Primary-switched ESSENTIAL POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC /
120 W
Your advantages
Worldwide use thanks to the wide range input and international approval package
Fast installation, thanks to easy DIN rail mounting
Greater availability, thanks to fanless convention cooling
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4055626464411
Weight per Piece (excluding packing)
674.800 g
Custom tariff number
85044030
Country of origin
Thailand
Technical data
Dimensions
Width
40 mm
Height
123.6 mm
Depth
117.6 mm
Installation distances left/right
10 mm
Installation distances top/bottom
50 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
02/27/2020 Page 1 / 8
https://www.phoenixcontact.com/gb/products/2910586
Power supply unit - ESSENTIAL-PS/1AC/24DC/120W/EE - 2910586
Technical data
Ambient conditions
Degree of pollution
2
Installation height
≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range
85 V AC ... 264 V AC (< 100 V AC derating 1%/V AC)
AC frequency range
47 Hz ... 63 Hz
Discharge current to PE
< 0.25 mA (264 V AC)
Current consumption
2.2 A (115 V AC)
1.2 A (230 V AC)
Nominal power consumption
249.56 VA
Inrush current
typ. 20 A (115 V AC)
typ. 40 A (230 V AC)
Mains buffering time
typ. 20 ms (115 V AC)
typ. 90 ms (230 V AC)
Input fuse
4 A (slow-blow, internal)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±2 %
Setting range of the output voltage (USet)
22 V DC ... 28 V DC (max. power ≤ 120 W)
Nominal output current (IN)
5A
Derating
-20 °C ... -10 °C (2 % / °C)
> 40 °C (1.67 % / °C, 115 V AC)
> 50 °C (2.5 % / °C, 230 V AC)
Max. capacitive load
8000 μF
Active current limitation
105% - 150% of the max. output power (in the event of short circuit)
Residual ripple
< 120 mVPP (-10 °C ... +70 °C)
< 240 mVPP (-20 °C ... -10 °C)
Output power
120 W
Typical response time
200 ms
Maximum power dissipation in no-load condition
0.65 W (115 V AC / 230 V AC)
Power loss nominal load max.
13.3 W (115 V AC / 230 V AC)
General
Net weight
0.54 kg
Operating voltage display
Green LED
Efficiency
85 % (115 V AC)
88 % (230 V AC)
Insulation voltage input/output
3 kV AC
Insulation voltage input / PE
2 kV AC
02/27/2020 Page 2 / 8
https://www.phoenixcontact.com/gb/products/2910586
Power supply unit - ESSENTIAL-PS/1AC/24DC/120W/EE - 2910586
Technical data
General
Insulation voltage output / PE
0.5 kV AC
Protection class
I (with PE connection)
Degree of protection
IP20
MTBF (Telcordia SR-332)
> 700000 h
Assembly instructions
alignable: horizontally 10 mm, vertically 50 mm
Connection data, input
Connection method
Screw connection
Conductor cross section AWG min.
18
Conductor cross section AWG max.
8
Stripping length
7 mm
Connection data, output
Connection method
Screw connection
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
7 mm
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Noise emission
EN 55011 (EN 55022) Class B
Noise immunity
EN 61000-6-2
EN 61000-6-1
Standards/regulations
EN 61000-6-3
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Standard - Electrical safety
EN 60950-1
Standard – Safety extra-low voltage
EN 60950-1 (SELV)
UL approvals
UL/C-UL listed UL 508
Shock
IEC 60068-2-27, 27, half sinusoidal wave: 50g for 11 ms; 3x per
direction, 9x overall
Vibration (operation)
IEC 60068-2-6, sinusoidal waves: 10 Hz ... 500 Hz, 19,6 m/s² (2g peak),
10 min. per cycle, 60 min. in the X direction
Approval - requirement of the semiconductor industry with regard to
mains voltage dips
SEMI F47 - 0706 (200 V AC)
Drawings
02/27/2020 Page 3 / 8
https://www.phoenixcontact.com/gb/products/2910586
Power supply unit - ESSENTIAL-PS/1AC/24DC/120W/EE - 2910586
Dimensional drawing
02/27/2020 Page 4 / 8
https://www.phoenixcontact.com/gb/products/2910586
Power supply unit - ESSENTIAL-PS/1AC/24DC/120W/EE - 2910586
Schematic diagram
02/27/2020 Page 5 / 8
https://www.phoenixcontact.com/gb/products/2910586
Power supply unit - ESSENTIAL-PS/1AC/24DC/120W/EE - 2910586
Dimensional drawing
Block diagram
02/27/2020 Page 6 / 8
https://www.phoenixcontact.com/gb/products/2910586
Power supply unit - ESSENTIAL-PS/1AC/24DC/120W/EE - 2910586
Diagram
Diagram
Classifications
eCl@ss
eCl@ss 5.1
27049002
eCl@ss 9.0
27040701
Approvals
Approvals
02/27/2020 Page 7 / 8
https://www.phoenixcontact.com/gb/products/2910586
Power supply unit - ESSENTIAL-PS/1AC/24DC/120W/EE - 2910586
Approvals
Approvals
EAC
Ex Approvals
Approval details
EAC
EAC*DE*08*02578
Accessories
Accessories
Device protection
Type 3 surge protection device - PLT-EE-T3-230-FM - 2910544
Pluggable device protection, according to type 3/Class III, for 1-phase power supply networks with separate N and
PE (3-conductor system: L1, N, PE) with remote indication contact.
Type 3 surge protection device - PLT-EE-T3-24-FM - 2910540
Pluggable device protection, according to type 3/Class III, for 1-phase power supply networks with separate N and
PE (3-conductor system: L1, N, PE) with remote indication contact.
Phoenix Contact 2020 © - all rights reserved
http://www.phoenixcontact.com
02/27/2020 Page 8 / 8