PLT-SEC-T3-230-P-UT/PT 数据手册
https://www.phoenixcontact.com/gb/products/2907923
Type 3 surge protection plug - PLT-SEC-T3-230-P-UT/PT - 2907923
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Replacement plug for type 2/3 surge protection from the PLT-SEC-…-UT/PT product series. Nominal voltage
230 V.
Key Commercial Data
Packing unit
10 pc
GTIN
GTIN
4055626257600
Weight per Piece (excluding packing)
33.160 g
Custom tariff number
85363030
Country of origin
Germany
Technical data
Dimensions
Height
46.7 mm
Width
17.5 mm
Depth
65.7 mm
Horizontal pitch
1 Div.
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 80 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 6000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
Shock (operation)
30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (5 ... 500 Hz / 2.5 h / X, Y, Z)
General
EN type
T2 / T3
12/30/2019 Page 1 / 6
https://www.phoenixcontact.com/gb/products/2907923
Type 3 surge protection plug - PLT-SEC-T3-230-P-UT/PT - 2907923
Technical data
General
IEC power supply system
TN-S
TT
Number of ports
One
Mode of protection
L-N
L-PE
N-PE
Mounting type
on base element
Color
light grey RAL 7035
Housing material
PA 6.6-FR 20 % GF
PA 6.6-FR
Degree of pollution
2
Flammability rating according to UL 94
V-0
Type
Male
Number of positions
2
Surge protection fault message
optical
Protective circuit
Nominal voltage UN
240 V AC (TN-S)
240 V AC (TT)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous voltage UC
264 V AC
Residual current IPE
≤ 5 µA
Nominal discharge current In (8/20) µs
5 kA
Standby power consumption PC
≤ 26.4 mVA (at UREF)
≤ 26.4 mVA (at UC)
Reference test voltage UREF
264 V AC
Max. discharge current Imax (8/20) µs
10 kA
Combination wave UOC
6 kV
Voltage protection level Up (L-N)
≤ 1.25 kV (at UOC)
≤ 1.4 kV (at In)
Voltage protection level Up (L-PE)
≤ 1.4 kV
Voltage protection level Up (N-PE)
≤ 1.4 kV
TOV behavior at UT (L-N)
400 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
TOV behavior at UT (L-PE)
457 V AC (5 s / withstand mode)
457 V AC (120 min / withstand mode)
1464 V AC (200 ms / safe failure mode)
TOV behavior at UT (N-PE)
1200 V AC (200 ms / safe failure mode)
Response time tA (L-N)
≤ 25 ns
Response time tA (L-PE)
≤ 100 ns
12/30/2019 Page 2 / 6
https://www.phoenixcontact.com/gb/products/2907923
Type 3 surge protection plug - PLT-SEC-T3-230-P-UT/PT - 2907923
Technical data
Protective circuit
Response time tA (N-PE)
≤ 100 ns
Short-circuit current rating ISCCR
10 kA AC
Max. backup fuse with branch wiring
32 A (gG / B / C)
Additional technical data
Short-circuit current rating ISCCR
0.25 kA DC (without additional backup fuse)
5 kA DC (for 20 A gG / B backup fuse)
Maximum continuous voltage UC
275 V AC
240 V DC
Mode of protection
(DC+) - (DC-)
(DC+/DC-) - PE
IEC test classification (in accordance with IEC 61643-21)
D1
Impulse durability (line-line)
D1 - 500 A
Impulse durability (line-earth)
D1 - 500 A
Pulse discharge current Iimp (10/350) µs (line-line)
0.5 kA
Pulse discharge current Iimp (10/350) µs (line-earth)
0.5 kA
Connection data
Connection method
pluggable
UL specifications
SPD Type
4CA
Maximum continuous operating voltage MCOV
264 V AC
240 V DC
Nominal voltage
240 V DC
Mode of protection
L-N
L-G
N-G
(DC+) - (DC-)
(DC+) - G
(DC-) - G
Power distribution system
Single phase
DC
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-N)
1150 V
Measured limiting voltage MLV (L-G)
1180 V
Measured limiting voltage MLV (N-G)
1180 V
Nominal discharge current In
5 kA
Standards and Regulations
Standards/specifications
IEC 61643-11 2011
EN 61643-11 2012
12/30/2019 Page 3 / 6
https://www.phoenixcontact.com/gb/products/2907923
Type 3 surge protection plug - PLT-SEC-T3-230-P-UT/PT - 2907923
Technical data
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Drawings
Circuit diagram
12/30/2019 Page 4 / 6
https://www.phoenixcontact.com/gb/products/2907923
Type 3 surge protection plug - PLT-SEC-T3-230-P-UT/PT - 2907923
Dimensional drawing
Classifications
eCl@ss
eCl@ss 10.0.1
27130890
eCl@ss 6.0
27130800
eCl@ss 7.0
27130890
eCl@ss 8.0
27130890
eCl@ss 9.0
27130890
ETIM
ETIM 5.0
EC002496
ETIM 6.0
EC002497
ETIM 7.0
EC002497
Approvals
Approvals
Approvals
DNV GL / CCA / UL Recognized / KEMA-KEUR / cUL Recognized / IECEE CB Scheme / EAC / CSA / cULus Recognized
Ex Approvals
UL Recognized / cUL Recognized / cULus Recognized
12/30/2019 Page 5 / 6
https://www.phoenixcontact.com/gb/products/2907923
Type 3 surge protection plug - PLT-SEC-T3-230-P-UT/PT - 2907923
Approvals
Approval details
DNV GL
CCA
https://approvalfinder.dnvgl.com/
TAE00002U7
NTR-NL 7676
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330181
KEMA-KEUR
http://www.dekra-certification.com
71-103027
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330181
IECEE CB Scheme
http://www.iecee.org/
NL-51083
EAC
RU CDE.A*30.B01561
CSA
http://www.csagroup.org/services-industries/product-listing/
70194378
cULus Recognized
Phoenix Contact 2019 © - all rights reserved
http://www.phoenixcontact.com
12/30/2019 Page 6 / 6
PLT-SEC-T3-230-P-UT/PT 价格&库存