typical response time at UN
20 μs
6 ms
Typical release time at UN
300 μs
10 ms
Transmission frequency flimit
300 Hz
10 Hz
Yellow LED, protection
against polarity
reversal, free-wheeling
diode
Yellow LED, bridge rectifier
Input circuit
4 mA
3 ms
5 ms
Output Data
Maximum switching voltage
48 V DC
Minimum switching voltage
3 V DC
Limiting continuous current
100 mA
Output configuration
2-wire floating
Output circuit
Protection against polarity reversal, surge protection
Voltage drop at maximum limiting continuous current
≤1V
103152_en_01
PHOENIX CONTACT
2
PLC-OS…/SEN
General Data
Impulse voltage withstand level
2.5 kV, 50 Hz, 1 min.
Ambient temperature range
Operation
-25°C ... 60°C (230 V type 20°C ... 55°C)
Storage/transport
-40°C ... 85°C
Nominal operating mode
100% operating factor
Inflammability class according to UL 94 (housing)
V0
Standards/specifications1
IEC 60664, IEC 60664 A, DIN VDE 0110 (basic insulation)
Pollution degree
2
Surge voltage category
III
Mounting position
Any
Mounting
Can be aligned without spacing
Conductor cross-section
Solid, with screw connection
0.14 mm2 ... 2.5 mm2 (26 - 14 AWG)
Stranded, with screw connection
0.14 mm2 ... 1.5 mm2 (26 - 14 AWG)
Solid, with spring-cage connection
0.2 mm2 ... 2.5 mm2 (24 - 14 AWG)
Stranded, with spring-cage connection
0.2 mm2 ... 1.5 mm2 (24 - 14 AWG)
Stripping length
Screw connection
10 mm
Spring-cage connection
8 mm
Dimensions (W x H x D)
6.2 mm x 94 mm x 80 mm
Housing material
Polyamide PA, green
1
The PLC-ATP BK insulating plate must be installed for safe isolation between adjacent modules (see "Accessories"). FBST 8-PLC... or FBST 500... is
then used for potential bridging.
Tests/Approvals
c
Uu
F
CE
UL
GL
Block Diagram
5
Load current [A]
4
13+
A2
14
BB
Derating Curve
3
2
1
1)
A1
1)
103152_en_01
The input circuit
depends on the type
0
0
10
20
30
40
50
60
Ambient temperature [°C]
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
3