Type 0AFG
240V, BS88‐4 Semiconductor Fuse
RoHS Compliant
0AFG Series
Description
BS88‐4 style stud‐mount Fuse
Features
- High speed semi‐conductor fuse
- Full compliance with EU Directive 2011/65/EU and amending directive 2015/863
Applications
Supplementary protection in appliance
AC/DC, DC/DC module for EV/EV charging
Physical Specifications
Materials
Body : Ceramic
Terminals : Tin Plated Copper
On Fuse :
“bel”,“0AFGX”,”Voltage Rating“,
Marking
“Current Rating ”,”Interrupting Rating”, ”Appropriate Safety Logos”, “aR”
On Label :
"bel","0AFGX”,"Current Rating", "Voltage Rating", "Interrupting Rating",
”Appropriate Safety Logos” and "
", "
"(China RoHS compliant).
Safety Agency Approvals
Safety
Agency
Safety
Agency
Certificate
E491441
Electrical Characteristics
Ampere Rating /
Voltage Rating
Ampere Range / Volt
@ I.R. ability*
25A -180A / 240V AC
25A - 180A / 240V @ 50kA AC
25A -180A / 150V DC
25A - 180A / 150V @ 10kA DC
*I.R.= Interrupting Rating = Short Circuit Rating(Amps)
Total Cleaning I²t
Arc Voltage
Power Loss
The total clearing I²t at rated voltage and at
power factor of 15% are given in the
electrical characteristics. For other voltages,
the clearing I²t is found by multiplying by
correction factor, K, given as a function of
applied working voltage, Eg, (rms).
This curve gives the peak arc voltage, UL,
which may appear across the fuse during its
operation as a function of the applied
working voltage, Eg, (rms) at a power factor
of 15%.
Watts loss at rated current is given in the
electrical characteristics. The curve allows
the calculation of the power losses at load
currents lower than the rated current. The
correction factor, Kp, is given as a function
of the RMS load current, Ib, in % of the
rated current.
Specifications subject to change without notice
belfuse.com/circuit-protection
Type 0AFG
2/3
Temperature Re-Rating Curve
Average Time Current Curve
Operating temperature: -50℃ to 100℃
Electrical Specifications
Part Number
Rated
Current
(RMS-A)
Voltage and
Interrupting
Ratings
Energy Integrals I²t (A²S)
Agency
Approvals
Pre-Arcing
Clearing at 120V
Clearing at 240V
Power
loss
(W)
18
120
250
4
Y
100
500
1400
7
Y
300
1900
3800
10
Y
600
3800
7500
10
Y
0AFGx9250Sxx
25A
0AFGx9500Sxx
50A
0AFGx9800Sxx
80A
0AFGxK100Sxx
100A
0AFGxK125Sxx
125A
600
3800
7500
16
Y
0AFGxK160Sxx
160A
1100
7000
16000
20
Y
0AFGxK180Sxx
180A
1600
12000
29000
21
Y
See Table of Ratings
on Page 1 for
Voltage and
associated
Interrupting Ratings
Consult manufacturer for other ratings
-Typical Pre-arcing I²t are measured at 10In Current
-Power loss provided at rated current
Conditions for operation in service
Where the following conditions apply, fuses complying with this standard are deemed capable of operating satisfactorily without
further qualification.
Normal temperature: -5℃ to 40℃;
The altitude of the site of installation of the fuses does not exceed 2000m above sea level;
The air is clean and the relative humidity does not exceed 50 % at the maximum temperature of 40℃;
Higher relative humidities are permitted at lower temperatures, e.g. 90 % at 20℃;
Under these conditions, moderate condensation may occasionally occur due to variation in temperature.
For operation conditions other than above, please contact manufacturer.
Specifications subject to change without notice
Bel Fuse Inc.
206 Van Vorst Street
Jersey City, NJ 07302 USA
+1 201.432.0463
Bel.US.CS@belf.com
belfuse.com/circuit-protection
© 2023 Bel Fuse, Inc.
Rev. 0AFG May2023
Type 0AFG
3/3
Fuse FGNO Explanation
0AFG X [XXXX] -XX
0AFGB=0AFGB; [XXXX]=Ampere Rating; XX=See Ordering Information as below
Amps
Bel FGNO[XXXX]
25
9250
50
9500
80
9800
100
K100
125
K125
160
K160
180
K180
Mechanical Dimensions
Ordering Information
Packaging
Packaging Option
Quantity
Packaging Code
Bulk
20pcs/box
BA
Specifications subject to change without notice
Bel Fuse Inc.
206 Van Vorst Street
Jersey City, NJ 07302 USA
+1 201.432.0463
Bel.US.CS@belf.com
belfuse.com/circuit-protection
© 2023 Bel Fuse, Inc.
Rev. 0AFG May2023
很抱歉,暂时无法提供与“0AFGBK160SBA”相匹配的价格&库存,您可以联系我们找货