https://www.phoenixcontact.com/us/products/2817990
Type 2 surge protection plug - F-MS 12 ST - 2817990
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection plug type 2, with N-PE total current spark gap for base element.
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
37.7 g
Custom tariff number
85363010
Country of origin
Germany
Technical data
Dimensions
Height
52.4 mm
Width
17.5 mm
Depth
55.3 mm
Horizontal pitch
1 Div.
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 80 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
Shock (operation)
25g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
05/16/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/2817990
Type 2 surge protection plug - F-MS 12 ST - 2817990
Technical data
General
Standards/specifications
IEC 61643-11 2011
EN 61643-11 2012
IEC test classification
II
T2
EN type
T2
IEC power supply system
TN
TT
SPD design
Voltage-switching type
Mode of protection
N-PE
Mounting type
On base element
Color
jet black RAL 9005
Housing material
PA 6.6
Degree of pollution
2
Flammability rating according to UL 94
V-0
Type
DIN rail module, two-section, divisible
Number of positions
1
Arrester can be tested with CHECKMASTER from software version:
From SW rev. 1.10
Surge protection fault message
optical
Protective circuit
Nominal voltage UN
240/415 V AC (TN - only N-PE)
240/415 V AC (TT - only N-PE)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous voltage UC
260 V AC
Residual current IPE
≤ 5 µA
Standby power consumption PC
≤ 1.5 mVA
Nominal discharge current In (8/20) µs
20 kA
Maximum discharge current Imax (8/20) µs
40 kA
Follow current interrupt rating Ifi
100 A (260 V)
Voltage protection level Up
≤ 1.5 kV
Residual voltage Ures
≤ 0.4 kV (at In)
≤ 0.25 kV (at 10 kA)
≤ 0.15 kV (at 5 kA)
≤ 0.1 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs
≤ 1.5 kV
TOV behavior at UT
1200 V AC (200 ms / withstand mode)
Response time tA
≤ 100 ns
05/16/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/2817990
Type 2 surge protection plug - F-MS 12 ST - 2817990
Technical data
Connection data
Connection method
VALVETRAB plug-in system
UL specifications
SPD Type
4CA
Maximum continuous operating voltage MCOV (N-G)
260 V AC
Mode of protection
N-G
Power distribution system
1
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (N-G)
1490 V
Nominal discharge current In (N-G)
20 kA
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130805
eCl@ss 7.0
27130805
eCl@ss 8.0
27130805
eCl@ss 9.0
27130805
ETIM
ETIM 2.0
EC000941
ETIM 3.0
EC000941
ETIM 4.0
EC000941
ETIM 5.0
EC000941
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
05/16/2016 Page 3 / 5
https://www.phoenixcontact.com/us/products/2817990
Type 2 surge protection plug - F-MS 12 ST - 2817990
Approvals
Approvals
ÖVE / IECEE CB Scheme / UL Recognized / KEMA-KEUR / cUL Recognized / GL / CCA / CSA / EAC / EAC / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
ÖVE
IECEE CB Scheme
UL Recognized
KEMA-KEUR
cUL Recognized
GL
CCA
CSA
05/16/2016 Page 4 / 5
https://www.phoenixcontact.com/us/products/2817990
Type 2 surge protection plug - F-MS 12 ST - 2817990
Approvals
EAC
EAC
cULus Recognized
Drawings
Dimensional drawing
Circuit diagram
52,4
17,5
43,3
55,3
44,8
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
05/16/2016 Page 5 / 5
很抱歉,暂时无法提供与“F-MS 12 ST”相匹配的价格&库存,您可以联系我们找货