Safety relay for emergency stop and safety door and light grid monitoring up to SIL 3 or Cat. 4, PL e according to
EN ISO 13849, single or two-channel operation, 3 enabling current paths, nominal input voltage of 24 V AC/DC,
plug-in screw terminal blocks
Why buy this product
Manually monitored and automatic activation
Up to Cat. 4/PL e according to ISO 13849-1, SILCL 3 according to IEC 62061, SIL 3 according to IEC 61508
Three enabling and one signaling current path
Single and two-channel control
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4017918927202
Weight per Piece (excluding packing)
220.000 g
Custom tariff number
85371098
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
22.5 mm
Height
99 mm
03/09/2018 Page 1 / 10
https://www.phoenixcontact.com/us/products/2981059
Safety relays - PSR-SCP- 24UC/ESL4/3X1/1X2/B - 2981059
Technical data
Dimensions
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 55 °C
Ambient temperature (storage/transport)
-40 °C ... 70 °C
Max. permissible relative humidity (operation)
75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)
75 % (on average, 85% infrequently, non-condensing)
Maximum altitude
≤ 2000 m (Above sea level)
Input data
Nominal input voltage UN
24 V AC/DC
Input voltage range in reference to UN
0.85 ... 1.1
Typical input current at UN
150 mA AC
70 mA DC
Voltage at input/start and feedback circuit
approx. 24 V DC
Typical response time
25 ms (manual start)
100 ms (automatic start)
Typical release time
10 ms
Concurrence input 1/2
∞
Recovery time
1s
Operating voltage display
Green LED
Status display
Green LED
Protective circuit
Fuse PTC resistor
Surge protection Suppressor diode
Output data
Contact type
3 enabling current paths
1 signaling current path
Contact material
AgSnO2, + 0.2 µm Au
Maximum switching voltage
250 V AC/DC
Minimum switching voltage
15 V AC/DC
Limiting continuous current
6A
Maximum inrush current
6A
Inrush current, minimum
25 mA
Sq. Total current
72 A (ITH = I1 + I2 + I3 )
Interrupting rating (ohmic load) max.
144 W (24 V DC, τ = 0 ms)
2
2
2
2
2
288 W (48 V DC, τ = 0 ms)
77 W (110 V DC, τ = 0 ms)
03/09/2018 Page 2 / 10
https://www.phoenixcontact.com/us/products/2981059
Safety relays - PSR-SCP- 24UC/ESL4/3X1/1X2/B - 2981059
Technical data
Output data
88 W (220 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms)
Maximum interrupting rating (inductive load)
48 W (24 V DC, τ = 40 ms)
40 W (48 V DC, τ = 40 ms)
35 W (110 V DC, τ = 40 ms)
33 W (220 V DC, τ = 40 ms)
Switching capacity min.
0.4 W
Mechanical service life
Approx. 10 cycles
Switching capacity (360/h cycles)
6 A (24 V DC)
7
5 A (230 V AC)
Output fuse
10 A gL/gG NEOZED (N/O contact)
General
Relay type
Electromechanical relay with forcibly guided contacts in accordance with
EN 50205
Nominal operating mode
100% operating factor
Net weight
193.9 g
Mounting position
any
Mounting type
DIN rail mounting
Degree of protection
IP20
IP54
Min. degree of protection of inst. location
IP54
Housing color
yellow
Connection data
Connection method
Screw connection
pluggable
Yes
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M3
Safety-related characteristic data
Stop category
0
Designation
IEC 61508 - High demand
03/09/2018 Page 3 / 10
https://www.phoenixcontact.com/us/products/2981059
Safety relays - PSR-SCP- 24UC/ESL4/3X1/1X2/B - 2981059
Technical data
Safety-related characteristic data
Safety Integrity Level (SIL)
3
Designation
IEC 61508 - Low demand
Safety Integrity Level (SIL)
3
Designation
EN ISO 13849
Performance level (PL)
e
Category
4
Designation
EN 62061
Safety Integrity Level Claim Limit (SIL CL)
3
Standards and Regulations
Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
DIN EN 50178/VDE 0160
Rated insulation voltage
250 V
Rated surge voltage/insulation
4 kV / basic insulation (safe isolation, reinforced insulation, and 6 kV
between A1-A2/logic/enabling and signaling current paths)
Degree of pollution
2
Overvoltage category
III
Shock
15g
Vibration (operation)
10 Hz ...150 Hz, 2g
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Circuit diagram
A1
S11 S33 S12
»
23
33
41
14
24
34
42
K1
=
Logic
A2
13
K2
S34 S35 S22
03/09/2018 Page 4 / 10
https://www.phoenixcontact.com/us/products/2981059
Safety relays - PSR-SCP- 24UC/ESL4/3X1/1X2/B - 2981059
Circuit diagram
L+
(L1)
Emergency
stop
S1
S11
(+)
A1
S12
( )
S22
( )
13
23
33
41
K3
PSR-ESL4/3x1/1x2/B
A2
(+)
( )
( )
S33
S34
S35
14
24
34
42
M
Reset
S2
K3
M
(N)
Single-channel safety door monitoring
03/09/2018 Page 5 / 10
https://www.phoenixcontact.com/us/products/2981059
Safety relays - PSR-SCP- 24UC/ESL4/3X1/1X2/B - 2981059
Circuit diagram
L+
(L1)
Safety door
21
open
B1
22
13
B2
14
closed
S11
(+)
A1
S12
( )
S22
( )
13
23
33
41
K3
14
24
34
42
K4
PSR-ESL4/3x1/1x2/B
( )
(+)
S33 S34
A2
( )
S35
K3
K4
Reset
S2
M
K4
K3
M
(N)
Two-channel safety door monitoring
03/09/2018 Page 6 / 10
https://www.phoenixcontact.com/us/products/2981059
Safety relays - PSR-SCP- 24UC/ESL4/3X1/1X2/B - 2981059
Circuit diagram
L+
(L1)
Transmitter
Light grid type 4
A1
Receiver
OSSD1 OSSD2
S11
(+)
S12
( )
S22
( )
13
23
33
41
K3
14
24
34
42
K4
PSR-ESL4/3x1/1x2/B
A2
(+)
( )
( )
S33
S34
S35
K4
Reset
K4
M
S2
K3
K3
M
(N)
Light grid monitoring
03/09/2018 Page 7 / 10
https://www.phoenixcontact.com/us/products/2981059
Safety relays - PSR-SCP- 24UC/ESL4/3X1/1X2/B - 2981059
Circuit diagram
L+
(L1)
Emergency
stop
S11
(+)
A1
S1
S12
( )
S22
( )
13
23
33
41
K3
14
24
34
42
K4
PSR-ESL4/3x1/1x2/B
( )
(+)
S33 S34
A2
( )
S35
K4
Reset
S2
M
K4
K3
K3
M
(N)
Two-channel emergency stop monitoring
Classifications
eCl@ss
eCl@ss 4.0
27371102
eCl@ss 4.1
27371102
eCl@ss 5.0
27371901
eCl@ss 5.1
27371901
eCl@ss 6.0
27371819
eCl@ss 7.0
27371819
eCl@ss 8.0
27371819
eCl@ss 9.0
27371819
ETIM
ETIM 2.0
EC001449
ETIM 3.0
EC001449
ETIM 4.0
EC001449
ETIM 5.0
EC001449
ETIM 6.0
EC001449
03/09/2018 Page 8 / 10
https://www.phoenixcontact.com/us/products/2981059
Safety relays - PSR-SCP- 24UC/ESL4/3X1/1X2/B - 2981059
Classifications
UNSPSC
UNSPSC 6.01
30211901
UNSPSC 7.0901
39121501
UNSPSC 11
39121501
UNSPSC 12.01
39121501
UNSPSC 13.2
39121501
Approvals
Approvals
Approvals
UL Listed / cUL Listed / Functional Safety / EAC / EAC / cULus Listed
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 140324
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 140324
Functional Safety
01/205/5265.01/17
EAC
RU CDE.A*30.B.01082
EAC
EAC-Zulassung
03/09/2018 Page 9 / 10
https://www.phoenixcontact.com/us/products/2981059
Safety relays - PSR-SCP- 24UC/ESL4/3X1/1X2/B - 2981059
Approvals
cULus Listed
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
03/09/2018 Page 10 / 10
很抱歉,暂时无法提供与“2981059”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+1894.191641+245.83150
- 5+1758.798955+228.26000