https://www.phoenixcontact.com/us/products/2838526
Surge protection plug - CTM 2X1-110AC - 2838526
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
LSA-PLUS plug (COMTRAB CTM) with protective circuit for 2-conductor signal circuits grounded on one side.
Nominal voltage: 110 V AC
The illustration shows version CTM
2x1- 24 DC
Product Features
The CTM 10-MAG surge protection magazine can be freely fitted with various protective plugs
Can be used in LSA-PLUS disconnect and control strips or CT-TERMIBLOCK
Typical installation locations include marshalling distributors
Space-saving LSA-PLUS connection technology
Modular compact protection for high-density networks
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
10.3 g
Custom tariff number
85363010
Country of origin
Germany
Technical data
Dimensions
Height
21 mm
Width
9.5 mm
Depth
53.5 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 75 °C
Degree of protection
IP20
02/09/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/2838526
Surge protection plug - CTM 2X1-110AC - 2838526
Technical data
General
Housing material
PA
Flammability rating according to UL 94
V0
Color
black
Standards for cearances and creepage distances
DIN VDE 0110-1
IEC 60664-1
Overvoltage category
II
Degree of pollution
2
Mounting type
On CT-TERMIBLOCK and LSA-PLUS disconnect strip
Type
LSA-PLUS module
Number of positions
2
Direction of action
Line-Line & Line-Earth Ground
Arrester can be tested with CHECKMASTER from software version:
From SW rev. 1.10
Protective circuit
IEC test classification
B2
C1
C2
C3
D1
VDE requirement class
B2
C1
C2
C3
D1
Nominal voltage UN
110 V AC
Maximum continuous voltage UC
± 180 V DC
125 V AC
Maximum continuous voltage UC (wire-ground)
± 180 V DC
Nominal current IN
380 mA (25 °C)
Operating effective current IC at UC
≤ 5 µA
Residual current IPE
≤ 5 µA
Nominal discharge current In (8/20) µs (Core-Earth)
5 kA
Total surge current (8/20) µs
10 kA
Total surge current (10/350) µs
2.5 kA
Max. discharge current Imax (8/20) µs maximum (Core-Earth)
10 kA (in total)
Nominal pulse current Ian (10/1000) µs (Core-Earth)
100 A
Impulse discharge current (10/350)˽µs, peak value limp
1 kA
02/09/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/2838526
Surge protection plug - CTM 2X1-110AC - 2838526
Technical data
Protective circuit
Output voltage limitation at 1 kV/µs (Core-Earth) spike
≤ 260 V
Output voltage limitation at 1 kV/µs (Core-Earth) static
≤ 15 V
Residual voltage at In (conductor-ground)
≤ 10 V
Residual voltage with Ian (10/1000)µs (conductor-ground)
≤ 10 V
Voltage protection level Up (core-ground)
≤ 260 V (C2 - 10 kV/5 kA, spike)
≤ 10 V (C2 - 10 kV/5 kA, static)
≤ 260 V (C3, 7.5 kV/100 A, spike)
≤ 10 V (C3, 7.5 kV/100 A, static)
Response time tA (Core-Earth)
≤ 1 ns
Input attenuation aE, asym.
0.3 dB (≤ 3 MHz)
Cut-off frequency fg (3 dB), asym. (PE) in 100 Ohm system
typ. 20 MHz
Capacity (Core-Earth)
100 pF (f=1 MHz / VR= 0 V)
Resistance in series
3.3 Ω 10 %
3.3 Ω
Surge protection fault message
None
Max. required back-up fuse
150 mA
Impulse durability (conductor-ground)
C2 - 4 kV/2 kA
C3 - 100 A
B2 - 4 kV/100 A
D1 - 1 kA
Alternating current carrying capacity (conductor-ground)
5A-1s
Connection data
Connection method
can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect
and switching strips
Connection type IN
COMTRAB plug-in system
Connection type OUT
COMTRAB plug-in system
Connection method
LSA-PLUS
Connection, equipotential bonding
Connection method
Spring contact
Standards and Regulations
Standards/regulations
IEC 61643-21
Classifications
eCl@ss
eCl@ss 4.0
27140201
02/09/2016 Page 3 / 5
https://www.phoenixcontact.com/us/products/2838526
Surge protection plug - CTM 2X1-110AC - 2838526
Classifications
eCl@ss
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130807
eCl@ss 7.0
27130807
eCl@ss 8.0
27130807
ETIM
ETIM 2.0
EC000943
ETIM 3.0
EC000943
ETIM 4.0
EC000943
ETIM 5.0
EC000943
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
UL Listed / EAC / EAC
Ex Approvals
Approvals submitted
Approval details
UL Listed
02/09/2016 Page 4 / 5
https://www.phoenixcontact.com/us/products/2838526
Surge protection plug - CTM 2X1-110AC - 2838526
Approvals
EAC
EAC
Drawings
Dimensional drawing
18,5
Circuit diagram
9,4
1
1'
IN
52,4
38
OUT
2
2'
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
02/09/2016 Page 5 / 5
很抱歉,暂时无法提供与“CTM 2X1-110AC”相匹配的价格&库存,您可以联系我们找货
免费人工找货