Four-Conductor Spring Cage Terminal Blocks
ST ...-QUATTRO
The double connection of ST...-QUATTRO allows four
conductors to be connected on one potential. The
QUATTRO variants can therefore be used as compact
power distributors.
The FBS plug-in bridge system allows bridging any
number of terminal blocks and thus achieves further
power distribution.
Phoenix Contact GmbH & Co. KG • 32823 Blomberg, Germany
Phone +49 52 35 3-00 • Fax +49 52 35 3-4 12 00 • www.phoenixcontact.com
Local Contact: www.phoenixcontact.com/salesnetwork
Four-Conductor Spring Cage
Terminal Block
ST 1,5-QUATTRO
(IEC)
[mm2]
rigid
solid
flexible
stranded
AWG
I
[A]
U
[V]
IEC 60 947-7-1
0.08-1.5
0.08-1.5
28-16 17.5* 500
EN 50 019**
0.08-1.5
0.08-1.5
28-16 17.5* 420
** EU certificate of design approval no.: KEMA 00ATEX2129U 1)
1) For installation notes and the use of accessories for EEx e applications
see Catalog CLIPLINE.
* The max. load current must not be exceeded by the total current of all connected
conductors.
u P F KEMA
Technical data
Spring cage terminal block,
for mounting on 3
gray
blue
terminal width 4.2
terminal width 4.2
Type
Order No.
Pcs.
Pkt.
ST 1,5-QUATTRO
ST 1,5-QUATTRO BU
30 31 18 6
30 31 19 9
50
50
(1) End cover
gray
D-ST 2,5-QUATTRO
30 30 51 4
50
(2) Segment cover, for covering
projecting terminal segments
gray
DS-ST 2,5
30 36 60 2
10
ISH 1,5/0,2
ISH 1,5/0,5
32 06 13 1
30 31 03 4
50
50
30 30 11 6
30 30 12 9
30 30 13 2
30 30 14 5
30 30 15 8
30 30 35 2
50
50
50
50
10
10
(3) Insulating stop sleeve, prevents unintentional clamping
of the insulation in the case of smaller cross sections
white
Cross section range:
0.08-0.2 mm2
0.25-0.5 mm2
gray
(4) Plug-in bridge, for
cross-connections in the
terminal center
2-pos.
3-pos.
4-pos.
5-pos.
10-pos.
20-pos.
FBS 2-4
FBS 3-4
FBS 4-4
FBS 5-4
FBS 10-4
FBS 20-4
Imax.: 17.5 A
17.5 A
17.5 A
17.5 A
17.5 A
17.5 A
(5) Partition plate, for
visual and electrical separation
of terminal groups, 2 mm thick
ATP ST-QUATTRO
30 30 81 5
50
(6) Test adapter, for 4 mm ∅ test connector PS
and 4 mm ∅ safety test connectors,
making contact in the bridge shaft
PAI 4
30 30 92 5
10
(7) Warning cover, for the
operating shafts of the “mini-spring”
ST spring cage terminal blocks
WST 1,5
30 30 95 8
50
(8) Screwdriver, for
actuating the tension spring
SZF 0 - 0,4 x 2,5
12 04 50 4
10
(9) Zack marker sheet, flat, 100-section, for
labeling the outer marker grooves
white
ZBF 4:UNPRINTED
08 08 58 7
10
ZB 4:UNPRINTED
08 05 00 1
10
(10) Zack strip, 10-section, for
labeling in the terminal center
and on the plug-in bridges
white
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7.5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current/ cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulation material group
–/–
Capacity connection
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inflammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nom. voltage / nom. current / conduc. sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
Phoenix Contact page 2 of 10
4.2 / 72 / 2.2
36.5 / 44
17.5 / 1.5
6/3
III / I
0.25 - 1.5
0.25 - 1.5
0.5
10
A1
PA
V0
–
–
Four-Conductor Spring Cage
Ground Terminal Block
ST 1,5-QUATTRO-PE
(IEC)
[mm2]
rigid
solid
flexible
stranded
AWG
IEC 60 947-7-2
0.08-1.5
0.08-1.5
28-16
EN 50 019*
0.08-1,5
0.08-1.5
28-16
* EU certificate of design approval no.: KEMA 00ATEX2129U 1)
1) For installation notes and the use of accessories for EEx e applications
see Catalog CLIPLINE.
The current carrying capacity of the mounting rails should be observed.
u P F KEMA
Technical data
Spring cage ground terminal block,
green-yellow
for mounting on 3
terminal width 4.2
Type
Order No.
Pcs.
Pkt.
ST 1,5-QUATTRO-PE
30 31 20 9
50
(1) End cover
gray
D-ST 2,5-QUATTRO
30 30 51 4
50
(2) Segment cover, for covering
projecting terminal segments
gray
DS-ST 2,5
30 36 60 2
10
(3) Insulating stop sleeve, prevents unintentional clamping
of the insulation in the case of smaller cross sections
white
Cross section range:
0.08-0.2 mm2
0.25-0.5 mm2
gray
ISH 1,5/0,2
ISH 1,5/0,5
32 06 13 1
30 31 03 4
50
50
(4) Screwdriver, for
actuating the tension spring
SZF 0 - 0,4 x 2,5
12 04 50 4
10
white
ZBF 4:UNPRINTED
08 08 58 7
10
white
ZB 4:UNPRINTED
08 05 00 1
10
(5) Zack strip, flat, for
labeling the outer marker grooves
(6) Zack strip, 10-section, for
labeling in the terminal center
and on the plug-in bridges
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7.5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current/ cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulation material group
–/–
Capacity connection
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inflammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nom. voltage / nom. current / conduc. sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
Phoenix Contact page 3 of 10
4.2 / 72 / 2.2
36.5 / 44
–
6/3
III / I
0.25 - 1.5
0.25 - 1.5
0.5
10
A1
PA
V0
–
–
Four-Conductor Spring Cage
Terminal Block
ST 2,5-QUATTRO
(IEC)
[mm2]
rigid
solid
flexible
stranded
AWG
I
[A]
U
[V]
IEC 60 947-7-1
0.08-4
0.08-2.5
28-12 28*
800
EN 50 019**
0.08-4
0.08-2.5
28-12 24/21* 550
** EU certificate of design approval no.: KEMA 00ATEX2052U 1)
1) For installation notes and the use of accessories for EEx e applications
see Catalog CLIPLINE.
* The max. load current must not be exceeded by the total current of all connected
conductors.
u P F KEMA
Technical data
Spring cage terminal block,
for mounting on 3
Type
Order No.
Pcs.
Pkt.
ST 2,5-QUATTRO
ST 2,5-QUATTRO BU
30 31 30 6
30 31 31 9
50
50
gray
D-ST 2,5-QUATTRO
30 30 51 4
50
gray
DS-ST 2,5
30 36 60 2
10
ISH 2,5/0,2
ISH 2,5/0,5
ISH 2,5/1
30 02 84 3
30 02 85 6
30 02 86 9
50
50
50
30 30 16 1
30 30 17 4
30 30 18 7
30 30 19 0
30 30 21 3
30 30 22 6
50
50
50
50
10
10
gray
blue
terminal width 5.2
terminal width 5.2
(1) End cover
(2) Segment cover, for covering
projecting terminal segments
(3) Insulating stop sleeve, prevents unintentional clamping
of the insulation in the case of smaller cross sections
white
Cross section range:
0.08-0.2 mm2
0.25-0.5 mm2
gray
black
0.75-1 mm2
(4) Plug-in bridge, for
cross-connections in the
terminal center
2-pos.
3-pos.
4-pos.
5-pos.
10-pos.
20-pos.
FBS 2-5
FBS 3-5
FBS 4-5
FBS 5-5
FBS 10-5
FBS 20-5
Imax.: 24 A
24 A
24 A
24 A
24 A
24 A
(5) Partition plate, for
visual and electrical separation
of terminal groups, 2 mm thick
ATP ST-QUATTRO
30 30 81 5
50
(6) Test adapter, for 4 mm ∅ test connector PS
and 4 mm ∅ safety test connectors,
making contact in the bridge shaft
PAI 4
30 30 92 5
10
MPS-RD
02 01 55 3
10
RPS
02 01 64 7
10
WST 2,5
30 30 94 1
50
SZF 1 - 0,6 x 3,5
12 04 51 7
10
white
ZBF 5:UNPRINTED
08 08 64 2
10
white
ZB 5:UNPRINTED
10 50 00 4
10
(7) 2.3 mm ∅ test connector 1), consisting of
metal part and red insulating sleeve
(8) Reducing plug
(9) Warning cover, for the
operating shafts of the “mini-spring”
ST spring cage terminal blocks
(10) Screwdriver, for
actuating the tension spring
(11) Zack strip, flat, for
labeling the outer marker grooves
(12) Zack strip, 10-section, for
labeling in the terminal center
and on the plug-in bridges
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7.5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current/ cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulation material group
–/–
Capacity connection
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inflammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nom. voltage / nom. current / conduc. sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
1
) Further colors are available on request.
Phoenix Contact page 4 of 10
5.2 / 72 / 2.2
36.5 / 44
28 / 4
8/3
III / I
0.25 - 2.5
0.25 - 2.5
0.5
10
A3
PA
V0
600 / 20 / 26 - 12
600 / 20 / 26 - 12
Four-Conductor Spring Cage
Ground Terminal Block
ST 2,5-QUATTRO-PE
(IEC)
[mm2]
rigid
solid
flexible
stranded
AWG
IEC 60 947-7-2
0.08-4
0.08-2.5
28-12
EN 50 019*
0.08-4
0.08-2.5
28-12
* EU certificate of design approval no.: KEMA 00ATEX2052U 1)
1) For installation notes and the use of accessories for EEx e applications
see Catalog CLIPLINE.
The current carrying capacity of the mounting rails should be observed.
u P F KEMA
Technical data
Spring cage ground terminal block,
green-yellow
for mounting on 3
terminal width 5.2
Type
Order No.
Pcs.
Pkt.
ST 2,5-QUATTRO-PE
30 31 32 2
50
(1) End cover
gray
D-ST 2,5-QUATTRO
30 30 51 4
50
(2) Segment cover, for covering
projecting terminal segments
gray
DS-ST 2,5
30 36 60 2
10
(3) Insulating stop sleeve, prevents unintentional clamping
of the insulation in the case of smaller cross sections
white
Cross section range:
0.08-0.2 mm2
gray
0.25-0.5 mm2
black
0.75-1 mm2
ISH 2,5/0,2
ISH 2,5/0,5
ISH 2,5/1
30 02 84 3
30 02 85 6
30 02 86 9
50
50
50
(4) Screwdriver, for
actuating the tension spring
SZF 1 - 0,6 x 3,5
12 04 51 7
10
white
ZBF 5:UNPRINTED
08 08 64 2
10
white
ZB 5:UNPRINTED
10 50 00 4
10
(5) Zack strip, flat, for
labeling the outer marker grooves
(6) Zack strip, 10-section, for
labeling in the terminal center
and on the plug-in bridges
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7.5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current/ cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulation material group
–/–
Capacity connection
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inflammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nom. voltage / nom. current / conduc. sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
Phoenix Contact page 5 of 10
5.2 / 72 / 2.2
36.5 / 44
–
8/3
III / I
0.25 - 2.5
0.25 - 2.5
0.5
10
A3
PA
V0
– / – / 26 - 12
– / – / 26 - 12
Four-Conductor Spring Cage
Terminal Blocks
ST 4-QUATTRO
(IEC)
[mm2]
rigid
solid
flexible
stranded
AWG
I
[A]
U
[V]
IEC 60 947-7-1
0.08-6
0.08-4
28-10 40*
800
EN 50 019**
0.08-6
0.08-4
28-10 34/25* 550
** EU certificate of design approval no.: KEMA 00ATEX2129U 1)
1) For installation notes and the use of accessories for EEx e applications
see Catalog CLIPLINE.
* The max. load current must not be exceeded by the total current of all connected
conductors.
u P F KEMA
Technical data
Spring cage terminal block,
for mounting on 3
gray
blue
terminal width 6.2
terminal width 6.2
Type
Order No.
Pcs.
Pkt.
ST 4-QUATTRO
ST 4-QUATTRO BU
30 31 44 5
30 31 45 8
50
50
(1) End cover
gray
D-ST 4-QUATTRO
30 30 52 7
50
(2) Segment cover, for covering
projecting terminal segments
gray
DS-ST 4
30 36 61 5
10
ISH 4/0,5
ISH 4/1
30 02 88 5
30 02 89 8
50
50
30 30 33 6
30 30 24 2
30 30 25 5
30 30 34 9
30 30 27 1
30 30 36 5
50
50
50
50
10
10
(3) Insulating stop sleeve, prevents unintentional clamping
of the insulation in the case of smaller cross sections
gray
Cross section range:
0.25-0.5 mm2
black
0.75-1 mm2
(4) Plug-in bridge, for
cross-connections in the
terminal center
2-pos.
3-pos.
4-pos.
5-pos.
10-pos.
20-pos.
FBS 2-6
FBS 3-6
FBS 4-6
FBS 5-6
FBS 10-6
FBS 20-6
Imax.: 32 A
32 A
32 A
32 A
32 A
32 A
(5) Partition plate, for
visual and electrical separation
of terminal groups, 2 mm thick
ATP ST-QUATTRO
30 30 81 5
50
(6) Test adapter, for 4 mm ∅ test connector PS
and 4 mm ∅ safety test connectors,
making contact in the bridge shaft
PAI 4
30 30 92 5
10
MPS-RD
02 01 55 3
10
RPS
02 01 64 7
10
WST 4
30 30 95 4
50
SZF 1 - 0,6 x 3,5
12 04 51 7
10
white
ZBF 6:UNPRINTED
08 08 71 0
10
white
ZB 6:UNPRINTED
10 51 00 3
10
(7) 2.3 mm ∅ test connector 1), consisting of
metal part and red insulating sleeve
(8) Reducing plug
(9) Warning cover, for the
operating shafts of the “mini-spring”
ST spring cage terminal blocks
(10) Screwdriver, for
actuating the tension spring
(11) Zack strip, flat, for
labeling the outer marker grooves
(12) Zack strip, 10-section, for
labeling in the terminal center
and on the plug-in bridges
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7.5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current/ cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulation material group
–/–
Capacity connection
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inflammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nom. voltage / nom. current / conduc. sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
1
) Further colors are available on request.
Phoenix Contact page 6 of 10
6.2 / 87 / 2.2
36.5 / 44
40 / 6
8/3
III / I
0.25 - 4
0.25 - 4
0.5 - 1
10
A4
PA
V0
–
–
Four-Conductor Spring Cage
Ground Terminal Block
ST 4-QUATTRO-PE
(IEC)
[mm2]
rigid
solid
flexible
stranded
AWG
IEC 60 947-7-2
0.08-6
0.08-4
28-10
EN 50 019*
0,08-6
0,08-4
28-10
* EU certificate of design approval no.: KEMA 00ATEX2129U 1)
1) For installation notes and the use of accessories for EEx e applications
see Catalog CLIPLINE.
The current carrying capacity of the mounting rails should be observed.
u P F KEMA
Technical data
Spring cage ground terminal block,
green-yellow
for mounting on 3
terminal width 6.2
Type
Order No.
Pcs.
Pkt.
ST 4-QUATTRO-PE
30 31 46 1
50
(1) End cover
gray
D-ST 4-QUATTRO
30 30 52 7
50
(2) Segment cover, for covering
projecting terminal segments
gray
DS-ST 4
30 36 61 5
10
(3) Insulating stop sleeve, prevents unintentional clamping
of the insulation in the case of smaller cross sections
gray
Cross section range:
0.25-0.5 mm2
black
0.75-1 mm2
ISH 4/0,5
ISH 4/1
30 02 88 5
30 02 89 8
50
50
(4) Screwdriver, for
actuating the tension spring
SZF 1 - 0,6 x 3,5
12 04 51 7
10
white
ZBF 6:UNPRINTED
08 08 71 0
10
white
ZB 6:UNPRINTED
10 51 00 3
10
(5) Zack strip, flat, for
labeling the outer marker grooves
(6) Zack strip, 10-section, for
labeling in the terminal center
and on the plug-in bridges
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7.5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current/ cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulation material group
–/–
Capacity connection
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inflammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nom. voltage / nom. current / conduc. sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
Phoenix Contact page 7 of 10
6.2 / 87 / 2.2
36.5 / 44
–
8/3
III / I
0.25 - 4
0.25 - 4
0.5 - 1
10
A3
PA
V0
–
–
Four-Conductor Spring Cage
Terminal Block
ST 1,5-QUATTRO-U
(IEC)
[mm2]
rigid
solid
flexible
stranded
AWG
I
[A]
U
[V]
IEC 60 947-7-1
0.08-1.5
0.08-1.5
28-16 17.5* 500
* The max. load current must not be exceeded by the total current of all connected
conductors.
Technical data
Spring cage terminal block,
for mounting on 3
Type
Order No.
Pcs.
Pkt.
ST 1,5-QUATTRO-U
30 38 60 0
50
gray
D-ST 2,5-QUATTRO
30 30 51 4
50
gray
DS-ST 2,5
30 36 60 2
10
ISH 2,5/0,2
ISH 2,5/0,5
30 02 84 3
30 02 85 6
50
50
30 30 11 6
30 30 12 9
30 30 13 2
30 30 14 5
30 30 15 8
30 30 35 2
50
50
50
50
10
10
gray
terminal width 4.2
(1) End cover
(2) Segment cover, for covering
projecting terminal segments
(3) Insulating stop sleeve, prevents unintentional clamping
of the insulation in the case of smaller cross sections
white
Cross section range:
0.08-0.2 mm2
gray
0.25-0.5 mm2
(4) Plug-in bridge, for
cross-connections in the
terminal center
2-pos.
3-pos.
4-pos.
5-pos.
10-pos.
20-pos.
FBS 2-4
FBS 3-4
FBS 4-4
FBS 5-4
FBS 10-4
FBS 20-4
Imax.: 17,5 A
17,5 A
17,5 A
17,5 A
17,5 A
17,5 A
(5) Partition plate, for
visual and electrical separation
of terminal groups, 2 mm thick
ATP ST-QUATTRO
30 30 81 5
50
(6) Test adapter, for 4 mm ∅ test connector PS
and 4 mm ∅ safety test connectors,
making contact in the bridge shaft
PAI 4
30 30 92 5
10
MPS-RD
02 01 55 3
10
RPS
02 01 64 7
10
WST 1,5
30 30 95 8
50
SZF 1 - 0,4 x 2,5
12 04 50 4
10
white
ZBF 4:UNPRINTED
08 08 58 7
10
white
ZB 4:UNPRINTED
08 05 00 1
10
(7) 2.3 mm ∅ test connector 1), consisting of
metal part and red insulating sleeve
(8) Reducing plug
(9) Warning cover, for the
operating shafts of the “mini-spring”
ST spring cage terminal blocks
(10) Screwdriver, for
actuating the tension spring
(11) Zack strip, flat, for
labeling the outer marker grooves
(12) Zack strip, 10-section, for
labeling in the terminal center
and on the plug-in bridges
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7.5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current/ cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulation material group
–/–
Capacity connection
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inflammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nom. voltage / nom. current / conduc. sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
1
) Further colors are available on request.
Phoenix Contact page 8 of 10
4.2 / 72 / 2.2
36.5 / 44
17.5 / 1.5
6/3
III / I
0.25 - 2.5
0.25 - 2.5
0.5
10
A1
PA
V0
–
–
Four-Conductor Spring Cage
Terminal Block
ST 2,5-QUATTRO-U
(IEC)
[mm2]
rigid
solid
flexible
stranded
AWG
I
[A]
U
[V]
IEC 60 947-7-1
0.08-4
0.08-2.5
28-12 28*
800
* The max. load current must not be exceeded by the total current of all connected
conductors.
Technical data
Spring cage terminal block,
for mounting on 3
Type
Order No.
Pcs.
Pkt.
ST 2,5-QUATTRO-U
30 31 63 6
50
gray
D-ST 2,5-QUATTRO
30 30 51 4
50
gray
DS-ST 2,5
30 36 60 2
10
ISH 2,5/0,2
ISH 2,5/0,5
ISH 2,5/1
30 02 84 3
30 02 85 6
30 02 86 9
50
50
50
30 30 16 1
30 30 17 4
30 30 18 7
30 30 19 0
30 30 21 3
30 30 22 6
50
50
50
50
10
10
gray
terminal width 5.2
(1) End cover
(2) Segment cover, for covering
projecting terminal segments
(3) Insulating stop sleeve, prevents unintentional clamping
of the insulation in the case of smaller cross sections
white
Cross section range:
0.08-0.2 mm2
gray
0.25-0.5 mm2
black
0.75-1 mm2
(4) Plug-in bridge, for
cross-connections in the
terminal center
2-pos.
3-pos.
4-pos.
5-pos.
10-pos.
20-pos.
FBS 2-5
FBS 3-5
FBS 4-5
FBS 5-5
FBS 10-5
FBS 20-5
Imax.: 24 A
24 A
24 A
24 A
24 A
24 A
(5) Partition plate, for
visual and electrical separation
of terminal groups, 2 mm thick
ATP ST-QUATTRO
30 30 81 5
50
(6) Test adapter, for 4 mm ∅ test connector PS
and 4 mm ∅ safety test connectors,
making contact in the bridge shaft
PAI 4
30 30 92 5
10
MPS-RD
02 01 55 3
10
RPS
02 01 64 7
10
WST 2,5
30 30 94 1
50
SZF 1 - 0,6 x 3,5
12 04 51 7
10
white
ZBF 5:UNPRINTED
08 08 64 2
10
white
ZB 5:UNPRINTED
10 50 00 4
10
(7) 2.3 mm ∅ test connector 1), consisting of
metal part and red insulating sleeve
(8) Reducing plug
(9) Warning cover, for the
operating shafts of the “mini-spring”
ST spring cage terminal blocks
(10) Screwdriver, for
actuating the tension spring
(11) Zack strip, flat, for
labeling the outer marker grooves
(12) Zack strip, 10-section, for
labeling in the terminal center
and on the plug-in bridges
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7.5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current/ cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulation material group
–/–
Capacity connection
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inflammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nom. voltage / nom. current / conduc. sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
1
) Further colors are available on request.
Phoenix Contact page 9 of 10
5.2 / 72 / 2.2
36.5 / 44
28 / 4
8/3
III / I
0.25 - 2.5
0.25 - 2.5
0.5
10
A3
PA
V0
–
–
Four-Conductor Spring Cage
Terminal Block
ST 4-QUATTRO-U
(IEC)
[mm2]
rigid
solid
flexible
stranded
AWG
I
[A]
U
[V]
IEC 60 947-7-1
0.08-4
0.08-2.5
28-12 28*
800
* The max. load current must not be exceeded by the total current of all connected
conductors.
Technical data
Spring cage terminal block,
for mounting on 3
Type
Order No.
Pcs.
Pkt.
ST 4-QUATTRO-U
30 38 63 9
50
gray
D-ST 4-QUATTRO
30 30 52 7
50
gray
DS-ST 4
30 36 61 5
10
ISH 4/0,5
ISH 4/1
30 02 88 5
30 02 89 8
50
50
30 30 33 6
30 30 24 2
30 30 25 5
30 30 34 9
30 30 27 1
30 30 36 5
50
50
50
50
10
10
gray
terminal width 6.2
(3) Insulating stop sleeve, prevents unintentional clamping
of the insulation in the case of smaller cross sections
gray
Cross section range:
0.25-0.5 mm2
black
0.75-1 mm2
(4) Plug-in bridge, for
cross-connections in the
terminal center
2-pos.
3-pos.
4-pos.
5-pos.
10-pos.
20-pos.
FBS 2-6
FBS 3-6
FBS 4-6
FBS 5-6
FBS 10-6
FBS 20-6
Imax.: 32 A
32 A
32 A
32 A
32 A
32 A
(5) Partition plate, for
visual and electrical separation
of terminal groups, 2 mm thick
ATP ST-QUATTRO
30 30 81 5
50
(6) Test adapter, for 4 mm ∅ test connector PS
and 4 mm ∅ safety test connectors,
making contact in the bridge shaft
PAI 4
30 30 92 5
10
MPS-RD
02 01 55 3
10
RPS
02 01 64 7
10
WST 4
30 30 95 4
50
SZF 1 - 0,6 x 3,5
12 04 51 7
10
white
ZBF 6:UNPRINTED
08 08 71 0
10
white
ZB 6:UNPRINTED
10 51 00 3
10
(7) 2.3 mm ∅ test connector 1), consisting of
metal part and red insulating sleeve
(8) Reducing plug
(9) Warning cover, for the
operating shafts of the “mini-spring”
ST spring cage terminal blocks
(10) Screwdriver, for
actuating the tension spring
(11) Zack strip, flat, for
labeling the outer marker grooves
(12) Zack strip, 10-section, for
labeling in the terminal center
and on the plug-in bridges
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7.5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current/ cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulation material group
–/–
Capacity connection
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inflammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nom. voltage / nom. current / conduc. sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
1
) Further colors are available on request.
Phoenix Contact page 10 of 10
6.2 / 87 / 2.2
36.5 / 44
40 / 6
8/3
III / I
0.25 - 4
0.25 - 4
0.5 - 1
10
A4
PA
V0
–
–
TNR 5124910/15.05.2003-02
(2) Segment cover, for covering
projecting terminal segments
Phoenix Contact 2003
(1) End cover