https://www.phoenixcontact.com/gb/products/2811103
Voltage measuring transducers - MCR-VAC-UI-O-DC - 2811103
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR voltage measuring transducer, for alternating current voltages from 0..20 V AC to 0..440 V AC, output
signal 0..10 V/0(4)..20 mA
Your advantages
Replacement device MACX MCR-VAC-(PT) 2906239 with 8 measurement ranges from 0 V ... 20 V AC to 0 V ... 660 V AC, output signals:
0 V ... 10 V / 0 (4) mA ... 20 mA
Adjustable voltage ranges
Bidirectional output signals
3-way isolation
ZERO/SPAN adjustment ±20%
Tool-free parameterization of measured values
Teach-in configuration of the measured value range
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4017918125400
Weight per Piece (excluding packing)
204.500 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
02/27/2020 Page 1 / 7
https://www.phoenixcontact.com/gb/products/2811103
Voltage measuring transducers - MCR-VAC-UI-O-DC - 2811103
Technical data
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C (non-condensing)
Maximum altitude
< 2000 m
Degree of protection
IP20
Noise immunity
EN 61000-6-2
Input data
Input voltage range
0 V ... 370 V AC
Input resistance
370 kΩ
Input voltage range
0 V ... 250 V AC
Input resistance
250 kΩ
Input voltage range
0 V ... 170 V AC
Input resistance
170 kΩ
Input voltage range
0 V ... 120 V AC
Input resistance
120 kΩ
Input voltage range
0 V ... 80 V AC
Input resistance
80 kΩ
Input voltage range
0 V ... 54 V AC
Input resistance
54 kΩ
Input voltage range
0 V ... 36 V AC
Input resistance
36 kΩ
Input voltage range
0 V ... 24 V AC
Input resistance
24 kΩ
Nom. voltage
440 V (ungrounded)
250 V (to earth)
Output data
Output name
Voltage output
Voltage output signal
0 V ... 10 V
Max. output voltage
15 V
Load/output load voltage output
> 10 kΩ
Ripple
< 50 mVPP
Output name
Current output
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. output current
30 mA
Load/output load current output
< 500 Ω
Ripple
< 50 mVPP
Power supply
Supply voltage range
18.5 V DC ... 30.2 V DC
Max. current consumption
< 45 mA
02/27/2020 Page 2 / 7
https://www.phoenixcontact.com/gb/products/2811103
Voltage measuring transducers - MCR-VAC-UI-O-DC - 2811103
Technical data
Connection data
Connection method
Pluggable screw connection
Connection technology
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
General
Maximum transmission error
< 1.5 % (of final value)
Temperature coefficient, typical
0.02 %/K (50/60 Hz)
Frequency measuring range
45 Hz ... 400 Hz
Alignment zero
± 20 %
Alignment span
± 20 %
Step response (10-90%)
250 ms
Overvoltage category
III
Degree of pollution
2
Rated insulation voltage
300 V DC
Test voltage input/output
3.3 kV (50 Hz, 1 min.)
Test voltage input/power supply
3.3 kV (50 Hz, 1 min.)
Test voltage output/power supply
1 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2
Color
green
Housing material
Polyamide PA non-reinforced
Conformance
CE-compliant
UL, USA/Canada
cULus
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2
Connection in acc. with standard
CUL
Conformance
CE-compliant
UL, USA/Canada
cULus
Conformance/approvals
Designation
CE
Identification
CE-compliant
Designation
UL, USA/Canada
Identification
cULus
02/27/2020 Page 3 / 7
https://www.phoenixcontact.com/gb/products/2811103
Voltage measuring transducers - MCR-VAC-UI-O-DC - 2811103
Technical data
Environmental Product Compliance
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Application drawing
Voltage measurement in case of grounded circuits
02/27/2020 Page 4 / 7
https://www.phoenixcontact.com/gb/products/2811103
Voltage measuring transducers - MCR-VAC-UI-O-DC - 2811103
Dimensional drawing
Circuit diagram
Classifications
eCl@ss
eCl@ss 4.0
27271100
eCl@ss 4.1
27200300
02/27/2020 Page 5 / 7
https://www.phoenixcontact.com/gb/products/2811103
Voltage measuring transducers - MCR-VAC-UI-O-DC - 2811103
Classifications
eCl@ss
eCl@ss 5.0
27200300
eCl@ss 5.1
27200300
eCl@ss 6.0
27210100
eCl@ss 7.0
27210125
eCl@ss 8.0
27210125
eCl@ss 9.0
27210125
ETIM
ETIM 4.0
EC002477
ETIM 5.0
EC002477
ETIM 6.0
EC002477
ETIM 7.0
EC002477
UNSPSC
UNSPSC 6.01
30211504
UNSPSC 7.0901
39121006
UNSPSC 11
39121006
UNSPSC 12.01
39121006
UNSPSC 13.2
39121006
UNSPSC 18.0
39121008
UNSPSC 19.0
39121008
UNSPSC 20.0
39121008
UNSPSC 21.0
39121008
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / EAC / cULus Recognized
Ex Approvals
Approval details
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
02/27/2020 Page 6 / 7
https://www.phoenixcontact.com/gb/products/2811103
Voltage measuring transducers - MCR-VAC-UI-O-DC - 2811103
Approvals
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
EAC
RU*DE.*08.B.01852-19
cULus Recognized
FILE E 238705
Phoenix Contact 2020 © - all rights reserved
http://www.phoenixcontact.com
02/27/2020 Page 7 / 7