https://www.phoenixcontact.com/us/products/2986229
Safety module - PSR-SCP- 24DC/TS/S - 2986229
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Freely configurable safety module with 20 safe inputs and 4 safe outputs; 4 alarm, 2 clock, and 2 ground
switching outputs; diagnostics possible via bus gateways, up to SILCL 3, Cat.4/PL e, SIL 3, EN 50156, plug-in
screw connection terminal blocks
Why buy this product
Freely configurable safety module for monitoring emergency stops, safety doors, light grids, etc.
With 20 safe inputs, 4 safe outputs, 4 alarm outputs, and 2 clock outputs on a design width of just 67.5 mm
Multifunctional use for a wide range of safety functions
Including IFS-CONFSTICK memory stick for easily storing and saving the configuration
Easy graphical configuration with the SAFECONF software
Easy graphical configuration instead of complex programming
Quick startup thanks to comprehensive simulation and test functions
Option for connecting fieldbus gateways for diagnostics and signaling functions
Up to Cat. 4/PL e according to ISO 13849-1, SILCL 3 according to IEC 62061, SIL 3 according to IEC 61508
EN 50156
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4046356477192
Weight per Piece (excluding packing)
420.000 g
Custom tariff number
85371098
Country of origin
Germany
03/28/2018 Page 1 / 11
https://www.phoenixcontact.com/us/products/2986229
Safety module - PSR-SCP- 24DC/TS/S - 2986229
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
67.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 55 °C
Ambient temperature (storage/transport)
-20 °C ... 70 °C
Max. permissible relative humidity (operation)
75 % (On average, 85 % occasionally)
Max. permissible humidity (storage/transport)
75 % (On average, 85 % occasionally)
Air pressure (operation)
70 kPa ... 108 kPa (up to 3000 m above mean sea level)
Air pressure (storage/transport)
66 kPa ... 108 kPa (up to 3500 m above mean sea level)
Maximum altitude
max. 2000 m (See Appendix "Using PSR-TRISAFE
modules at altitudes greater than 2000 m above sea level")
Power supply
Rated control circuit supply voltage US
24 V DC (A1/A2)
18 V DC ... 30 V DC (Incl. all tolerances, incl. residual ripple)
Rated control supply current IS
typ. 110 mA
Limiting continuous current
max. 6 A (For looped-through current paths A1/A1 and A2/A2)
Filter time
typ. 20 ms (Load-dependent, in the event of voltage dips at US)
Status display
3x LED green, 1x LED red
Protective circuit
Yes, within the scope of the operating voltage limits
Digital inputs
Description of the input
Digital, type HTL
Number of inputs
10 (Two-channel, up to SIL 3)
20 (Single-channel, up to SIL 2)
Input voltage range "0" signal
0 V DC ... 5 V DC (for safe Off)
Input voltage range "1" signal
11 V DC ... 30 V DC
Current consumption
typ. 4 mA
Cable length
max. 2000 m
Status display
20 x LED green (1 LED per input)
Digital outputs
Number of outputs
4 (Safe semiconductor outputs, up to Cat. 4 in accordance with
EN ISO 13849-1)
03/28/2018 Page 2 / 11
https://www.phoenixcontact.com/us/products/2986229
Safety module - PSR-SCP- 24DC/TS/S - 2986229
Technical data
Digital outputs
2 (Ground switching outputs)
Nominal output voltage
24 V DC (Supply via 24 V/0 V)
Nominal output voltage range
18 V DC ... 30 V DC (Incl. all tolerances, incl. residual ripple)
Limiting continuous current
2 A (Per channel, see Derating)
2 A (Total current of all outputs)
Output voltage
< 5 V (Low state)
Leakage current
max. 2 mA
Max. capacitive load
max. 1 µF (Electronic components)
Max. inductive load
See "Protective circuit"
Test pulses
< 1 ms
Note on protection circuit
Yes, within the scope of the operating voltage limits
Short-circuit protection
Yes
Status display
4 x LED green (1 LED per output)
Clock outputs
Output description
Digital
Number of outputs
2
Voltage
24 V DC (Supply via 24 V/0 V)
Limiting continuous current
100 mA
Test pulses
< 1 ms
Short-circuit protection
Yes
Alarm outputs
Output description
Digital
Number of outputs
4
Voltage
24 V DC (Supply via 24 V/0 V)
Limiting continuous current
100 mA
Short-circuit protection
Yes
Times
Response time
max. 30 ms (plus response time of PSR-TS-SDOR4)
Recovery time
< 10 s
General
Nominal operating mode
100% operating factor
Net weight
154 g
Mounting position
On horizontal DIN rail
Mounting type
DIN rail mounting
Degree of protection
IP20
03/28/2018 Page 3 / 11
https://www.phoenixcontact.com/us/products/2986229
Safety module - PSR-SCP- 24DC/TS/S - 2986229
Technical data
General
IP54
Min. degree of protection of inst. location
IP54
Housing material
Polyamide PA non-reinforced
Housing color
yellow
Number of possible extension modules
1 (Max. continuous current via PSR-TBUS: 4 A)
Connection data
Connection method
Screw connection
pluggable
Yes
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M3
Torque
0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Safety-related characteristic data
Stop category
0
Designation
IEC 61508 - High demand
Safety Integrity Level (SIL)
2 ()
3 (2-channel parameterization)
Designation
IEC 61508 - Low demand
Safety Integrity Level (SIL)
2 ()
3 (2-channel parameterization)
Designation
EN ISO 13849
Performance level (PL)
d ()
e (2-channel parameterization)
Category
2 ()
4 (2-channel parameterization)
Designation
EN 62061
Safety Integrity Level Claim Limit (SIL CL)
2 ()
3 (2-channel parameterization)
Designation
EN 50156
Safety Integrity Level (SIL)
max. 3 (Reference IEC 61508)
03/28/2018 Page 4 / 11
https://www.phoenixcontact.com/us/products/2986229
Safety module - PSR-SCP- 24DC/TS/S - 2986229
Technical data
Standards and Regulations
Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
DIN EN 50178
Degree of pollution
2
Overvoltage category
III
Vibration (operation)
2g
Shock (operation)
10g (Δt = 11 ms, three shocks in each space direction)
10g (Δt = 16 ms, continuous shock, 1000 shocks in each space direction)
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Diagram
Circuit diagram
2
POWER
24V DC
1,5
TBUS
NON-SAFE
Total current
Output Ox [A]
A1 A2
1
0,5
0
25 30 35 40 45 50 55 60
Ambient temperature [°C]
TEST PULSE
OUTPUT
I0 I1
I19 M0 M1 M2 M3
SAFE INPUT
MONITORING
OUTPUT
LOGIC
POWER
24V DC
0
T0 T0 T1 T1
SAFE OUTPUT
USB
CONF
STICK
24V 0V O0 O1 O2 O3 O0- O1-
03/28/2018 Page 5 / 11
https://www.phoenixcontact.com/us/products/2986229
Safety module - PSR-SCP- 24DC/TS/S - 2986229
Application drawing
TBUS
NON-SAFE
A1
A1
A2
A2
24V
0V
O0O1T0
T0
T1
T1
M0
M1
M2
M3
24V DC
I0
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
I17
I18
I19
O0
O1
O2
O3
TRISAFE-S
S1
K2
K1
K1
K2
S2
0V
Classifications
eCl@ss
eCl@ss 4.0
27371102
eCl@ss 4.1
27371102
eCl@ss 5.0
27371901
eCl@ss 5.1
27371901
eCl@ss 6.0
27371001
eCl@ss 7.0
27371001
eCl@ss 8.0
27371819
eCl@ss 9.0
27371819
ETIM
ETIM 2.0
EC001449
ETIM 3.0
EC001449
ETIM 4.0
EC001449
ETIM 5.0
EC001449
ETIM 6.0
EC001449
UNSPSC
UNSPSC 6.01
30211901
UNSPSC 7.0901
39121501
UNSPSC 11
39121501
UNSPSC 12.01
39121501
03/28/2018 Page 6 / 11
https://www.phoenixcontact.com/us/products/2986229
Safety module - PSR-SCP- 24DC/TS/S - 2986229
Classifications
UNSPSC
UNSPSC 13.2
39121501
Approvals
Approvals
Approvals
UL Listed / cUL Listed / Functional Safety / cULus Listed
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 140324
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 140324
Functional Safety
01/205/5151.03/17
cULus Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Accessories
Accessories
Device parameterization
03/28/2018 Page 7 / 11
https://www.phoenixcontact.com/us/products/2986229
Safety module - PSR-SCP- 24DC/TS/S - 2986229
Accessories
Configuration package - SAFECONF - 2986119
Configuration software for SafetyBridge technology and PSR-TRISAFE modules, connecting cable for PSR-TRISAFE
DIN rail connector
DIN rail bus connectors - ME 22,5 TBUS 1,5/ 5-ST-3,81 GN - 2707437
Plug component, nominal current: 8 A, nominal current (Ex): 8 A, nominal voltage (Ex): 125 V, number of positions: 5,
pitch: 3.81 mm, Articles with gold-plated contacts, bus connectors for connecting with electronic housings
DIN rail bus connectors - PSR-TBUS - 2890425
DIN rail connector for safety switching devices, for supplying/controlling/monitoring (depending on the module)
Filter terminal block
Filter terminal block - PSR-FTB/20/86 - 2904477
Terminal block for filtering test pulses from safe semiconductor outputs with adjustable filter values (20 µF/86 µF), as well
as for EMC filtering of 24 V signals up to an amperage of 2 A.
Filter terminal block - PSR-FTB/1.5/11.5 - 2904476
Terminal block for filtering test pulses from safe semiconductor outputs with adjustable filter values (1.5 µF/11.5 µF), as
well as for EMC filtering of 24 V signals up to an amperage of 2 A.
03/28/2018 Page 8 / 11
https://www.phoenixcontact.com/us/products/2986229
Safety module - PSR-SCP- 24DC/TS/S - 2986229
Accessories
Gateways/Proxies
Data interface - EM-CAN-GATEWAY-IFS - 2901504
®
Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via CANopen . The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Data interface - EM-MODBUS-GATEWAY-IFS - 2901528
Gateway for the connection of up to 32 INTERFACE system devices via Modbus/TCP to a higher-level controller. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Data interface - EM-DNET-GATEWAY-IFS - 2901529
Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via DeviceNet™. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Data interface - EM-ETH-GATEWAY-IFS - 2901988
Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via EtherNet/IP™. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Data interface - EM-PNET-GATEWAY-IFS - 2904472
Gateway for the connection of up to 32 INTERFACE system devices via PROFINET to a higher-level controller. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
03/28/2018 Page 9 / 11
https://www.phoenixcontact.com/us/products/2986229
Safety module - PSR-SCP- 24DC/TS/S - 2986229
Accessories
Data interface - EM-PB-GATEWAY-IFS - 2297620
Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via PROFIBUS DP. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Data interface - EM-RS232-GATEWAY-IFS - 2901526
Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via Modbus/RS-232. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Data interface - EM-RS485-GATEWAY-IFS - 2901527
Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via Modbus/RS-485. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Memory block
Memory block - IFS-CONFSTICK - 2986122
Multi-functional memory block for the INTERFACE systemf for easy storage and backup of the configuration.
Copy and delete station - COPYSTATION - IFS - 2901985
Copy and delete station for IFS-CONFSTICK memory modules for copying data from a master stick to up to four slave
sticks and for deleting data on one ore more slave sticks, connection via USB/mini USB cable.
03/28/2018 Page 10 / 11
https://www.phoenixcontact.com/us/products/2986229
Safety module - PSR-SCP- 24DC/TS/S - 2986229
Accessories
Programming cable
USB cable - CABLE-USB/MINI-USB-3,0M - 2986135
USB connecting cable: USB plug type A to USB plug type Mini-B; length: 3 m
Starter kit
Starter kit - PSR-TRISAFE STARTER KIT - 2986300
STARTER kit for the PSR-TRISAFE safety module consisting of: PSR-TRISAFE demoboard (with inputs & outputs),
SAFECONF CD, Quick Start Guide, USB cable (3m) , voltage supply with international connector adapters and package
inserts.
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
03/28/2018 Page 11 / 11