KP Series with PFC
250 Watt AC-DC Converters
Input voltage from 187...255 V AC 1 or 2 isolated outputs up to 56.5 V DC 4 kV AC I/O electric strength test voltage
LGA
• • • •
Rugged electrical and mechanical design Integrated power factor correction No derating over ambient temperature range Special battery charging features
Selection chart
Output 1 Output 2 Input voltage Rated power Type Options
Uo nom
[V DC] 24 24 24 25.25...28.25 25.25...28.25 25.25...28.25 48 48 48 50.5...56.5 50.5...56.5 50.5...56.5 24 24 24
Io nom
[A] 9.6 10.4 11.6 8 9 10 4.8 5.2 5.8 4 4.5 5 4.8 5.2 5.8
Uo nom
[V DC] 24 24 24
Io nom
[A] 4.8 5.2 5.8
Ui
[V AC] 187...255 187...255 187...255 187...255 187...255 187...255 187...255 187...255 187...255 187...255 187...255 187...255 187...255 187...255 187...255
Po tot
[W] 230 250 278 226 254 282 230 250 278 226 254 282 230 250 278 LKP 5662-7R LKP 5660-6R LKP 5661-5R LKP 5742-7R LKP 5740-6R LKP 5741-5R LKP 5662-7R LKP 5660-6R LKP 5661-5R LKP 5742-7R LKP 5740-6R LKP 5741-5R LKP 5662-7R LKP 5660-6R LKP 5661-5R E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1 E, D, P, T, B1
www.power-one.com
Edition 4/04.2001
1
Cassette Style
Input
Input voltage AC Input frequency Power factor Inrush current limitation
KP Series with PFC
187...255 V AC 50/60 Hz >95%
per IEC/EN 61000-3-2 by thermistor
Output
Efficiency Output voltage setting accuracy Output voltage switching noise Line regulation Load regulation Minimum load Current limitation Operation in parallel Hold-up time
Ui nom, Io nom Ui nom, Io nom
IEC/EN 61204, total
Ui min...Ui max, Io nom Ui nom, 0.1...Io nom, symmetrical output load
not required foldback U/I characteristic by current limitation Ui nom, Io nom
up to 86% ±0.6% Uo nom typ. 0.6% Uo nom typ. ±0.1% Uo nom typ. 0.4% 0A typ. 110...100% Io nom 9 ms
Control and protection
Input fuse Input undervoltage lockout Input overvoltage lockout Input transient protection Output Output overvoltage Overtemperature Output voltage adjustment Inhibit Status indication not user accessible 4 AT typ. 80% Ui min typ. 115% Ui max
varistor no-load, overload and short circuit proof suppressor diode in each output switch-off with auto restart TTL input, output(s) disabled if open circuit LEDs: OK, inhibit, overload
typ. 130% Uo nom TC typ. 100 °C 0...110% Uo nom
Safety
Approvals Class of equipment Protection degree Electric strength test voltage EN 60950, UL 1950, CSA 22.2 No. 950 class I IP 30 2 kV AC 4 kV AC 1 kV AC 0.1 kV AC
I/case I/O O/case O/O
EMC
Electrostatic discharge Electromagnetic field Electr. fast transients/bursts Surge Conducted disturbances Electromagnetic emissions IEC/EN 61000-4-2, level 4 (8/15 kV) IEC/EN 61000-4-3, level 3 (10 V/m) IEC/EN 61000-4-4, level 4 (2/4 kV) IEC/EN 61000-4-5, level 3 (2 kV) IEC/EN 61000-4-6, level 3 (10 V) CISPR 22/EN 55022 criterion A criterion A criterion A criterion B criterion A class B
www.power-one.com
Edition 4/04.2001
2
KP Series with PFC
Environmental
250 Watt AC-DC Converters
–25...50 °C –25...60 °C –25...71 °C –25...90 °C –40...100 °C 56 days 0.35 mm/5 gn 100 gn 40 gn 4.9 gn rms 514'000 h
Operating ambient temperature Ui nom, Io nom, convection cooled, -5 Ui nom, Io nom, convection cooled, -6 Ui nom, Io nom, convection cooled, -7 Operating case temperature TC Ui nom, Io nom Storage temperature non operational Damp heat IEC/EN 60068-2-3, 93%, 40 °C Vibration, sinusoidal IEC/EN 60068-2-6, 10...60/60...2000 Hz Shock IEC/EN 60068-2-27, 6 ms Bump IEC/EN 60068-2-29, 6 ms Random vibration IEC/EN 60068-2-64, 20...500 Hz MTBF MIL-HDBK-217F, GB, 40 °C
Options
Electronic inrush current limitation Output voltage adjustment 40...110% Uo nom, excludes feature R and vice versa Input and/or output undervoltage monitoring Current sharing Cooling plate E P D0…D9 T B1
Pin allocation
Pin 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 Vo2+ Vo2+ Vo2– Vo2– Vo1+ Vo1– R i D T N N P P LKP 5000 Output 2 Output 2 Output 2 Output 2 Output 1 Output 1 Control of Uo1 Inhibit Save data Current sharing Protective earth Neutral Neutral Phase Phase
Connector type H15 30 26 22 18 14 10
S10010
6
32 28 24 20 16 12
8
4
www.power-one.com
Edition 4/04.2001
3
Cassette Style
Mechanical data
Tolerances ±0.3 mm (0.012") unless otherwise indicated.
159 (6.25")
KP Series with PFC
European Projection
4.5 (0.18")
7 TE
9 TE
111 (3U) (4.37")
89 (3.50")
Test jacks Option P (Uo) Option D (Uto) Option D (Uti) LED i LED OK LED IoL
Measuring point of case temperature TC
50 (1.97")
171.93 (6.77") (DIN 41494) 168.5 (6.63")
S09002
6.5 (0.26")
80 (3.15")
Accessories
Front panels 19” (Schroff/Intermas) Mating H15 connectors with screw, solder, fast-on or press-fit terminals Connector retention facilities and code key system for connector coding Chassis or wall mounting plates for frontal access Universal mounting brackets for chassis or DIN-rail mounting Temperature sensor for battery charger
www.power-one.com
Edition 4/04.2001
4