Test disconnect terminal block - UGSK 6 - 3026285
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Test disconnect terminal block, With slide, Connection method: Screw connection, Cross section: 0.5 mm² -10
mm² , AWG: 20 - 10, Width: 8.2 mm, Mounting type: NS 35/7,5, NS 35/15, NS 32, Color: gray
Product Features
The URTK 6 test disconnect terminal block and the UGSK 6 slide-type terminal block were developed specifically for use in current transformer
secondary circuits
Can be fitted on both sides with fixed and switchable bridges as well as test sockets with 4 mm diameter
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
31.61 GRM
Custom tariff number
85369010
Country of origin
Poland
Technical data
General
Number of levels
1
Number of connections
2
Color
gray
Insulating material
PA
Inflammability class according to UL 94
V0
Rated surge voltage
6 kV
Pollution degree
3
Surge voltage category
III
Insulating material group
I
Connection in acc. with standard
IEC 60947-7-1
Maximum load current (lower level)
57 A
Additional text
with 10 mm² conductor cross section
11/03/2014 Page 1 / 8
https://www.phoenixcontact.com/us/products/3026285
Test disconnect terminal block - UGSK 6 - 3026285
Technical data
General
Nominal current IN (lower level)
41 A
Nominal voltage UN
400 V
Open side panel
ja
Shock protection test specification
DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection
guaranteed
Finger protection
guaranteed
Surge voltage test setpoint
7.3 kV
Result of surge voltage test
Test passed
Power frequency withstand voltage setpoint
1.89 kV
Result of power-frequency withstand voltage test
Test passed
Checking the mechanical stability of terminal points (5 x conductor
connection)
Test passed
Bending test rotation speed
10 rpm
Bending test turns
135
Bending test conductor cross section/weight
0.5 mm² / 0.3 kg
2
6 mm / 1.4 kg
10 mm² / 2 kg
Result of bending test
Test passed
Conductor cross section tensile test
0.5 mm²
Tractive force setpoint
40 N
Conductor cross section tensile test
6 mm²
Tractive force setpoint
160 N
Conductor cross section tensile test
10 mm²
Tractive force setpoint
180 N
Tensile test result
Test passed
Requirements, voltage drop
U1 ≤ 3.2 mV; U2 ≤ 1.5 x U1
Result of voltage drop test
Test passed
Temperature-rise test
Test passed
Dimensions
Length
91 mm
Width
8.2 mm
Height NS 35/7,5
51 mm
Height NS 35/15
58.5 mm
Height NS 32
56 mm
Connection data
Conductor cross section solid min.
0.5 mm²
11/03/2014 Page 2 / 8
https://www.phoenixcontact.com/us/products/3026285
Test disconnect terminal block - UGSK 6 - 3026285
Technical data
Connection data
Conductor cross section solid max.
10 mm²
Conductor cross section stranded min.
0.5 mm²
Conductor cross section stranded max.
6 mm²
Conductor cross section AWG/kcmil min.
20
Conductor cross section AWG/kcmil max
8
Conductor cross section stranded, with ferrule without plastic sleeve min.
0.5 mm²
Conductor cross section stranded, with ferrule without plastic sleeve max.
6 mm²
Conductor cross section stranded, with ferrule with plastic sleeve min.
0.5 mm²
Conductor cross section stranded, with ferrule with plastic sleeve max.
6 mm²
2 conductors with same cross section, solid min.
0.5 mm²
2 conductors with same cross section, solid max.
2.5 mm²
2 conductors with same cross section, stranded min.
0.5 mm²
2 conductors with same cross section, stranded max.
4 mm²
2 conductors with same cross section, stranded, ferrules without plastic
sleeve, min.
0.5 mm²
2 conductors with same cross section, stranded, ferrules without plastic
sleeve, max.
2.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic
0.5 mm²
sleeve, min.
2 conductors with same cross section, stranded, TWIN ferrules with plastic
4 mm²
sleeve, max.
Connection method
Screw connection
Stripping length
10 mm
Screw thread
M4
Tightening torque, min
1.2 Nm
Tightening torque max
1.4 Nm
Disconnect element
M3 0.6 Nm 0.8 Nm
Classifications
eCl@ss
eCl@ss 4.0
27141126
eCl@ss 4.1
27141126
eCl@ss 5.0
27141127
eCl@ss 5.1
27141127
eCl@ss 6.0
27141127
eCl@ss 7.0
27141127
eCl@ss 8.0
27141126
11/03/2014 Page 3 / 8
https://www.phoenixcontact.com/us/products/3026285
Test disconnect terminal block - UGSK 6 - 3026285
Classifications
ETIM
ETIM 2.0
EC000902
ETIM 3.0
EC000902
ETIM 4.0
EC000902
ETIM 5.0
EC000902
UNSPSC
UNSPSC 6.01
30211811
UNSPSC 7.0901
39121410
UNSPSC 11
39121410
UNSPSC 12.01
39121410
UNSPSC 13.2
39121410
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / GOST / PRS / GOST / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
UL Recognized
mm²/AWG/kcmil
26-8
Nominal current IN
50 A
Nominal voltage UN
300 V
11/03/2014 Page 4 / 8
https://www.phoenixcontact.com/us/products/3026285
Test disconnect terminal block - UGSK 6 - 3026285
Approvals
cUL Recognized
mm²/AWG/kcmil
26-8
Nominal current IN
50 A
Nominal voltage UN
300 V
GOST
PRS
GOST
cULus Recognized
Drawings
11/03/2014 Page 5 / 8
https://www.phoenixcontact.com/us/products/3026285
Test disconnect terminal block - UGSK 6 - 3026285
Circuit diagram
Schematic diagram
Three-phase linked transducer test set
11/03/2014 Page 6 / 8
https://www.phoenixcontact.com/us/products/3026285
Test disconnect terminal block - UGSK 6 - 3026285
Schematic diagram
Three-phase transducer test set
11/03/2014 Page 7 / 8
https://www.phoenixcontact.com/us/products/3026285
Test disconnect terminal block - UGSK 6 - 3026285
Circuit diagram
a = open
1 = cover
2 = fixed bridge
3 = switch bar
4 = switching lock
5 = test plug socket
6 = short-circuit plug
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
11/03/2014 Page 8 / 8