https://www.phoenixcontact.com/us/produkte/2986041
Extension module - PSR-SPP- 24DC/TS/SDI8/SDIO4 - 2986041
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Module for I/O extension of the PSR-TRISAFE master module with 8 safe inputs and 4 safe,
freely parameterizable channels (safe inputs or outputs), easy connection via PSR-TBUS DIN rail
connector, width: 22.5 mm
The figure shows a version with
a screw connection
Why buy this product
Flexible extension with safe inputs and outputs
Narrow 22.5 mm housing
4 safe digital outputs or 4 additional digital inputs (that can be configured using SAFECONF)
Multifunctional use for a wide range of safety functions
Easy graphical configuration instead of complex programming
Quick startup thanks to user-friendly simulation and test options
Including PSR-TBUS plug-in connector (DIN rail connector) for adapting to the PSR-TRISAFE-M master module
Up to Cat. 4/PL e according to ISO 13849-1, SILCL 3 according to IEC 62061, SIL 3 according to IEC 61508
8 safe digital inputs
2 alarm outputs or 2 clock outputs (that can be configured using SAFECONF)
Key commercial data
Packing unit
0
Minimum order quantity
1
Catalog page
Page 31 (IF-2011)
GTIN
Custom tariff number
85389091
Country of origin
GERMANY
Technical data
Input data
Nominal input voltage UN
24 V DC (A1 / A2)
Input voltage range in reference to UN
0.85 ... 1.1
Typical input current at UN
100 mA
Maximum response time
< 30 ms
Bypassing voltage dips
20 ms
Recovery time
< 10 s
05.06.2012 Page 1 / 4
https://www.phoenixcontact.com/us/produkte/2986041
Extension module - PSR-SPP- 24DC/TS/SDI8/SDIO4 - 2986041
Technical data
Input data
Protective circuit
Surge protection Suppressor diode
Status display
2 LEDs (green, red)
Number of safe inputs
12 (of which 4 can be configured as input or output)
Nominal voltage UN
24 V DC
Typical current consumption
4 mA
Signal level "0" signal
11 V
Permissible cable length
2000 m
Error detection time at 1-channel structure
很抱歉,暂时无法提供与“2986041”相匹配的价格&库存,您可以联系我们找货