https://www.phoenixcontact.com/gb/products/2864587
Temperature measuring transducer - MCR-FL-TS-LP-I-EX - 2864587
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Measurement and control temperature transducers, resistance thermometers, thermocouples, resistance-type
sensors, and voltage sensors. Replacement part: 2908660 MACX MCR-EX-TS-I-OLP.
Your advantages
Input for resistance thermometers, thermocouples, and linear mV signals, Ex ia IIC
Configuration via software
Can be installed in zone 1
2-way electrical isolation
Output: 4 mA ... 20 mA/20 mA ... 4 mA
Loop-powered
1-channel
HART-compatible (MCR-FL-TS-LP-I-EX)
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4017918907266
Weight per Piece (excluding packing)
104.300 g
Custom tariff number
85437090
Country of origin
Germany
Note
Made to Order (non-returnable)
Technical data
Dimensions
Width
12.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
02/27/2020 Page 1 / 6
https://www.phoenixcontact.com/gb/products/2864587
Temperature measuring transducer - MCR-FL-TS-LP-I-EX - 2864587
Technical data
Ambient conditions
Ambient temperature (operation)
-40 °C ... 55 °C
Degree of protection
IP20
Input data
Configurable/programmable
Yes, programmable
Sensor types (RTD) that can be used
Pt, Ni (100, 500, 1000); min. measurement range 10 K
Sensor types that can be used (TC)
B, C, D, E, J, K, L, N, R, S, T, U; min. measurement range 50 K/500 K
Connection technology
2, 3, 4-wire
Input signal range
10 Ω ... 400 Ω (min. measurement range 10 Ω)
10 Ω ... 2000 Ω (min. measurement range 100 Ω)
-10 mV ... 100 mV (min. measurement range 5 mV)
Output data
Signal output
Current output
Configurable/programmable
Yes
Current output signal
4 mA ... 20 mA
20 mA ... 4 mA
Max. current output signal
≤ 23 mA
Output current with short-circuit
≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples)
Output current with wire break
≤ 3.6 mA or ≥ 21 mA (adjustable)
Output current range with overrange/underrange
3.8 mA ... 20.5 mA
Load/output load current output
≤ 520 Ω (At UV = 24 V; Usupply - 12 V / 0.023 A)
Configurable/programmable
no
Power supply
Designation
Loop-powered
Supply voltage range
12 V DC ... 30 V DC
Max. current consumption
< 3.5 mA
Connection data
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Torque
0.5 Nm ... 0.6 Nm
pluggable
no
General
Step response (10-90%)
很抱歉,暂时无法提供与“MCR-FL-TS-LP-I-EX”相匹配的价格&库存,您可以联系我们找货
免费人工找货