https://www.phoenixcontact.com/us/products/3042984
Plug - SP 4/10 - 3042984
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Plug, Connection method: Spring-cage connection, Number of positions: 10, Cross section: 0.08 mm² - 6 mm²,
AWG: 28 - 10, Width: 62 mm, Height: 41.5 mm, Color: gray
The illustration shows the 6-position
version
Product Features
Large-surface labeling option
Practical coding option
Tested for railway applications
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
42.96 g
Custom tariff number
85366990
Country of origin
Poland
Technical data
General
Number of levels
1
Number of connections
10
Nominal cross section
4 mm²
Color
gray
Insulating material
PA
Flammability rating according to UL 94
V0
Area of application
Railway industry
Mechanical engineering
Plant engineering
Maximum load current
32 A (with 6 mm² conductor cross section)
01/03/2016 Page 1 / 7
https://www.phoenixcontact.com/us/products/3042984
Plug - SP 4/10 - 3042984
Technical data
General
Rated surge voltage
8 kV
Pollution degree
3
Overvoltage category
III
Insulating material group
I
Connection in acc. with standard
IEC 61984
Maximum load current
32 A (with 6 mm² conductor cross section)
Nominal current IN
32 A
Nominal voltage UN
800 V
Open side panel
nein
Number of positions
10
Dimensions
Width
62 mm
Length
21 mm
Height
41.5 mm
24.00 mm
Connection data
Connection method
Spring-cage connection
Connection in acc. with standard
IEC 61984
Conductor cross section solid min.
0.08 mm²
Conductor cross section solid max.
6 mm²
Conductor cross section AWG min.
28
Conductor cross section AWG max.
10
Conductor cross section flexible min.
0.08 mm²
Conductor cross section flexible max.
4 mm²
Min. AWG conductor cross section, flexible
28
Max. AWG conductor cross section, flexible
10
Conductor cross section flexible, with ferrule without plastic sleeve min.
0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.
4 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.
0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.
4 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic
0.5 mm²
sleeve, min.
2 conductors with same cross section, stranded, TWIN ferrules with plastic
1 mm²
sleeve, max.
Stripping length
8 mm ... 10 mm
Internal cylindrical gage
A4
Connection method
Plug connection
01/03/2016 Page 2 / 7
https://www.phoenixcontact.com/us/products/3042984
Plug - SP 4/10 - 3042984
Technical data
Standards and Regulations
Connection in acc. with standard
CSA
IEC 61984
Flammability rating according to UL 94
V0
Classifications
eCl@ss
eCl@ss 4.0
272607xx
eCl@ss 4.1
27260701
eCl@ss 5.0
27260701
eCl@ss 5.1
27260701
eCl@ss 6.0
27141151
eCl@ss 7.0
27141151
eCl@ss 8.0
27141151
ETIM
ETIM 2.0
EC000897
ETIM 3.0
EC000897
ETIM 4.0
EC002021
ETIM 5.0
EC002021
UNSPSC
UNSPSC 6.01
30211802
UNSPSC 7.0901
39121402
UNSPSC 11
39121402
UNSPSC 12.01
39121402
UNSPSC 13.2
39121402
Approvals
Approvals
Approvals
CSA / UL Recognized / VDE Gutachten mit Fertigungsüberwachung / cUL Recognized / IECEE CB Scheme / EAC / cULus Recognized
Ex Approvals
01/03/2016 Page 3 / 7
https://www.phoenixcontact.com/us/products/3042984
Plug - SP 4/10 - 3042984
Approvals
Approvals submitted
Approval details
CSA
B
C
mm²/AWG/kcmil
24-12
24-12
Nominal current IN
30 A
30 A
Nominal voltage UN
600 V
600 V
B
C
mm²/AWG/kcmil
28-10
28-10
Nominal current IN
30 A
30 A
Nominal voltage UN
600 V
600 V
UL Recognized
VDE Gutachten mit Fertigungsüberwachung
mm²/AWG/kcmil
0.2-6
Nominal voltage UN
800 V
cUL Recognized
B
C
mm²/AWG/kcmil
28-10
28-10
Nominal current IN
30 A
30 A
Nominal voltage UN
600 V
600 V
01/03/2016 Page 4 / 7
https://www.phoenixcontact.com/us/products/3042984
Plug - SP 4/10 - 3042984
Approvals
IECEE CB Scheme
mm²/AWG/kcmil
0.2-6
Nominal voltage UN
800 V
EAC
cULus Recognized
Drawings
Diagram
Maximaler Belastungsstrom [A]
Circuit diagram
35
30
25
20
15
= 2-pos.
= 5-pos.
= 10-pos.
! = 15-pos.
10
5
!
0
0
10
20
30
40
50
60
70
80
90 100 110
Umgebungstemperatur [°C]
Derating curve for ST 4/ 1P and for all plug versions SP... .
Current carrying capacity [A]
Diagram
35
30
1
25
20
2
4
15
3
10
1 = 2-pos.
2 = 5-pos.
3 = 10-pos.
4 = 15-pos.
5
0
0
20
40
60
80
100
120
Ambient temperature [°C]
The figure shows the derating curve of the ST 4... terminal block in connection with the SP 4 plug
01/03/2016 Page 5 / 7
https://www.phoenixcontact.com/us/products/3042984
Plug - SP 4/10 - 3042984
Diagram
Derating curve for spring-cage terminals ST 4/1P.. and ST 4/2P.. with all plug versions SP 4/... . The derating curves are determined by multiplying the
values of the base curves by the factor 0.8.
01/03/2016 Page 6 / 7
https://www.phoenixcontact.com/us/products/3042984
Plug - SP 4/10 - 3042984
Diagram
Derating curve for the spring-cage terminal with all plug versions SP 4/... .
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
01/03/2016 Page 7 / 7
很抱歉,暂时无法提供与“3042984”相匹配的价格&库存,您可以联系我们找货