co
s.
nt
po
ne
The Þelds of application for the pluggable ST-COMBI
spring-cage terminal blocks has been added to with
solutions for larger conductor cross sections and a
higher nominal current.
The product range includes both feed-through terminal
blocks with one cable entry and four-wire terminal
blocks with two cable entries. Ground terminal blocks
with the same shape and the same pitch are available
for the various base terminal blocks. Contact is made by
simply snapping the terminal block onto the mounting
rail.
The corresponding plug types SP 4... can either be
ordered ready assembled with 1-15 positions, or the
individual components can be ordered for applicationspeciÞc assembly.
At every connection point of a conductor to the base
terminal block or connector there is a testing facility for
a 2.3 mm test plug.
m
ST-COMBI 4 mm2 Pluggable
Spring-Cage Terminal Blocks
om
Strain relief PZ
Strain reliefs are available for the plugs which, as an
option, can be snapped on the SP 4 ... connectors
externally.
on
l
in
ec
PZ/PRZ snap-lock Þtting
The PR... snap-lock Þtting is snapped into the outside of
the plug housing as an option and hooks onto the
terminal block housing when the plug is snapped on.
PRZ can be used when an application requires strain
relief and a snap-lock Þtting. PRZ is also snapped into
the plug housing as an option and offers a combination
of functions in a single component.
PC coding option
SpeciÞc connector positions can be deÞned for all the
base terminal blocks using the PC coding star. To do
this, the individual branches of the coding star are
inserted at the coding position in the base terminal
block and the coding lug is removed at the
corresponding point of the connector.
Shield connection PSH
PSH... provides a solution for the connection of
shielded conductors. PSH... is snapped into PZ... or
PRZ after the terminal blocks have been wired and is
then permanently secured using a cable tie. The PSH
connecting cable is connected to a connector conductor
and makes contact directly with the terminal block when
inserted.
Phoenix Contact GmbH & Co. KG • 32823 Blomberg, Germany
Phone +49 52 35 3-00 • Fax +49 52 35 3-4 12 00 • www.phoenixcontact.com
Local Contact: www.phoenixcontact.com/salesnetwork
Pluggable
Spring-Cage Terminal Blocks
ST 4/ 1P
AWG
I
[A]
U
[V]
0.08-4
28-10
30*
800
IEC 61 984
0.08-6
* Derating curve see page 9.
Technical data
Spring-cage terminal block,
for mounting on 3
terminal width 6.2
terminal width 6.2
gray
Insulating stop sleeve, prevents
unintentional clamping of the insulation
in the case of smaller cross sections
Cross section range:
gray
black
ST 4/ 1P
ST 4/ 1P BU
30 42 71 9
30 42 87 4
50
50
D-ST 4
30 30 42 0
50
0.25-0.5 mm2
0.75-1 mm2
ISH 4/0,5
ISH 4/1
2-pos.
3-pos.
4-pos.
5-pos.
10-pos.
20-pos.
FBS 2-6
FBS 3-6
FBS 4-6
FBS 5-6
FBS 10-6
FBS 20-6
50
50
30 30 33 6
30 30 24 2
30 30 25 5
30 30 34 9
30 30 27 1
30 30 36 5
50
50
50
50
10
10
30 30 72 1
50
PAI 4
30 30 92 5
10
MPS-RD
02 01 55 3
10
PS-6
30 30 99 6
10
PC
30 40 58 8
50
WST 4
30 30 95 4
50
SZF 1 - 0,6 x 3,5
12 04 51 7
10
white
ZBF 6:UNBEDRUCKT
08 08 71 0
10
white
ZB 6:UNBEDRUCKT
10 51 00 3
10
ATP-ST 4
Coding star,
with 4 coding pins,
for mounting in all base terminal blocks
in
ec
Warning cover, for the
actuating ducts of the "mini-spring"
ST spring-cage terminal blocks
om
2.3 mm ∅ test plug 1), consisting of
metal part and red insulating sleeve
Modular test plug, labeling with ZBF 6
po
Test adapter, for 4 mm ∅ PS test plug
and 4 mm ∅ safety test plugs,
makes contact in the bridge shaft
Screwdriver, for
actuating the tension spring
on
l
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7,5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current / cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulating material group
–/–
Connection capacity
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inßammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nominal voltage / current / conductor sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
1
Imax.: 32 A
32 A
32 A
32 A
32 A
32 A
ne
Partition plate,
for visual and electrical separation
of terminal groups, 2 mm thick
Zack strip, 10-section, for
labeling in the terminal center
Pcs.
Pkt.
30 02 88 5
30 02 89 8
Plug-in bridge, for
cross bridging in the terminal
center
Zack strip, ßat, for labeling
the center and outer marker
grooves
Order No.
nt
Cover
gray
blue
Type
m
ßexible
stranded
co
rigid
solid
s.
(IEC)
[mm2]
) Further colors on request.
Phoenix Contact page 2 of 10
6.2 / 55.8 / 2.2
36.5 / 44
30 / 6
6/3
III / I
0.25 - 4
0.25 - 4
0.5 - 1
10
A4
PA
V0
Applied for
Applied for
Pluggable
Spring-Cage Ground Terminal Blocks
ST 4/ 1P-PE
(IEC)
[mm2]
rigid
solid
ßexible
stranded
AWG
IEC 61 984
0.08-6
0.08-4
28-10
Observe the current carrying capacity of the mounting rails.
gray
Insulating stop sleeve, prevents
unintentional clamping of the insulation
in the case of smaller cross sections
Cross section range:
gray
black
50
D-ST 4
30 30 42 0
50
0.25-0.5 mm2
0.75-1 mm2
ISH 4/0,5
ISH 4/1
2-pos.
3-pos.
4-pos.
5-pos.
10-pos.
20-pos.
FBS 2-6
FBS 3-6
FBS 4-6
FBS 5-6
FBS 10-6
FBS 20-6
50
50
30 30 33 6
30 30 24 2
30 30 25 5
30 30 34 9
30 30 27 1
30 30 36 5
50
50
50
50
10
10
30 30 72 1
50
PC
30 40 58 8
50
WST 4
30 30 95 4
50
SZF 1 - 0,6 x 3,5
12 04 51 7
10
white
ZBF 6:UNBEDRUCKT
08 08 71 0
10
white
ZB 6:UNBEDRUCKT
10 51 00 3
10
ne
Partition plate,
for visual and electrical separation
of terminal groups, 2 mm thick
ATP-ST 4
Screwdriver, for
actuating the tension spring
in
ec
om
Warning cover, for the
actuating ducts of the "mini-spring"
ST spring-cage terminal blocks
po
Coding star,
with 4 coding pins,
for mounting in all base terminal blocks
Zack strip, 10-section, for
labeling in the terminal center
30 42 72 2
30 02 88 5
30 02 89 8
Plug-in bridge, for
cross bridging in the terminal
center
Zack strip, ßat, for labeling
the center and outer marker
grooves
ST 4/ 1P-PE
m
terminal width 6.2
Pcs.
Pkt.
nt
Cover
greenyellow
Order No.
s.
Spring-cage terminal block,
for mounting on 3
Type
co
Technical data
on
l
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7,5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current / cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulating material group
–/–
Connection capacity
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inßammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nominal voltage / current / conductor sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
Phoenix Contact page 3 of 10
6.2 / 55.8 / 2.2
36.5 / 44
–
6/3
III / I
0.25 - 4
0.25 - 4
0.5 - 1
10
A4
PA
V0
Applied for
Applied for
Pluggable
Spring-Cage Terminal Blocks
ST 4-QUATTRO/ 2P
(IEC)
[mm2]
rigid
solid
ßexible
stranded
I
[A]
AWG
U
[V]
terminal width 6.2
terminal width 6.2
gray
Insulating stop sleeve, prevents
unintentional clamping of the insulation
in the case of smaller cross sections
Cross section range:
gray
black
Plug-in bridge, for
cross bridging in the terminal
center
30 43 74 7
50
30 43 75 0
50
30 02 88 5
30 02 89 8
50
50
Imax.: 32 A
32 A
32 A
32 A
32 A
32 A
30 30 33 6
30 30 24 2
30 30 25 5
30 30 34 9
30 30 27 1
30 30 36 5
50
50
50
50
10
10
ATP-ST QUATTRO
30 30 81 5
50
PAI 4
30 30 92 5
10
MPS-RD
02 01 55 3
10
PS-6
30 30 99 6
10
PC
30 40 58 8
50
WST 4
30 30 95 4
50
ISH 4/0,5
ISH 4/1
2-pos.
3-pos.
4-pos.
5-pos.
10-pos.
20-pos.
FBS 2-6
FBS 3-6
FBS 4-6
FBS 5-6
FBS 10-6
FBS 20-6
po
Warning cover, for the
actuating ducts of the "mini-spring"
ST spring-cage terminal blocks
Screwdriver, for
actuating the tension spring
on
l
D-ST 4-QUATTRO/ 2P
0.25-0.5 mm2
0.75-1 mm2
in
ec
Coding star,
with 4 coding pins,
for mounting in all base terminal blocks
50
50
DS-ST 4/P
om
2.3 mm ∅ test plug 1), consisting of
metal part and red insulating sleeve
Modular test plug, labeling with ZBF 6
30 42 84 5
30 42 86 1
gray
Partition plate,
for visual and electrical separation
of terminal groups, 2 mm thick
Test adapter, for 4 mm ∅ PS test plug
and 4 mm ∅ safety test plugs,
makes contact in the bridge shaft
ST 4-QUATTRO/ 2P
ST 4-QUATTRO/ 2P BU
nt
End cover segment, serves for covering
multi-conductor terminal blocks when twoconductor terminal blocks are aligned
Pcs.
Pkt.
ne
Cover
gray
blue
Order No.
m
Spring-cage terminal block,
for mounting on 3
Type
co
Technical data
s.
IEC 61 984
0.08-6
0.08-4
28-10 30 1)* 800
1) The max. load current must not be exceeded by the total current of all connected
conductors.
* Derating curve see page 9.
SZF 1 - 0,6 x 3,5
12 04 51 7
10
Zack strip, ßat, for center and external labeling
white
ZBF 6:UNBEDRUCKT
08 08 71 0
10
Zack strip, 10-section, for labeling in the terminal center
white
ZB 6:UNBEDRUCKT
10 51 00 3
10
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7,5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current / cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulating material group
–/–
Connection capacity
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inßammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nominal voltage / current / conductor sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
1
) Further colors on request.
Phoenix Contact page 4 of 10
6.2 / 97.3 / 2.2
36.5 / 44
30 / 6
6/3
III / I
0.25 - 4
0.25 - 4
0.5 - 1
10
A4
PA
V0
Applied for
Applied for
Pluggable
Spring-Cage Ground Terminal Blocks
ST 4-QUATTRO/ 2P-PE
(IEC)
[mm2]
rigid
solid
ßexible
stranded
AWG
IEC 61 984
0.08-6
0.08-4
28-10
Observe the current carrying capacity of the mounting rails.
gray
Insulating stop sleeve, prevents
unintentional clamping of the insulation
in the case of smaller cross sections
Cross section range:
gray
black
Plug-in bridge, for
cross bridging in the terminal
center
Zack strip, ßat, for labeling
the center and outer marker
grooves
50
30 43 75 0
50
30 02 88 5
30 02 89 8
50
50
30 30 33 6
30 30 24 2
30 30 25 5
30 30 34 9
30 30 27 1
30 30 36 5
50
50
50
50
10
10
ATP-ST QUATTRO
30 30 81 5
50
PC
30 40 58 8
50
WST 4
30 30 95 4
50
SZF 1 - 0,6 x 3,5
12 04 51 7
10
ZBF 6:UNBEDRUCKT
08 08 71 0
10
ZB 6:UNBEDRUCKT
10 51 00 3
10
ISH 4/0,5
ISH 4/1
2-pos.
3-pos.
4-pos.
5-pos.
10-pos.
20-pos.
FBS 2-6
FBS 3-6
FBS 4-6
FBS 5-6
FBS 10-6
FBS 20-6
po
white
on
l
Zack strip, 10-section, for
labeling in the terminal center
30 43 74 7
0.25-0.5 mm2
0.75-1 mm2
in
ec
Screwdriver, for
actuating the tension spring
D-ST 4-QUATTRO/ 2P
DS-ST 4/P
om
Warning cover, for the
actuating ducts of the "mini-spring"
ST spring-cage terminal blocks
50
gray
Partition plate,
for visual and electrical separation
of terminal groups, 2 mm thick
Coding star,
with 4 coding pins,
for mounting in all base terminal blocks
30 42 85 8
nt
End cover segment, serves for covering
multi-conductor terminal blocks when twoconductor terminal blocks are aligned
ST 4-QUATTRO/ 2P-PE
white
m
terminal width 6.2
Pcs.
Pkt.
ne
Cover
greenyellow
Order No.
co
Spring-cage terminal block,
for mounting on 3
Type
s.
Technical data
Dimensions
Width / length / end cover width
[mm]
Height (NS 35/7,5 / NS 35/15)
[mm]
Technical data in accordance with IEC/ DIN VDE
Maximum load current / cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulating material group
–/–
Connection capacity
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inßammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nominal voltage / current / conductor sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
Phoenix Contact page 5 of 10
6.2 / 97.3 / 2.2
36.5 / 44
–
6/3
III / I
0.25 - 4
0.25 - 4
0.5 - 1
10
A4
PA
V0
Applied for
Applied for
ST-COMBI Plugs
SP 4
AWG
I
[A]
U
[V]
0.08-4
28-10
30*
800
Technical data
0.25-0.5 mm2
0.75-1 mm2
Strain relief,
Snap-lock Þtting and
strain relief for all plugs
2-pos.
orange
orange
1-pos.
2-pos.
2-pos.
in
ec
orange
Shielding, for mounting on
PZ/... and PRZ, for shielded
conductors with
50
50
50
50
50
25
25
25
25
25
10
10
10
10
10
30 02 88 5
30 02 89 8
50
50
PZ/2
30 40 62 7
50
PR
PR/2
30 40 55 9
30 40 63 0
50
50
PRZ
30 40 61 4
50
3-6 mm ∅
5-10 mm ∅
PSH 3-6
PSH 5-10
30 40 59 1
30 40 60 1
50
50
white
ZBF 6:UNBEDRUCKT
08 08 71 0
10
on
l
Zack strip, ßat,
for labeling the outer marker
grooves
30 42 88 7
30 42 89 0
30 42 90 0
30 42 92 6
30 42 93 9
30 42 94 2
30 42 95 5
30 42 96 8
30 42 97 1
30 42 98 4
30 42 99 7
30 43 00 6
30 43 37 8
30 43 72 1
30 43 73 4
ISH 4/0,5
ISH 4/1
om
Snap-lock Þtting,
for all plugs
black
SP 4/1
SP 4/2
SP 4/3
SP 4/4
SP 4/5
SP 4/6
SP 4/7
SP 4/8
SP 4/9
SP 4/10
SP 4/11
SP 4/12
SP 4/13
SP 4/14
SP 4/15
nt
Insulating stop sleeve, prevents
unintentional clamping of the insulation
in the case of smaller cross sections
Cross section range:
gray
black
1-pos.
2-pos.
3-pos.
4-pos.
5-pos.
6-pos.
7-pos.
8-pos.
9-pos.
10-pos.
11-pos.
12-pos.
13-pos.
14-pos.
15-pos.
Pcs.
Pkt.
ne
gray
gray
gray
gray
gray
gray
gray
gray
gray
gray
gray
gray
gray
gray
gray
Order No.
po
ST-COMBI plug, single, not
bridgeable, 6.2 mm wide
Type
m
Connection data
0.08-6
* Derating curve see page 9.
ßexible
stranded
co
rigid
solid
s.
(IEC)
[mm2]
Technical data in accordance with IEC/ DIN VDE
Maximum load current / cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulating material group
–/–
Connection capacity
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inßammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nominal voltage / current / conductor sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
Phoenix Contact page 6 of 10
30 / 6
8/3
III / I
0.25 - 4
0.25 - 4
0.5 - 1
10
A4
PA
V0
Applied for
Applied for
ST-COMBI Plugs for Self-Assembly
co
m
Structure of a plug
For each multiple-position plug, a left element (at the
beginning of the plug) and a right element (at the end of
the plug) is required. How many middle elements need
to be inserted depends on the number of positions of
the desired plug. The individual elements are connected
by pushing them together and are held by the
engagement pins.
Example for the structure
of a 6-position plug:
nt
s.
Withden
Mit
theselbstkonfektionierbaren
ST-COMBI plugs for self-assembly,
ST-COMBI-Steckern
we offer a
ist für jede
solution
for Aufgabenstellung
every task and it can
einebeLösung
implemented
vorhanden,
by the
die vom
user
himself.
Anwender
The plug
selbst
is assembled
realisiert werden
directlykann.
on site
Der
by
Stecker wird
snapping
together
hierbeione-position
direkt vor Ort
plug
anwendungsgerecht
elements.
aus einpoligen Steckerelementen zusammengerastet.
For the existing SP 4… plug a one-position base
version
Für die vorhandenen
is available in Steckertypen
gray, blue andSP
green-yellow:
2,5…,
SPB 2,5… und SPDB 2,5… stehen jeweils einpolige
Grundvarianten in den Farben grau, blau, grün-gelb zur
Verfügung:
SP 4/1-L
om
po
ne
left element
SP…4/1-L
left side: smooth
right side: open
on
l
in
ec
middle element
SP…4/1-M
left side: engagement pin
right side: open
right element
SP…4/1-R
left side: engagement pin
right side: end cover
In this view, the open side of the plug is on the right.
The different color versions can be combined with each
other in any order.
Phoenix Contact page 7 of 10
SP 4/1-M
SP 4/1-M BU
SP 4/1-R GNYE
Plugs for Self-Assembly
SP 4/1…
(IEC)
[mm2]
rigid
solid
Connection data
0.08-6
* Derating curve see page 9.
ßexible
stranded
AWG
I
[A]
U
[V]
0.08-4
28-10
30*
800
Technical data
Type
Order No.
Pcs.
Pkt.
gray
blue
green-yellow
SP 4/1-L
SP 4/1-L BU
SP 4/1-L GNYE
30 42 75 1
30 42 76 4
30 42 77 7
50
50
50
ST-COMBI plug, single, not
bridgeable, 6.2 mm wide,
middle element
gray
blue
green-yellow
SP 4/1-M
SP 4/1-M BU
SP 4/1-M GNYE
30 42 78 0
30 42 79 3
30 42 80 3
50
50
50
ST-COMBI plug, single, not
bridgeable, 6.2 mm wide,
right element
gray
blue
green-yellow
SP 4/1-R
SP 4/1-R BU
SP 4/1-R GNYE
30 42 81 6
30 42 82 9
30 42 83 2
50
50
50
black
2-pos.
PZ/2
30 40 62 7
50
orange
orange
1-pos.
2-pos.
PR
PR/2
30 40 55 9
30 40 63 0
50
50
orange
2-pos.
PRZ
30 40 61 4
50
PSH 3-6
PSH 5-10
30 40 59 1
30 40 60 1
50
50
ZBF 6:UNBEDRUCKT
08 08 71 0
10
Shielding, for mounting on
PZ/... and PRZ, for shielded
conductors with
Zack strip, for labeling the outer
marker grooves
3-6 mm∅
5-10 mm ∅
white
co
nt
ne
Snap-lock Þtting and
strain relief for all plugs
po
Snap-lock Þtting,
for all plugs
s.
Strain relief,
m
ST-COMBI plug, single, not
bridgeable, 6.2 mm wide,
left element
on
l
in
ec
om
Technical data in accordance with IEC/ DIN VDE
Maximum load current / cross section
[A] / [mm2]
Rated surge voltage / contamination class
[kV] / –
Surge voltage category / insulating material group
–/–
Connection capacity
Stranded with ferrule with plastic sleeve
[mm2]
Stranded with ferrule without plastic sleeve
[mm2]
Stranded with TWIN ferrule with plastic sleeve
[mm2]
Stripping length
[mm]
Internal cylindrical gauge (IEC 60 947-1)
Insulating material
Inßammability class in acc. with UL 94
Approval data (UL and CSA/CUL)
Nominal voltage / current / conductor sizes
UL: [V] / [A] / AWG
CSA/CUL: [V] / [A] / AWG
Phoenix Contact page 8 of 10
30 / 6
8/3
III / I
0.25 - 4
0.25 - 4
0.5 - 1
10
A4
PA
V0
Applied for
Applied for
Derating curve for ST-COMBITerminal Blocks
Max. load current [A]
! #
!
2-pos.
5-pos.
#
10-pos.
15-pos.
#
"
$
&
m
#
co
Ambient temperature[°C]
s.
Derating curve for ST 4/1P.
Is valid for all connector versions SP... .
nt
ne
!
2-pos.
5-pos.
#
po
10-pos.
15-pos.
om
#
in
ec
#
"
$
&
Ambient temperature [°C]
Derating curve for ST 4-QUATTRO/ 2P.
Is valid for all connector versions SP... .
on
l
Max. load current [A]
! #
Phoenix Contact page 9 of 10
Additional technical data
≤ 3.2 mV
≤ 45 K
Immunity to vibration (DIN EN 60 068-2-6:1996-05)
- Frequency
- Amplitude
- Acceleration
- Duration per axis
10-150 Hz
0.35 mm (10-60 Hz)
50 m/s2
2.5 h
Resistance to industrial atmospheres (DIN 50 018:1997-06)
- Level
- No. of cycles
KFW 1.0 S
2
Assessment of Þre risk
( DIN EN 60 695-2-11/VDE 0471 Part 2-11:2001-11)
- Test temperature
- Duration
960°C
30 s
TNR: 101429-00-en/15.03.04
Phoenix Contact 2004
on
l
in
ec
om
po
ne
nt
s.
co
m
Voltage drop over two terminal points (DIN EN 60 947-7-1/2)
Rise in temperature (DIN EN 60 947-7-1/2)
Phoenix Contact page 10 of 10